Document gapqRJEg2ELz9mXwe36KOMrL3

I.L. 10234-F DESCRIPTION OPERATION MAINTENANCE INSTRUCTIONS PNEUMATIC TIMING RELAYS Type AM With or without Auxiliary Switch Units I L FIG. 1. Typa AM Relay With One Auxiliary Switch Unit TYPE AM PNEUMATIC TIMING RELAYS are for general use where it is desired to open or close electrical circuits following a definite time delay. The timing period is initiated by energizing the coil of the "on delay" Type AM Relay or by de energizing the coil of the "off-delay" Type AM Timing Relay. The switch unit, which has the alternating and direct current ratings shown in the table, contains a normally-open and a normally-closed contact. The relay may be supplied with the time delay switch unit alone, or with the time delay switch unit accompanied by one or two auxiliary switch units. The units are identical in rating, but the auxiliary switch units are operated directly by the magnet without introduced time delay. The magnet is designed for operating on alternat ing current only. The operating coils are rated for continuous duty and will operate the relays at from 85 per cent to 110 per cent of their rated volt age. The coils are insulated for 600 volts maximum INSTALLATION Mounting. The relay may be mounted on either insulating or metal panels using the three mount ing holes in the base plate. The relay should be mounted in the vertical position with the graduated regulating valve dial at the top.' OPERATION "Off Delay". The operation of the "off delay" relay is as follows: When the magnet is energized the armature moves upward acting through the dia phragm pin to move the diaphragm upward and ex haust the air promptly from the lower half of the air chamber through the check valve. At the same time the main and auxiliary contacts transfer. When it is intended to start the timing period, the magnet is de-energized, permitting the armature RATINGS OF SWITCH UNIT CONTACTS A-C VOLTS AMPERES Continuous and ' Interrjptinj Capacity , Clasint Capacity D-C VOLTS AMPERES CONTINUOUS AND INTERRUPTING CAPACITY For Inductive Coll Loads | For Non-hdudite | Resistance Loads 110 15 220 10 440 6 550 5 40 125 .30 j 20 250 .IS | 10 1 8 Net*' Switco uait insuUid ior 550 uclia . c and 250 .otts d-c amaua. Both circuits o[ osch switch unit must bo wired for ism# pol.ntr -60 .30 SUPERSEDES I.L. 10234.E 21424 JUNE, 1961 TYPE AM TIMING RELAY. TIME -- SECONDS HO. li. R*1 \t:ve Time Cur/e for Tvj.e AT*' v T irrm Curve o L 21425 TYPE AM TIMING RELAY I.L. 10ZU-F PNEUMATIC TIMING ASSEM3LC ^WUUUlilA/l OFF DELAY TIE PLATE ON DELAY FIG. 3. Conversion from "Off Dslay" to "On Delay" to drop and actuate any existing auxiliary switch units. The operating spring then acts through a lexer to retract the diaphragm pin downward. The movement oi the diaphragm is retarded by the rate at which air can enter the chamber through a re stricted orifice. Transfer of the main switch unit contacts to their normal position takes place before the final V4i inch travel of the diaphragm pin. "On Delay7'. The "on delay" relay is similar to the "off delay" relay except that the magnet is inverted and an additional spring is used to hold the armature open. To start the timing period, the coil is energized and the armature moves down ward, actuating any existing auxiliary switch units. Through the influence of the operating spring, act ing through a lever, the diaphragm pin is retracted downward. The movement of the latter is retarded by the rate at which air can enter the chamber through a restricted Orifice. Transfer of the main switch unit contacts takes place before the final Vb inch of the diaphragm pin travel. When the magnet is de-energized, the return spring lifts the armature and diaphragm pin up ward, exhausting the air promptly from the air chamber through the check valve. The action pro duces a prompt transfer of the contacts of both main and auxiliary switch units. The armature gap in this condition is normally Vis inch. Adjustment. Setting of the time delay is afford ed solely by turning the dial which controls the ori fice of the regulating valve. The timing range is .2 to 200 seconds. To determine the dial setting for a desired time delay, first measure, preferably between 30 and 60 seconds, the time delay produced by a random setting of the dial. Then determine from the curve the number of dial revolutions required to give the desired time delay. Adjust the dial accordingly and check the time delay obtained. Tighten the lock-plate when desired time delay is obtained. The timing calibration of the relay is unaffected by changes in humidity and ambient temperature. The internal parts are kept free from dust by a wool felt filter through which the air entering the cham ber passes. Switch Units. The contacts of the switch units are of a modified transfer type. Adjacent terminals must be wired to have the same polarity. Conversion. An "off delay" relay may be con verted to an "on delay" relay by proceeding as 21426 3 TTP* AM TIMING RELAY follows, referring to Fig. 3. Ramove the magnet inch from the shoulder of the operating pin. Cau mounting screws. Assemble bracket S# ISIS "47 using the .164-32 tion must be used when making this adjustment since very little turning of adjusting screw is re x 'A" fillister head screw and lockwasher. Reas quired to correct the action of the operating lever. semble the magnet assembly to the base plate with After correct adjustment is made, lock adjusting the armature above the coil. Install spring as per screw in this position using the locknut. Fig. 3. Energise the operating coil with the front plate mounting screws loosened. This permits the arma ture to seat itself squarely on the magnet. Tighten front plate mounting screws. TlePlate. The tie-plate is accurately adjusted at the factory when an instantaneous switch is pro vided on the relay. Should further adjustment be necessary, however, proceed as follows: Parts required for conversion: Brsakat Operating Spring fwlster bead screw Lockwasher SS1619 347 Sf 1619 346 .16442 i 'A' .164 Adjustment is accomplished by inserting a screw 1 Required * driver into the slot at the bendable portion of the 11RAceqquuitirrfeeedd-plate adjacent to the pushbutton of the switch 1Requairendd bowing out this section in the direction required. The initial design of the AM relay provided for the above described conversion using a tension spring. These relays may be converted as described above by ordering a new base plate which will have (he angle bracket necessary to provide a seat for the compression spring. Check the adjustment by moving the armature frame assembly to the end of its travel in each direction. The pushbutton of the switch should have a mini mum overtravel of .020* beyond the trip points, and have approximately .015* travel remaining to its bottoming position. Baee plate Ss 1619 348 1RequiredCare must be exercised in bowing out the bend MAINTENANCE able portion of the tie-plate to avoid bending cl the tie-plate at the knife edge. Fallore te Operate. Failure of the armature to cloee may be caused by an open coil circuit, a power Coil Replacement. In order to remove the coil, failure, excessively low voltage or mechanical in first remove the armature and front plate assembly terference. The armature and armature frame by taking out the two screws securing the plato tc should move freely when the diaphragm pin is held the stationary magnet. On the "On Delay" relay it up. The air chamber should not be dismantled for is necessary to remove one of the magnet mounting any reason. Introduction of dust particles into the sgrews and tilt the assembly before the armature check valve will cause a change in the time setting can be removed. Remove the coil by compressing or may cause complete failure of the time delay the coil hangar clips, and pull coil out. Replace with mechanism. the proper coil and reassemble. With those relay' The proper return spring must be used with the having two auxiliary switch units, it is necessary to "on delay" relay. This spring exerts 1.75 lbs. at 1 inch initial length and 2.55 lbs. at 1'/is inch final first remove one of the switch units to expose the front plate mounting screws. length. Opsiatiaf Lewes. The operating lever is accurately adjusted at the factory. If a change in dial setting is required after the initial time setting, it is suggested that this adjustment be checked. To adjust the lever, proceed as follows: Loosen locknut on the adjusting screw, turn the adjusting screw slightly, and- check to see that switch unit operates when operating lever is 'hr Pneumatic aseemhly complete with dining switch unit. ... . .. S* i540 654 A C mevnet i--mhly with Iront plain without coil or switch unit .. . S* 1437 766 '-witch Unit.............................. . . S* 177:3 715 Second Auxiliary Switch, include! witch, mounting hardware and shield................................................5 1776 716 Kickoul spring lor "on delay" relay . . Si 1619 346 Bearing retaining spring..................... SS 1553 647 (Required 2 per relay) WESTINGHOUSE ELECTRIC CORPORATION BSAVER PLANT STANDARD CONTROL DIVISION BEAVER, PA. (Her 2*1) '* 21427