Document gb1r8JxrJj4oXOX5p8voE8boa
178
CHAPTER 9
- : 1946.Gu.idc
both forces are acting together, even without interference, the resulting air flow is not equal to the sum of the . two estimated quantities. The flow through any opening is proportional to the square root of-, the sum
of the heads acting on that opening. - - . '
-
When the. two heads are about equal in value and the ventilating openings are operated so as to coordinate them, the total air flow through 'the building is about 10 per cent greater than that produced by either head acting independently under conditions ideal to it. This percentage decreases rapidly.as one head increases over the other' and the larger
will predominate.
. .
The wind velocity and , direction, the outdoor temperature, or the indoor distribution, cannot be predicted with certainty, and refinehient in calculations is not justified ^consequently, a simplified method can be
used. This may be done by using the equations and calculating the-flows produced by each force separately under \conditions of openings best suited for coordination of the forces. Then, by-determining, as a .per centage, the ratio of the flow produced by temperature difference to the sum of the two flows,' the actual'flow'due to the combined forces can be
approximated-from Fig. 3.
- Example-1. .Assume a drop forge shop, 200 ft long,-100 ft wide,.and,30 [thigh. The
cubical content is 600,000 cu ft, and the height of the air outlet _oyer;that of the inlet is
30 ft.: Oil fuel of 18,000 Btu per, pound is used in this shop at the rate of, 15 gal per:Hour (7.75 lb'per "gal). , Desired summer temperature difference is 10 deg and the prevailing
wind1 is 8 mph perpendicular to the'long'dimension'. `-What is the necessary area for the inlets'and outiets, and what is the rate of'air flow, through the building? - ;v.i.'Join-
15 X 7.75 X 13,000"" Solution for Temperature Difference Only, The heat II
' 34,;875 Btu per minute.
-'5By Equation 3, the ak flow required to remove this heat with!an'av<irage'temperature
' difference of lO deg is:
: u-rr;;.'!..': ndrv, bn.';
Natural Ventilation.
179
,,_ H V 0.0175 (1 - h)
34,875 0.0175 X 10
199,286 cfm.
This is equal to about 20 air changes per hour. From Equation 2 the inlet (or outlet) opening area should be:
9.4 ^ A (t - to)
199,286 = 1224 sq ft. 9.4 30 X 10
The flow per square foot of inlet or outlet would be 199,286 -5- 1224 = 163 cfm with all windows open.
Solution for Wind Only. With 1,224 sq ft. of inlet openings distributed around the sidewalls, there would be about 410 sq ft m each long side and 202 sq ft in each end. The outlet area will be equally distributed-on the two sfdes of the monitor, or 612 sq ft on each side. With the wind perpendicular to the long side, there will be 410 sq ft of opening in its path for inflow and 612 in the lee side of the monitor for outflow with the windward side closed. The air flow, as calculated by Equation 1', will be:
Q = 0.60 X 410 X 704 = 173,200 cfm.
This gives 17.3 air changes per, hour, which should be more than ample when there is no heat to be removed.
Solutionfor Combined Heads. Since the windward side of the monitor is closed when the wind is blowing, the flow due to temperature difference must be calculated for this condition, using Fig. 2. This chart shows that when inlets are twice the size of the outlets, in this case 1,224 sq ft in the sidewalls and 612 sq ft in the monitor, the flow will be increased 26.5 per cent over that produced by equal openings. Using the smaller opening and the flow per square foot obtained previously, the calculated amount for this condition will be: ' _
612 X 163 X 1.265 =. 126,200 cfm.
Adding the two computed flows:
. Temperature Difference = 126,200 = 42 per cent.
Wind
= 173,200 = 58 per cent.
Total
299,400 = 100 per cent.
From Fig. 3, it is determined that when the flow, due to temperature difference, is 42 per cent of the total, the actual flow, diie.to the combined forces, will be about 1.6 times that calculated for temperature difference alone, or 201,920 cfm.
The original flow, due to temperature difference alone, was 199,286 cfm with all openings in use. The effect of the wind is to increase this to 201,920 cfm even though half of the outlets are closed. \.
A factor of judgment is. necessary in the location of the openings in a'
building, especially those in the roof, where heat, smoke and fumes are to be removed. Usually windward monitor openings, should be closed,
but if the wind is low enough for the temperature head to overcome it, all windows may be opened. '
TYPES OF OPENINGS
Types of openings may be classified as: (1) windows, doors, monitor openings and skylights, (2) roof, ventilators, (3) stacks connecting to registers, and (4) specially designed inlet or outlet openings:
Windows, Doors and Skylights
Windows have the advantage of transmitting light, as well as providing Ventilating area when open. Their movable parts are arranged'to open in various^ ways; they may open by sliding either vertically or horizon tally, by tilting on horizontal pivots at or near the center, or by swinging on pivots at the top, bottom or side. Regardless of their design, the air flow per square foot of opening-may be considered to be the same under the same conditions. The type of pivoting should receive consideration