Document gaz6BvZjyLJg2drMqeqoMmrDq
240
CHAPTER 14
"1948 Guide
Temperature at-Proper Level: In-making the actual heat loss compu-, tatiidns, however, for the various rooms in a building it is often necessary to modify the temperatures given in Table 2 so that.the air temperature: at the proper level will be used. By air temperature at the proper level is meant, in the case of walls, the air temperature at-'the mean height be-: tween floor and ceiling; in the case of glass, the air temperature at the. leean height of the glass; in the case of roof or ceiling, the/air temperature at .the mean height of the roof or. ceiling above the floor of the1 heated room; and in the case of floors, the air temperature at the floor level.
_ Temperature at Ceiling: The air temperature at the ceiling is generally higher than at the breathing level due.to stratification of air resulting from': the tendency of the warmer, or less dense air to rise. An allowance for this fact should be made in calciilating'ceilirig heatiosses,-particularly in the
Table 2. Winter Inside Dry-Bulb Temperatures Usually Specified3
Type of Building
Deg F`;
' Type.op. Building.
Dbg F :
Schools--
l Toilets and baths......... ........... - Wardrobe and locker rooms....
Kitchens_________ ____________ Dining and lunch rooms. Playrooms Natatoriums..
70-72 68-72 55-65
70 65-68
66 65-70 60-65
75
Hospitals--
Private rooms (surgical)_____ ; Operating rooms.___
Kitchens and laundries . Toilets__
Bathrooms.__^________
70-72 70-80 70-95
68 66 68 70-80
Theaters--
68-72 68-72
68
Hotels-- Bedrooms and baths.Dining rooms_________________ Kitchens and laundries....;____ Ballrooms._____________ .1...____ Toilets and service rooms..
70 70 . 66 65^68 . 68
Homes
Stores......
...... .
Public buildings..-._____ ,___,___ Warm air raths
Steam baths
Factories and machine shops..
Foundries and boiler shops__
Paint shops___ ` "
70-72 65-68 68-72
120 no 60-65 50-60 80
Tbe most comfortable dryrbulb temperature to be maintained depends on the relative humidity and
air motion. These three factors^considered together constitute what is termed the effective temperature.
(See Chapter 12.) When relative humidity is not controlled separately, optimum dry-bulb temperature
for comfort will be slightly higher than shown in Table 2. *-
' -- .
case of high ceilings. However, the exact allowance, to be made may be, somewhat difficult to determine as it depends on many, factors, including(1) the type of heating system, (2) ceiling height, and (3) the insideoutside temperature differential. The type of heating system is par ticularly important as the temperature gradient from floor to breathinglevel to ceiling may depend to a large extent on whether direct radiation, unit heaters or warm air is used, and in. the latter case, whether the circu lation is by gravity, auxiliary fan or forced air. Although with properly adjusted air flow the temperature differential with unit heaters can be reduced to a minimum, it is possible with improper adjustment that it may be increased over that which would normally result without me chanical circulation of the air.
It would be difficult from present available information to establish rules for determining the temperature difference to use in all cases. However, for residences and other structures having ceiling heights under 10 ft, the comparatively small temperature differential between the-
Heating'Load
241
breathing level and ceiling may generally be neglected without serious error. For higher ceilings where specific test data are not available, an allowance of .approximately l,..per cent per foot of . height , above the breathing level may be made for ceiling heights up to 15 ft and approxi mately 1/10 of 1 deg per foot of height above this level. The values in Table 3 are calculated on this basis. For direct radiation and gravity warm air systems, the allowance should be increased from'50 per cent to 100 per cent over those given in Table 3. These rules should, however, , be used, with considerable discretion.
Temperature at Floor-Level: According to the University of Illinois Research Residence testss, the temperature at the floor level ranged from about 2j^ to 6 deg below that at the breathing level, or somewhat greater than the difference between the breathing level and ceiling
Table 3. Approximate Temperature Differentials Between Breathing Level and Ceiling, Applicable to Certain Types of Heating Systems3
Ceiling Height
(Ft)
10 11 ' 12 13 14
15
16 ` 17 18 19 20
25 30 35 40 . 45 : 50
Breathing Level Temperature (5 ft Above Floor)
60 65 70
3.0 3.3 3.5 3.6 3.9 4.2 4.2 4.6 4.9 4.8 5.2 5.6 5.4 5.9 6.3 6.0 6.5 7.0
.6.1 V 6.6 6.2 : 6.7, 6.3. 6.8 6.4 - 6.9 6.5 7.0
.
7.1 7.2
7.3 7.4 7.5
7.0 7.5 8.0 ,8.5 9.0 ` 9.5
' 7.5-'; 8.0 8.5
; . 9.0
9.5 4 10.0
8.0 8.5 9.0
9.5 10.0 10.5
72
3.6 4.3 5.0 5.8 6.5 7.2
7.3 7.4 7:5 7.6 7.7
8.2 , 8.7
9.2 9.7 ,10.2 . 10.7
74 76 78 80 85 90
3.7 3.8 .3.9 4.4' 4.6 4.7
6.2 5.3 5.5 5.9 6.1 6.2 6.7 6.8 7.0 7.4 7.6 7.8
4.0 1 4.3
4.8 5.1 5.6 6.0 6.4 6.8 7.2 7.7 8.0 8.5
4.5 5.4
6.3 7.2
8.1 9.0
7.5 7.7 . 7.9 8.1 8.6 . 9.1 7.6 7.8 8.0 8.2 8.7 9.2 7.7 7.9 . 8.1 8.3 8.8 9.3 7.8 8.0 8.2 8.4 8.9 9.4 7.9 8.1 8.3 8.5 9.0 9.5
8.4 8.9 9.4 9.9 10.4 10.9
8.6 9.1 9.6 10.1 10.6 11.1
8.8 9.3 9.8 10.3
10.8 11.3
9.0 9.5 10.0 10.5 11.0 11.5
9.5 10.0' 10.5 11.0 11.5 12.0
io.o
10.5 11.0 11.5 12.0 12.5
aThe figures in this table are based on an increase of 1 per cent per foot of height above the breathing level (5 ft' up to 15 ft and 1/10 of one degree for each foot above 15 ft. This table is generally applicable to forced air types of heating systems. For direct radiation or gravity warm air. increase values 50 per. cent :to 100 per cent.:
temperatures. Tests at the University of Wisconsin* indicated a some what smaller differential between the floor and breathing level tempera tures. As a general rule,, if the breathing level to ceiling temperature differential is neglected (as with'ceiling heights under 10 ft), the breathing level-floor differential may also be neglected as the two are somewhat compensating, especially where both floor and ceiling heat losses'are !calculated for the same space. In other, cases', the 10 ft temperature differentials in Table 3 may:be used in arriving at the floor heat loss, these differentials to be subtracted from the breathing level temperature. '
ATTIC TEMPERATURES
Frequently it-is necessary to estimate the attic temperature, and in such cases Equation 1 can be used for this purpose.
, ApUcti T to {ArU, -j- Av/Uy/ + AgUg) AtU, + AWUV + AgUs + AcUe
(!)