Environment Environnement Canada Canada Environmental Protection Service Service de la protection de I'environnement HONS 00201 PCB HANDBOOK For the Management of Electrical Equipment and Wastes Containing Polychlorinated Biphenyls Prepared by: Contract OSB77-08285 for: Regional Program Report 79-19 Stothert Engineering Ltd. Environmental Protection Service Department of Fisheries and Environment March 1979 HONS 002011 PREFACE This handbook was prepared by Stothert Engineering Ltd. of Vancouver, B.C. to fulfill part of a contract with the Environmental Protection Service of Environment Canada, Pacific and Yukon Region to develop guidelines for the management of electrical equipment and wastes containing polychlorinated biphenyls (PCBs), and to investigate the use of PCBfilled electrical equipment in British Columbia industry. The guidelines presented in this handbook were developed to provide a national code of good practise for the safe handling, management and disposal of PCBs and PCB-containing electrical equipment. The handbook consists of eight booklets providing comprehensive information on PCB management that will be useful to many companies or institutions. Some booklets may be of greater interest and applicability to certain individuals or companies (e.g., those involved in disposal, electrical servicing, etc.), and individual booklets as well as the entire manual are available from the Environmental Protection Service Regional Offices listed in the handbook. Each booklet has a cross-reference index so the reader of any individual booklet can be aware of other topics in the booklet series he may be interested in or require. Inquiries pertaining to the contents of this manual should be directed to the Environmental Protection Service Regional Offices listed in the handbook. HONS 002012 Guide des BPC pourja gestion du materiel electrique et des dechets contenant des biphenyles polychlores realisation du present guide par Stothert Engineering Ltd. de Vancouver repond a certains termes d'un marche passe avec la Region du Paciflque et du Yukon du SPE en vue d'elaborer des lignes directrices rationales pour la gestion (y comprls la manutention et 1'elimination) sure du materiel Electrique et des dechets contenant des BPC et d'etudier 1'usage de ce materiel dans l'industrie de la Colombie-Britannique. Le guide comprend hult brochures ou les entreprises privees et les organisms publics pourront trouver tous les renseignements sur la gestion des BPC. Cornne certalnes brochures peuvent etre plus utiles que les autres 3 certaines personnes ou entreprises (par ex., du secteur de 1'elimination ou de l'entretien), on peut se les procurer individuellement ou toutes des bureaux rEgionaux du SPE EnumerEs dans le guide. Chaque brochure contient un index complet qui renvoie aussl aux autres brochures. Pour plus de renseignements sur la teneur de guide, s'adresser aux bureaux rEgionaux du SPE enumeres dans le guide. HONS 0020X3 HONS 00201** BOOKLET 1: INTRODUCTION TO PCBs Prepared by: Contract OSB77- 08285 for: Stothert Engineering Ltd. Vancouver, B.C. Environmental Protection Service, Department of Fisheries and Environment March 1979 HONS 002015 CROSS - REFERENCE INDEX BOOKLET 1: BOOKLET 2: BOOKLET 3: INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1.5 Federal Government Legislation On PCB 1.6 The Future 1.7 Appendix 1-2 1-3 1-4 1-5 1-6 1-0 1-9 IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix 2-2 2-3 2-6 2-0 2-10 2-15 PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program For Transformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program For Capacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-14 3-15 3-17 MONS 002016 BOOKLET 4: BOOKLET 5; BOOKLET 6: PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4-2 4-3 4_s 4-7 4-8 4-9 4-9 4-10 4-12 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5.1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 5-4 s-7 5-8 s-9 5-13 5-17 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-5 6-9 6-13 HONS 002017 BOOKLET 7: BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGE 7-2 7-3 7-4 7-6 7-7 7-9 8-2 8-3 8-4 8-7 HONS 002018 1-1 FOREWORD This booklet is number 1 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special Interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002019 1-2 1.1 WHAT ARB PCBi? PCB or Polychorlnated Biphenyl is the scientific "name for a man made liquid chemical that has the unique characteris tics of being highly stable, non-corroding, and very fire resistant. There are several different chemical varieties of PCB. These and other unique characteristics heve made it an ideal choice for use inside certain electrical equipment. Its insulat ing properties prevent internal arcing, and its excellent thermal properties conduct heat away from critical internal areas very efficiently. All of these properties are essential to preventing the outbreak of a fire in electrical equipment. Since the 1930s, PCB has been widely used in electrical transformers and electrical capacitors. When used in such equipment, PCB is called "askarel". The PCB is part of a blend with other chemicals. PCB, or askarel, should not be confused with mineral oil. Mineral oil is sometimes used in the same equipment as an alterna tive to askarel. Otter Applications of PCB Besides being used in electrical equip ment, PCBs have been used for a number of years in these types of products: hydraulic fluids, oils, paints, varnishes, resins, inks, carbonless paper, waxes, seal ants, adhesives, caulking compounds, plastics, and asphalts. The reason is the attractive properties of the chemical. PCBs have been used in many common products. HONS 002020 1-3 1.2 HAZARDS OF PCB No electrical equipment will last forever. Eventually it will fail, perhaps even catas trophically while it is in operation. In such an event, there is the possibility that the PCB may contaminate the environ ment. Alternatively, such equipment may face an early retirement by being replaced with more modern equipment. Again, with the removal of the equipment there is the possibility that the PCB may contaminate the environment. From the time that askarel equipment is first installed, the problem of PCB management is extremely important. The hazards from PCB contamination are serious. As well as having many attractive chemical properties, PCB has the very unattractive property of essentially being non-biodegradable. This means that PCB will not break down easily in nature. In fact, studies have shown that certain types of PCB require more than SO years before they can decompose sufficiently to be acceptable in nature biologically. In the meantime, PCB contamination can do its damage to human health and the environment. Hazard to the Environment Scientific observations of marine life, birds and small mammals have shown that PCBs can produce cases of decreased growth in the newborn, interference with the reproduction cycle, degeneration of organ tissues, and mortality. There could, of course, be many other areas which have not been monitored but which could also contain high concentra tions of PCB. A small quantity of PCB liquid can cause a high level of contami nation in a local area. PCB is also present in sewage sludge, therefore, caution should be exercised in using sewage sludge as a fertilizer. Hazard to Human Health In 1968, over 1,000 people in southwest Japan consumed rice oil which was con taminated by one type of PCB. The contamination resulted from PCB-filled equipment in the food processing plant leaking some of its contents onto a ship ment of rice oil. It was an unnoticed industrial accident. The result was that people who consumed the rice oil over an extended period of time (it was estimated to be approximate ly 1/2 to 1-1/2 grams of PCB consumed per person) developed cases of skin erup tions, swelling of the eyelids, eye discharge, skin and nail pigmenting, and visual and digestive disturbances. They also had a higher incidence of malignant tumours than would have been expected. Some of the infants bom to the poisoned mothers had below normal birth weights and exhibited skin discolouration. Recent studies have shown that since PCB does not degrade, it can bind itself to cellular tissue, and that this in turn may cause the formation of cancerous tumours. Several areas in Canada presently have widespread PCB contamination in aquatic life. These include the Great Lakes, the St. Lawrence River, the Atlantic coast and the Pacific coast. MONS 002021 1-4 1.3 HOW DOBS PCB-CONTAMNATION OCCUR? The 1968 incident in Japan is an obvious case of PCB poisoning. There are other less obvious ways in which PCB may contaminate the environment and create a hazard to human health. PCB In Water PCB which leaks from damaged or rusted electrical equipment or which is spilled onto the ground can eventually seep into streams, rivers and lakes. It may also inadvertently be poured directly into sew age drains for disposal. Once into the environment, the PCB contamination can be accumulated In the bodies of all types of life. The contami nation is then passed on through the "food chain". For example: fish will ingest PCB in the water; game and animals will consume the contaminated fish; and man will consume the contaminated fish, game, and animals. PCB In Air Liquid PCB will vaporize and become airborne through improper incineration. It will then be dispersed by the wind and deposited back to the earth in rain and snowfall. For this reason, askarel liquids and other products containing PCB should never be burned. Scientists are presently studying the feas ibility of using special high temperature furnaces having temperatures in excess of 1000 C., for the destruction of PCBs. Exposure on the Job Some individuals who are involved in maintenance of electrical transformer and capacitors, or who are involved in the clean up of askarel leakage can accidentally come into contact with the liquid. If askarel is accidentally splashed on unprotected skin it can cause some types of skin irritation. The extent of the irritation depends upon how long the askarel is allowed to remain on the skin. Prolonged contact on unprotected, sensi tive skin can lead to drying, chapping or perhaps the development of a rash. These skin irritations are surface condi tions only. In addition, they are not contagious so they will not be passed from one person to another. Similar conditions may also result from exposure to paint thinners. Government Standards of Contamination Government standards declare that any substance that contains more than 0.01% by weight or 100 ppm of PCB is consider ed to be contaminated, and must be treated as a PCB substance. Examples include: - askarel fluids - mineral oil contaminated with PCB - certain hydraulic 8c heat exchange fluids - rinsing solvents - components from askarel-filled trans formers 8c capacitors, 8c heat transfer systems - containers for PCB waste 8c unused fluids Since one electrical transformer can contain upwards of 100 gallons of PCB askarel, this amount, if allowed to reach a water system, could potentially contami nate a very large area. In actual fact, however, unless the askarel from a spill is strongly agitated by waves, etc., it will tend to collect in pools at the bottom of the water body. The level of contamination will decrease as the distance from these pools increase. Unfortunately, once traces of PCB are in water, they cannot easily be removed by filtering, adding chemicals or boiling. Nor HONS 002022 1-5 can the contamination be seen with the naked eye. For more information on the extent of contamination that can occur with PCB, see Booklet 6 under "Clean Up Procedures". 1.4 B PCB STILL AVAILABLE? PCBs have always been imported into Canada rather than being manufactured here. There are presently no known manufacturers of PCBs in Canada. In 1971, the major importer of PCB liquids into Canada began restricting the sale of the product, selling only to electrical equipment manufacturers from that point on. In 1977, the major supplier of PCBs to North America discontinued production of these chemicals altogether. PCBs are still available from other countries, but with the introduction of new Federal regulations under the Environmental Contaminants Act, it will be prevented from being imported into the country. Manufacturers are presently working on developing substitute chemicals to replace PCBs in many applications. HONS 001023 1-6 1.5 FEDERAL GOVERNMENT LEGISLATION ON PCBs PCBs are everywhere In the environment. They are in varying concentrations in water, air, soil, sewage sludge, and in many types of life. To prevent further concentrations of PCB from contaminating the environment, the Government of Canada has been preparing special regulations under the Environ mental Contaminants Act. These regula tions will ban the use of PCBs in certain applications in the future. The ban will, however, allow PCBs to be used in certain other applications where control can be maintained to prevent contamination of the environment. The Canadian Environmental Contami nants Act is in addition to the Federal Fisheries Act, which is already in effect to proseoute individuals who discharge or who allow to be discharged, harmful substances such as PCB into waters frequented by fish. See the Appendix for a fact sheet on the Environmental Contaminants Act. The United States also has regulations pertaining to the control of PCBs. The regulations under the Environmental Contaminants Act are Included in the Appendix of this booklet. Interpretations of the regulations are provided here for reference purposes: Initial RagulaUoas As of September 1, 1977, the following restrictions were in effect under the Environmental Contaminants Act: 1. The regulation produced the restric tion that certain products may no longer be manufactured in Canada or imported into the country if they contain PCB. These products include: - Paints - Varnishes - Laquers - Resins - Inks - Pigments - Waxes - Adhesives - Caulking compounds - Sealants - Carbonless copy paper - Hydraulic fluid - Cutting oils - Oils - Lubricants - Rubbers - Petroleum additives - Plasticizers - Pesticide extenders - Dedusting agents - Fire retardants - Heat transfer fluids - Vapour diffusion fluids Such products are still allowed if substitute chemicals for PCB are used. 2. Certain equipment and machinery may no longer be manufactured in Canada or imported into the country if it uses PCBs. These include: - Heat transfer equipment - Hydraulic equipment - Vapour diffusion pumps 3. PCB may not be used for operating, servicing or maintaining any new installation of the types of equipment and machinery listed in item 2. These initial regulations did not apply to any PCB products, equipment or machinery which were manufactured in or imported into Canada before September 1, 1977. The intention was to prevent any new uses or installations of PCB in Canada, except for electrical capacitors, electrical transformers and associated switchgear. HONS 00202A 1-7 Proposed Regulations Proposed amendments to the intitial regulation would include these restrictions as of January 1, 1979: 1. PCB may not be used for operating, servicing or maintaining any new or already installed equipment and machinery such as: - Heat transfer equipment - Hydraulic equipment - Vapour diffusion pumps 2. The following electrical equipment will no longer be allowed to be manu factured in Canada or imported into the country if it uses PCBs: - Electrical capacitors - Electrical transformers - Electrical switchgear 3. PCBs will not be allowed for servicing electrical capacitors. These capa citors will have to be disposed of instead. 4. PCBs will not be allowed as a new filling or for make-up fluid In the servicing of electrical transformers or electrical switchgear. Substitute chemicals will have to be used instead. The PCB regulations may appear very demanding; however, they are designed to protect the Canadian public. At the present time there are no other feasible alternatives for halting the increasing contamination of our environment. Note The interpretation of these regulations is that of Stothert Engineering Ltd. and does not necessarily represent an interpret ation by the Government of Canada. This interpretation is also limited to the Chlorobiphenyl Regulations No. 1 and the proposed amendment shown in the Appendix of this booklet. Changes to the proposed amendment are presently being considered by the Environ mental Protection Service. When the final regulations are available, this page will be revised and reissued to all in receipt of this booklet. The Federal Government is also consider ing regulations which would pertain to: - the control of PCB releases to the environment. - record-keeping of PCB equipment and PCB-wastes. a resale prohibition on used PCB equipment and machinery. HONS 002025 1-8 1.6 THB PUTURB Due to the limited supply of PCBs in recent yean, and due to the Increasing knowledge about the hazards of PCB, many manufacturen of transformers and oapaciton discontinued production of their equipment, before the regulations came into effect. The future holds many challenges. There are a tremendous number of products presently in use or in storage which contain PCBs. Now comes the challenge of keeping watch over these PCB products, equipment and machinery to ensure that no situations develop which could accidentally release quantities of PCB into the environment. It is hoped that this booklet along with the other seven in this series will provide the informative instructions to meet that challenge. HONS 002026 1-9 1.7 APPENDIX HONS 002027 1-10 ENVIRONMENTAL PROTECTION SERVICE OFFICES Redon Pacific Northwest Ontario Quebec Atlantic Address Teleohone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5840 Environmental Protection Service 4th Floor 1550 de Maiaonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J IMS Emergency (902) 426-6200 Office (902) 426-6141 HONS 002028 28/9/77 Canada Gatelte Fan II. Voi. III. No. 18 Gazette du Canada Fame II. Voi. III. N* 18 SOS/DORS/77-734 Registration SOR/77-734 7 September, 1977 Enregiatrement DORS/77-734 7 septembre 1977 ENVIRONMENTAL CONTAMINANTS ACT CMorobipfcenyl Regulations No. 1 LOI SUR LES CONTAMINANTS DE L'ENVIRONNEMENT Rtglement sur les bipMiyln cfclorts (r 1) PC 1977-2470 31 August. 1977 C.P. 1977-2470 31 aoOt 1977 Wherds i copy of the proposed Regulation substantially in the form set out in the schedule hereto, was published in the Canada Gazette Part 1 on February 26, 1977; And Whereas no notice of objection was Hied with the Minister pursuant to subsection 5(3) of the Environmental Contaminants Act. Therefore. His Excellency the Governor General in Council, on the recommendation of the Minister of Fisheries and the Environment and the Minister of National Health and Wel fare. pursuant to paragraph I8(r) of the Environmental Con taminants Act. is pleased hereby to make the annexed Regula tions prescribing certain uses in respect of which certain chlorobipbenyls may not be used. Vu qu'une copie du Riglcmcnt proposd esienueHcnteni dans la forme expoabe 4 I'anncxe ci-aprts a 6(4 public dam la Gazette du Canada (Partie I) le 26 ftvrier 1977; Et vu qu'aucune objection n'a 6t6 formuitc at mimstre en vertu du paragraphe 5(3) de la Loi sur les contaminants de I'environnement. A ces causes, sur avis conformc du ministre do Pdchencs et de I'Environnement ainai que du ministre de la Sam6 ftatienak et du Bien-4trc social et en vertu de I'aiinda II c) de le Loi sur lo oontaminants de I'environncment, il plait 4 Sen Fwnllenre le Gouverneur gdndral en conscil de mettre en vigueur le Rdglemenl ci-annex6 interdisant certains emploii da eartains biphdnyles chlor4s. REGULATIONS PRESCRIBING CERTAIN USES IN RESPECT OF WHICH CERTAIN CHLOROBIPHENYLS MAY NOT BE USED Short Title 1. These Regulations may be cited as the Chlorobiphenyl Regulations /Vo. /. REGLEMENT INTERDISANT CERTAINS EMPLOIS DE CERTAINS B1PHENYLES CHLORES Titre abrige 1. Reglement sur les biphinyles chlores fir I). Interpretation 2. In these Regulations. ``Act ' means the Environmental Contaminants Aer. "chlorobtphenyls" means thcae chlorobiphenyls that have the molecular formula CnH,*.Cl,, in which "n" is greater than 2; "Minister" means the Minister of the Environment. Definitions 2. On emend per biph6nyles chlordt* lo byphinyles dont la formula moibcu- taire esi C|,H14..CI. oil n ot plus grand que 2. loi* la Loi sur les contaminants de I'enviromement, ministre* le ministre de I'Environnement Prescription of Uses 3. For the purpose of subsection 8(2) of the Act, the following commercial, manufacturing and processing uses sre hereby prescribed effective September I. 1977. as uses in respect of which chlorobiphenyls may not be used; (a) use in the operation, servicing or maintenance of any product, machinery or equipment other than 0) electrical capacitors, electrical transformers and associated switchgear and machinery or equipment used to manufacture electrical capacitors, electrical transform ers and associated switchgear, (ii) beat transfer equipment, hydraulic equipment and vapour diffusion pumps that were designed to use Emplois interdits 3. Pour Tapplicalion du paragraphe 8(2) de la Lot. lo emplois suivants des bipbinylo chlorts dans le commerce, le fabrication et la transformation sont interdits 4 compter du l" septembre 1977: a) les emplois dans I'expioiiation, la rdparation et I'entretten de tout produit. machinerie ou 6quiptmcnt sauf: (i) lo condenseteun tlectriquas, lo transfermateurs 4lectriquo et I'appareiUage connate at le machinerie ou rtquipement servant 4 leur fabrication, (li) tout matdriel de transfer! de le cheleur. tout metdrkl hydraulique ou toute pompe 4 diffusion de vepeur stilidi au Canada avnnt le 1" mars 1977 et dont la conception exige I'emploi de biph6nylo chlords et m 4229 HONS 002029 11/9/77 CaimdaGaztttt Part If. Voi. Ill, Na. 18 Gaxttudu Canada Portit If. Vol. Ill, N* 18 3Qfc/nnmy/T>_TM eblorobipbenyls and were in use in Canada before March I. 1977, and (iii) machinery or equipment, the operation of which is intended to destroy the chemical structure of chlorobiphe* nyli; and (6) use as a constituent of any machinery, equipment or product manufactured in or imported into Canada after September t, 197? other than electrical capacitors, eiectri* oal transformer! end associated switchgear. (iii) la machinerie ou I'dquipemcnt dcMindt i ddtmire la structure chimique des bipMnylcs chlorda et b) les emplois dans les produHs, la machinerie ou I'lquipe* ment fabriquds ou import4s au Canada aprts le 1* leptcm- bre 1977, sauf les condenuteurs ilectriquea, lea traaaforma* teurs ilectriques et I'appareiilagc conncxe. quibni raiNTUt roa Canada. Ottawa, i m 4130 IMMtlMEUR DE LA HEINE HOUH LE CANAOA. OTTAWA, IfT? (21 HONS 002030 La 2 ddctmbrt 197g La Caxette du Canada Parti* / 7117 DEPARTMENT OF FISHERIES AND THE ENVIRONMENT ENVIRONMENTAL CONTAMINANTS ACT Proposed Amendment io Chlorobtphtnyl Regulations So. / Notice is hereby given, pursuant to subsection 3(2) of the Environmental Contaminants Act, that the Minister of the Environment and the Minister of National Health and Welfare (a) have consulted with the governments of the provinces and appropriate departments and agencies of the Govern* ment of Canada pursuant to subsection 3(1) of that Act in order to determine whether the significant danger that the entry of chiorobiphenyls into the environment wilt constitute in Canada to human health or the environment will be eliminated by any action taken or proposed to be taken pursuant to any other law; \b) are satisfied that the significant danger referred to in paragraph (a) "ill not he eliminated by any action taken or propositi to be taken pursuant to any other law; and (r) propose to recommend to the Governor General in Council that Chlorobiphenyl Regulations No. 1 made by Order in Council PC. 1977-2470 of 31 August. 1977 be amended pursuant to paragraph 18(c) of the Environmental Contaminants Act to further restrict the use of ehlorobiphenyls in accordance with the following schedule. Any person having an interest therein may within sixty days of the publication of this notice Hie a notice of objection with the undersigned. Given at Ottawa, this seventh day of November. 1978 LEN MARCHAND Minister ofthe Environment ministEre des pEches et de L'ENVIRONNEMENT LO! SUR LES CONTAMINANTS DE LENVIRONNEMENT Projet de modification au Reglement sur Its biphenyles chlores (tf 1} Avis est par les pr*sent donn*. conformtment au paragraphe 3(2) de la Lot sur les contaminants de lenvironnemem. que )e minittre de PEnvironnemem et le mmistre de la Sami nationale et du Bien-itre social ) ont consult* les gouvemements des provinces ainsi que les rainist*res et organismes competent! du gouvemement du Canada, scion le paragraphe 3(1) de ladite Loi. afin de determiner si le danger riel que oonatitue pour la same ou t'environnemem la presence des biphenyles chferds dans 1`environnement au Canada, sera *ltmin* par des mesures prises ou projetfces en application de quclque autre loi. ) sont convaincus que le danger vise * I'alinda a) ne sera pts eiimine par les mesures en question, et c) sc proponent de recoinminder au gouverncur general en conseii qu'il modifie, conformement 8 I'alinea lie) de la Loi sur les biphenyles cMoris <tr l), le Rigtement sur Its biphenyles chlores In* 1} dtsbii par le dtcrei C P 1977-2470 du 31 aoflt 1977, afin de r*duire davantage 1`emploi des biphenyles chlores. Tout interesse pent, dans les soixantc jours de la publication de cet avis, deposcr un avis d'opposition aupr*s du soussign*. Ottawa, ce 7* jour de novembre 1978 Le mmistre d'itat lenvtronnementi LEN MARCHAND SCHEDULE ANNEXE 1. Section 3 of tht Chlorobiphenyl Regulations No. 1 it revoked end the following substituted therefor: *'3. For ihe purpose of subsection 8(2) of the Act. the following commercial, manufacturing and processing uses are hereby prescribed as uses in respect of which chiorobiphenyls may not be used: (e) effective January I. 1979, use in the operation of any product, machinery or equipment other than (i) electrical capacitors, electrical transformers and associated switchgear; <ii> heat transfer equipment, hydraulic equipment, elec tromagnets. and vapour diffusion pumps that were designed to use chiorobiphenyls and were in use in Canada before March I. 1977; and (iii> machinery or equipment, the operation of which is intended to destroy the chemical structure of chiorobiphenyls; l. L'artide 3 du Reglement n* I sur les biphenyles chlores eat ainsi remplac*: 3. Aux fins du paragraphe 8(2) de la Loi, la empiois suivants da biph*nyl chlores dans la operations commercities, la fabrication et la transformation sont interdits: a) * compter du I* janvier 1979, dans ('exploitation de tout produit, machincrie ou equipemem sauf: (i) la condensateurs electriqua, la transformateurs ilectriques et 1'appareillage connexe: (ii) riquipemem de transfer! de chaleur, I'iquipemeni hydraulique. les ilectro-aimants et la pompa 8 diffu sion de vapeur confus pour utiliser da biphenyles chlores et mis en service au Canada avant le I" mars 1977; (iii) la machinerie ou requipameni datinds 8 detruirc la structure chimique des biphenyles chlores; HONS 002031 71)8 Tht Canada Gatttte Part ! December 2. 1979 (b) effective January I. 1979, use in the operation of electromagnets that are used to handle food, animal feed or anything intended to be added to food or animal feed for any purpose whatsoever: (r) use as a constituent of any product, machinery or equipment manufactured in or imported into Canada after September I. 1977. other than electrical capacitors, electrical transformers and associated switchgear; (d) use as a constituent of electrical capacitors, electrical transformers and associated switchgear manufactured in or imported into Canada after January 1. 1979; (e) use. after January I. 1979. in the servicing or mainte nance of any product, machinery or equipment, other than electrical transformers and associated switchgear; and (/) use. after January I. 1979. as new filling or at make up fluid in the servicing or maintenance of any electrical transformer or associated switchgear " la-M 6) i compter du I" janvier 1979, dans ['exploitation d'tlectro-aimams qui servent 8 manutentionner ls ali ments destines i I'hommc et aua animaus au leura additifs; c) dans les produits, la machinerie ou I'tquipemem fabriques ou importes au Canada aprts le I*' septembre 1977. sauf les condensateurs electriques. les transformatcun Electriques et 1'appareillage connexe; d) dans les condensateurs Electriques, les transformateurs Electriques et 1'appareillage connexe fabnques ou importEs au Canada aprEs le I* janvier 1979; r) aprEs le l" janvier 1979. dans !a reparation et I'eniretien dea produits. de la machinenc ou de rtqutpemcni autres que les transformateurs electriques et 1'appareillage connexe; et f) aprEs le 1* janvier 1979. comme nouveau flutde de remplissage ou comme fluide d'appotnt pour la reparation ou I'entretien des transformateurs electriques et lappareillage connexe.* HONS 002032 1+ Environment Environnement Canada Canada FACT SHEET I* Hearth and Welfare Sante at Bien-etre sooa' Canada Canada Environmental Protection Service HONS 002033 Environmental Contaminants Act Number 4 The Neture of the Problem Many substances enter the en vironment in quantities, concentrations or under conditions that harm the envi ronment end thereby men. The Envi ronmental Contaminants Act is de signed to assist in protecting human health and the environment from such substancss. Where s substance is known to pose a direct threat to human health, controls can bs imposed under present federal snd provincial legislation. How ever, many substances may not pose a direct threat but, through their release to the environment, may cause longrange adverse effects to ecological systems and may also pose an indirect threat to human health. In addition to s variety of poten tial adverse health affects, the con sequences of contamination of the en vironment by substances inctuda a loss of food species, curtailment of im portant economic activities snd s van- tty of irreversible ecological changes that threaten man $.future use end en joyment of the living world. The most troublesome sub stances have some common charsctanatics: - they may become widely dispersed in the environment: - they may be highly persistent and accumulate indefinitely in the envi ronment; - they may be accumulated in biologi cal tissues end pass through food ehains; - they may causa biological changes St trees concentrations; - they may be irretrievable once dis persed in the environment end - they may enter the environment in many ways from large number of tourcaa. Ths magnitude of the problem is difficult to visualizs but some relevant facts art avertsbis. - A few million chemicals are known to science. Of these, according to a Japanese Government Hat. about 20.000 are in commercial use. - The U.S. Department of Health, Edu cation and Welfare has a published list of 15,000 tonic chemicals, an un known number of which are in com mercial use. - It has been estimated on the basis of U.S. information that about 500 new chemicals are introduced into com mercial use each year end it is esti mated that about \0% of these new chemicals ere likely to cause concern. Effective management of new substances that enter commerce re quires investigation and prediction (of their biological effects end of how they enter the environment) end the applica tion of controls designed to prevent their entry into the environment in quantities, concentrations or under conditions deemed unacceptable. The government is concerned bout the lack of pertinent knowledge of the safety or hazard of existing chemicals and new chemicals. It is concerned about the variety of new widespread uses of existing chemicals. It is concerned about the introduction of new chemicals into commercial use. The Sphere of the Environmental Contaminants Act There ere a number of federal snd provincial lews that deal directly or indirectly with contamination of the environment. There are three categories: ) Media-oriented legislation (eg. Fiahtnea Act. Dean Air Act), which seeks to control the dis charge of poNutants into a given medium, e.g. water or air b) Product-oriented legislation (e g. Hazardous Products Act), which deals with certain products and their constituent chemical com ponents with respect to their hazard to men. c) Subetance-onented legoletion (e.g. Pest Control Products Act) whereby the adverse effects of potentially dangerous substances ere reviewed and the use of the chemicals may be restricted. The new Environmental Conta minants Act is in cagetory c) and pro vides the government with the power to obtain a systematic overview of the problem of contammetion of the envi ronment by e substance regardless of source, use. product or meefca. and to apply the appropriate controls, if nec essary, in those cases where other leg islative authority does not exist or is not used. The Act has four characteristics e) The focus is upon substances b) It is comprehensive Ail relevant facets of production, use. dis posal and sources of entry of a substance into the environment can be examined to find our what controls, if any. should De imposed. No special activities are exempted from the ambit of the Act. c) Because of its comprehensive scope, it was necessary witnm the Act itself to define the re lationship of the Environmental Contaminants Act to other laws in the application of controls The Act is designed to operate as s back-up to other laws, fed eral or provincial The control provision is intended to apoly only where other authomies fail or neglect to implement aooro pnate controls. These control provisions of the Act are in tended to be residuary d) Because of the long term nature of problems creeled by environ mental contaminants the gov- emment intends to street the preventive poets of the Act. For this to be affective, one must know or be able to predict whet likely to take piece in the future. For example, it is neces sary to know or to be able to predict biological effects of chemicals present in the environ ment st trace concentrations. Hence the Act contains wide powers to collect information and to require testing. Mein Features of the Act The Act has two main features. One is the power to undertake system atic investigation of substances or classes of substances in order to de termine their fete in commerce and in the environment. Under Section 4, in dustry may be required to submit data on imports and production as well as details of processes, impurities and lo sses to the environment. Furthermore, industries may be required to carry out testa reapacting tha physical, chemical and biological propsrtiss of ssiactad substances to improve the under standing of what threats they may pots. An integral pan of the in vestigation will be an assessment of the potential impact of a substance, leading to e risk decision by the Gov ernment ss to first, the likelihood of the entry of that substance into the environment, end second, whether it constitutes a significant dinger to human health or the enwronmem. The other mam feature of the Act is concerned with controls. Sec tions B and tB of the Act which should be read together contain comprehen sive powers to restrict or prohibit 1. the release of e named sub stance into the environment 2. the use of that substance for certain purposes, or 3. the incorporation of it in s manu factured product. Controls under the Act will be ef fected by adding a substance or class of substances to a schedule to the Act and by prescribing regulations to pre vent the entry of the substance into the environment in quantities, concen trations or under conditions deemed unacceptable. The Schedule, therefore, will be a list of substancas and classes of substances that the Government believes pose a significant danger to human health and the environment, end for which regulations have been prescribed under the Act. Other Features of the Act Subsection 446) requires compa nies that manufacture or import a chemical compound for the first time in excess of 500 kilograms in a year to notify the Government. The notification must include the name of the chemical compound, of the quantity produced or imported and of any information the company has regarding the chemical's hazards. This provision of the Act will alert the Government to new chemicals that ere attaining commercial im portance. Subsection 31) requires companies to detail their immediate pest end future trade in these chem icals to bt specified from time to time, h will also enable the Government to identify, in advance, the prospective in crease in the commercial use of a chemical and thereby to obtain a warn ing of possible future difficulties with it. If the Government becomes con cerned about a substance or class of substances presently in commercial use. it may, under Subsection 4(1). re quire companies dealing in that sub stance to supply the Government with information, to assist in an evaluation of its safety or hazard. Before publishing the proposed regulations and scheduling a sub stance. the Government must, under Subsection 5(1). offer to consult the provinces. Withm sixty days of publication of tha terms of e proposed regulation control under the Act. company may, under Section 6. require e Board of Re view. The Board will inquire into the nature of the danger posed by the sub stance and shall give interested and knowledgeable persons an opportunity to be heard. After the Board has issued its report the government may add that substance to the Schedule end prescribe regulations for its control. The Government may take action to deal with emergencies but may have to establish a Board of Review. The Act contains several sactions concerning enforcement such as in spection, seizure, analysis. These sec tions are similar in form end intern to those found in other federal acts Those persons not complying with the regulations, ere liable to fines of up to $100,000 or to imprisonment for up to 2 years. Administration of the Act The Act is the joint responsibility of the Departments of Environment end National Health and Welfare. The latter will be concerned with human health matters and Environment Can ada will assess the ecological and envi ronmental impact of chemicals Envi ronment Canada. through the Environmental Contaminants Control Branch, will administer tha Act in co operation with other D.O.E. Services and National Health and Waifara. As indicated in Section 3 of the Act the advice and support of a vanary of agencies, federal, provincial and non governmental, wiH be sought and uaad. This wiH be parbeuiarty important m the development end effective imple mentation of the preventive aspect of the Act. which requires an Early Warn ing System to pinpoint problems and to predict future levels of environ mental contaminants and their hazards. HONS 002034 For more information. Public information. Environmental Protaction Sarvica. Environment Canada, Ottawa. Ontario, K1A0H3. or Any regional office of the Environmental Protection Service of Environment Canada. Booklet 2 MGNS 0CU035 BOOKLET 2: IDENTIFYING PCBs Prepared by: Contract OSB77-0828S for: Stothart Engineering Ltd. Vancouver, B.C. Environmental Protection Service, Department of Fisheries ft Environment March 1979 HONS 002036 CROSS - REFERENCE INDEX BOOKLET 1: INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB . 1.3 How Does PCB - Contamination Occur? j 1.4 Is PCB Still Available? 1.3 Federal Government Legislation OnPCB 1 1.6 The Future 1.7 Appendix PAGE t-2 1-3 i-* i-s i- i-s 1-9 BOOKLET 2: IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix 2-2 2-3 2-e 2-a 2-io 2-is BOOKLET 3; PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance ProgramFor Transformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance ProgramFor Capacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-i* 3-15 3-i7 HONS 002037 BOOKLET 4: BOOKLET 5i BOOKLET 6: PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4-2 4-3 4-6 4-7 4-s 4-9 4-9 4-10 4-12 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5.1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 5-4 5-7 5-8 5-9 5-13 5-17 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General $.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-s #- 6-13 HONS 002038 BOOKLET 7: BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGF 7-2 7-3 7-4 7-6 7-7 7-9 8-2 8-3 8-4 8-7 HONS 002039 2-1 FOREWORD This booklet is number 2 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. MQNS 002040 2-2 2.1 BRAND NAURS FOR PCB PCB or Polychlorinated Biphenyl is called askarel when-used in elecTrical equipment. The PCB is in a blend with other chemicals. The following is an alphabetical listing of most of the different brand names for askarel that are used around the world. Brand Names For Askarel Apirolio (Italy) Arodor (U.S.A. & Great Britain) Asbestol Askarel Chlorextol Clophen (Germany) Clorinol Diaclor DK (Decachlorodiphenyl) (Italy) Dykanol Elemex Eucarel Fenclor (Italy) Hyvol 1 lnerteen (Canada & U.S.A.) Kanechlor (Japan) Montar (U.3.A.) No-Flamol Phenoclor (France) Pydraul (U.S.A.) Pyralene (France) 2 Pyranol (Canada & U.S.A.) Pyrodor (Great Britain) Saf-T-Kuhl Santotherm FR (Japan) Therminol FR (U.S.A.) 1 Westinghouse product 2 General Electric product MONS 002041 2-3 2.2 IDENTIFYING PCB TRANSFORMBBS The following instructions will provide the necessary information on how to identify whether a transformer contains askarel or mineral oil. Both are commonly used in transformers, but mineral oil does not present the contamination problems of askarel. Appearance Transformers containing askarel or mineral oil will have rows of metal tubes on their outside for cooling purposes. The tubes serve the same purpose as the radiator in a car. They could be rounded or slightly flattened in shape and will run down the length of the transformer casing to allow for maximum air circulation around the transformer liquid located inside. Some transformers also have a fan mounted above the tubes to increase air circulation around the tubes. The only difference in outer appearance between an askarel transformer and a mineral oil transformer will be in size. A mineral oil transformer will be larger than an askarel transformer having the same power handling capacity. Transformers with no tubes on the outside are a dry type. Such transformers contain no liquids of any kind. Transformer Locations Electrical transformers are easy to recognize because of their size. The problem is in knowing where to look for them. These are most likely locations: Typioal Locations For Transformers - Inside a plant or building (usually along a wall) - Inside a plant or building (enclosed in a concrete vault or electrical room) - On the roof - Underground (usually in mines only) - Outside on a concrete pad - Outside on a utility pole It should be pointed out that some companies may have several transformers installed. Some may be located inside and others may be located outside on a concrete pad. In most cases, a transformer which is located inside a building, on a roof or underground will contain askarel. The reason is fire safety. Fire regulations would not allow a trans former to be located in such situations unless it were filled with a nonflammable liquid such as askarel. Mineral oil would not be allowed instead of askarel because it is more flammable and could create a fire hazard if ignited. The only exception to this rule would be if the transformer were sealed in a specially designed protective vault. Then mineral oil transformers could be used inside a building, on a roof or underground. Vaults are usually made of concrete and have a fire door that must be locked. HONS 002042 LOCATIONS Concrete Pad 2-4 Caution - The reader is cautioned that some transformers located outdoors could also contain askarel. It would not be required under fire regulations, however, some owners may have decided to use PCB anyway, for fire safety in the area. Such situations are rare since PCB trans formers are much more costly than mineral-oil types. Regardless, it should be verified. Nameplate Information Most transformers have a metal name plate or tag mounted on the outside casing to show the name of the manufacturer and provide technical details about the trans former. The nameplate also states what kind of liquid is contained inside (liquidfilled types only) and how many gallons or litres there are. If the liquid used in a transformer is on the list of brand names in the front of this booklet, then the transformer contains PCB. If the nameplate says oil, then it is filled with mineral oil, not askarel. On the same nameplate or metal tag, the Type Number will also Indicate if the transformer contains askarel. Any Type Number beginning with an "L" indicates askarel is used in the transformer. Some typical Type Numbers are LPAF, LFAN, LFWN, LNAF, LNP, LNS, LNW, LNWN. Any Type Number beginning with an "O" indicates the transformer contains oil, not askarel. One Type Number common for oil-filled transformers is ONAN. Tasting the Liquid If for any reason it is still not certain what liquid is in a transformer, then a simple test may be done. The instructions are as follows. 1. Clean the drain spout located at the base of the transformer of any dirt by wiping with a clean rag. HONS 002043 2-5 Drain a small quantity of the trans former liquid into a clean glass bottle. Only a few drops are necessary. Add a small quantity of clean water to the bottle. Pure askarel is heavier than water. Pure mineral oil is lighter than water. 2. If the drops of transformer liquid settle to the bottom of the bottle, then the liquid is askarel. Alternative ly, if the transformer liquid rises to the top level of the water, then it is mineral oil. If the liquid does neither, then it indicates the transformer liquid has been contaminated by impurities from the transformer or from other sources, and should be taken to a testing laboratory for professional analysis. (It is also quite possible for a mineral oil transformer to be contaminated with askarel during topping up. Vice versa for an askarel transformer.) Caution - Do not pour the contents of the bottle back into the transformer since the water will degrade the electrical performance of the askarel (or mineral oil) in the transformer. If the test demonstrates that the transformer contains askarel, dispose of the contents of the bottle, and the bottle, as instructed in the booklet in this series concerning the handling and disposal of PCBs (Booklet 4). MONS 002044 2-6 2.3 IDENTIFYING PCB CAPACITORS Almost every electrical capacitor manu factured since the 1930s has been made with askarel so it must be assumed that all capacitors still in existence today contain PCB. Capacitors are used primarily by manu facturers and large commercial buildings to correct for low power factor. This produces reduced electrical bills because of the more efficient usage of electrical power. The following types of electrical equip ment cause low power factor, therefore, if any are found on the premises then capacitors will likely be found on the premises also. Equipment Producing Lew Power Factor -A.C. Motors (three phase and single phase types) -Induction Furnaces -Lamp Ballasts (fluorescent, mercury, metal halide, high pressure sodium) -Electric Welders Appearance Capacitors vary in size considerably. The smallest size is used in lamp ballasts where they can be as small as an ice cube. The capacitors have two electrical terminals extending from one end of the hermetically-sealed metal casing. Larger capacitors are used for power factor correction of motors and electric welders. They may be as large as 4 feet high by 18 inches wide by 9 inches deep, but do vary in size depending upon the horsepower of the motor or electrical load they are correcting. They typically have three electrical terminals in a row extending from the top of the capacitor. Usually the terminate are not obvious due to being covered by a metal box for protection against damage. In other applications for large capacitors, such as for the correction of induction furnaces, a group of individual capacitors may be wired together side by side in a "bank" to provide even greater power factor correction. The bank may be installed in a metal enclosure for protec tion against damage. In some instances, the number of capacitors is so large that all of the capacitor banks are installed in a room of their own. Capacitor Location Indoors - Capacitors can be found in a variety of different locations in a plant or building. They can be found secured to the floor, walls, columns, and ceiling or located inside electrical cabinets or attached to individual motor frames. To assist in locating capacitors inside the building, an electrical wiring diapam for the building would be very useful. It might not show the capacitors, due to the fact that capacitors are sometimes instal led long after a plant is built, but it will show the location of the electrical lines, and these can be traced to determine if capacitors are connected to the electrical system. Typical Locations For Capacitors -Wired to the electrical terminate of individual A.C. motors (if 30 horsepower and larger), electric welders, induction furnaces. -In the plant area, wired to buu bars feeding a row of motors or electric welders. -Connected to motor control center panels (M.C.C.) -Connected to the main service cables inside the Electrical Room. Since capacitors should be kept as cool and dry as possible when in operation, they will likely be found installed in the cooler, dryer parts of the building or plant. HONS 002045 2-7 Capacitors which are used with lamp ballasts are usually encased together with the ballast transformer. The container is filled with a sealing compound and may be located inside the light fixture or a remote distance away from the fixture. Outdoors - Capacitors can sometimes be found outdoors on oilfields, irrigation areas or in other motor installations. These capacitors will probably be housed in a weatherproof, welded steel housing of rectangular construction. Power utilities also have a large number of capacitors mounted outdoors. These capacitors are connected in banks to high voltage power cables and are usually located inside a substation area protected by a security fence. They can also be found on utility poles, particularly in rural areas. Capacitor Markings A capacitor can be recognized by the letters KVAR or KVAC stamped on its nameplate. This indicates the electrical size of the capacitor, which could range anywhere from 5 KVAR to over 200 KVAR. Large capacitors may even have the word ASKAREL or one of the brand names for askarel printed across its side. See the various brand names for askarel which are listed in the front of this booklet. Very small capacitors will probably not have any printing on them because of insufficient room for labelling. Testing the Liquid in Capacitors Capacitors are hermetically sealed to reduce the possibility of leakage. For this reason, the liquid cannot be tested to verify it is askarel. Four-Capacitor Bank Wall Cradle Ceiling Cradle Wall Bracket A Typical Capacitor (with cover removed) Vertical Floor Rack 4 o<ooN 2-8 2.4 mnmFTiNO pcb liquids In this section, some basic instructions are provided on how to identify new PCB liquid in storage or PCB liquids which will be disposed of. If there is any doubt at all about the contents of an unmarked container, then a chemical testing laboratory should be contacted for a detailed analysis. They are listed in the yellow pages under Laboratories. New Aafearal Some owners of electrical transformers will have askarel stored in drums or barrels for maintenance of their electrical equipment. Askarel should be handled only when wearing protective gloves and a splash apron. See Booklet 4 for instructions. New or reconditioned askarel will have the physical characteristics listed in the following table. The most obvious difference between askarel and mineral oil is the odour. Askarel has a very strong odour. Also, mineral oil is lighter than water. Askarel is heavier. Physical Charseteristics of Askarel Colour Vapours Odour Texture Weight -Crystal dear to pale yellow -Invisible -Bitter smell -Somewhat slippery -Heavier than water To check the colour of the liquid, pour a small amount into a clear glass bottle and hold it against a white background for contrast. At temperatures below 15P (-10C), white crystals may be found floating on top of the askarel. This is normal. The crystals are formed from one of the chemicals constituents of askarel. It is not ice. The crystals will dissolve when the askarel warms up. To test whether a container actually contains askarel, not mineral oil, follow the steps in the earlier part of this booklet concerning the identification of PCB transformers. Used Askarel Askarel which has been drained out of electrical equipment for disposal or for reconditioning usually does not have the same physical appearance as new askarel. Askarel which has been in equipment may have become contaminated with impur ities such as dirt, moisture, black carbon particles due to arcing, and bits of insula tion from inside the equipment. These impurities will degrade the electrical per formance of the askarel, as well as mak ing it appear cloudy or darker in colour. Other types of impurities may cause a light brown, green, red or a bluish tinge. Used askarel can be reconditioned by treating with special filters. Afterwartk It can then be put back into the equip ment. Used askarel is just as hazardous to the environment as new askarel and should be handled with the same caution. To test that a liquid is actually used askarel, follow the same test procedures as with new askarel. If this test fails to provide a conclusive answer, then two other tests are possible. HONS 002047 2-9 Test 1 - Beilstein Test 1. Oxidize a piece of copper wire in a flame. 2. Dip the hot wire into the liquid that is being treated. 3. Put the wire back into the flame. If a bluish green flame results, then the liquid being tested may be askarel. It is not conclusive either. Test 2 - Trace Test Certain professional laboratories will test the contents of liquids and materials using a gas chromatography technique. The cost may be up to $100, depending upon the substance being examined. These are the sample sizes required and the levels of PCB that are detectable: Substance to Be ______ Examined Sample Size Required_______ Water Oil Dredged sediment Tissue 4i litres (1 gallon) 4i litres (1 gallon 30-50 grams (1-2 oz.) 25 grams (1 oz.) Lowest Quantity of PCB That is Detectable 10 p.p. trillion 5 p.p. billion 5 p.p. billion 5 p.p. billion * Parts per trillion or billion MQNS 002048 2-10 >.S NEW LABELLING SYSTEM FOR PCB A new labelling system for PCBs has been developed by the Federal Environmental Protection Service to alert persons to the presence of PCBs in equipment and to prepare an inventory listing of PCB equip ment which is located throughout Canada. PCB Equipment and Unused PCB Liquid The labels for PCB equipment and spare PCB liquid are brightly coloured with black printing against a white background of self-adhesive vinyl paper. There are two sizes: one 3 inches by 3 inches to be placed on the casing of small items such as PCB capacitors, and another 6 inches by 6 inches for PCB transformers and drums of PCB liquid. Each label has a registration number printed across the bottom for registering the equipment which the label will be adhered to. The labels should never be removed from the equipment, even if it is later removed from service for disposal. The PCB labels are now available from the Regional offices of the Environmental Protection Service, and one serialized label should be attached to each piece of electrical equipment that has been positively identified as containing PCB. This includes transformers and capacitors in storage, as well as those in service. With proper PCB labelling, it will be obvious to anyone working with the equip ment that it contains PCB and that caution is necessary. Contact the Environmental Protection office for labels. A special label should be attached to each piece of electrical equipment containing PCBs, even if it already has some other kind of labelling on it for PCB or askarel. Other labels will not have a serial number printed on them for identification pur poses. PCB Wastes and Discarded Equipment Drums containing waste PCB liquid, materials contaminated by askarel, and scrapped electrical equipment should each be labelled with the Number 4 - Severe Hazard label, also available from the Environmental Protection Service. It is a non-serialized label which is used for many different types of chemicals. When used with PCBs, it should be filled out as follows: HEALTH FIRE ENVIRONMENT REACTIVITY CONTENTS DISPOSAL HANDLING ORIGINATOR TELEPHONE DATE -4 -1 -4 -1 - PCBs are contained inside - (leave blank) - Class 9 - (your company name) - (your telephone number) - (the date) The label will then contain the informa tion that is necessary for a PCB container either being stored or later being shipped to a disposal site. The code numbers that are written into the four boxes on the top line of the label indicate the severity of PCB in that particular situation. For example: PCB is a high health hazard because of its effect on the food chain, it will not burn easily, it is a high hazard to the environment, and it does not react easily with other chemicals or materials. NUNS 002049 2-11 The Handling classification is a special coding system pertaining to the handling and transportation of hazardous goods. See booklet 7 if details are required. Entrance to Electrical Room and Storage Each entrance way into an electrical room, transformer vault, chain linked area or storage compound containing PCBs should be posted with the non-serialized version of the 6 inch by 6 inch black-andwhite PCB label. This will properly inform personnel enter ing the area that PCB is being stored and caution is necessary. With such informa tion, they might also notice a situation which would otherwise go unreported until an authorized employee makes his formal inspection rounch of the compound. How to Apply the Labels Peel the protective backing from the label and press it firmly against a clean, dry area where it is most likely to be seen by personnel. Rub the surface of the label well to ensure it is securely attached. HONS 002050 2-12 ATTENTION PCBCONTAINS CONTIENT DES POLYCHLORINATED BIPHENYLS 8IPHENYLES POLYCHLORES A TOXIC ENVIRONMENTAL CONTAMINANT SCHEDULED UNDER THE ENVIRON MENTAL CONTAMINANTS ACT IN CASE OF ACCIDENT. SPILL OR FOR DISPOSAL INFORMATION. CONTACT THE NEAREST OFFICE OF THE ENVIRONMENTAL PROTECTION SERVICE ENVIRONMENT CANAOA PRODUITS TOXIOUES MENTION NES DANS L ANNEXE DE LA LOI SUR LES CONTAMINANTS DE L ENVIRONNEMENT EN CAS 0 ACCIDENT. OU DE DEVERSEMENT OU POUR SAVOIR COMMENT LES fiLIMINER. CONTACTER LE BUREAU OU SERVICE DE LA PROTECTION DE L ENVIRONNEMENT MINISTERS OE L ENVIRONNEMENT LE PLUS PRES PR 20108 MQNS 002051 2-13 4 SEVERE HAZARD EXTREME DANGER HEALTH SANTE 1 FIRE 1 INCENOIE CONTENTS /CONT1ENT 1 ENVIRONMENT IENVIRONNEMENT 1 REACTIVITY 1 REACTIVITE OISPOSAL ELIMINATION ORIGINATOR / EXPEOITEUR 04-19U (01 '77) HANOLING MANIPULATION TEL TEL. DATE FOR USE ON PCB WASTES AND DISCARDED EQUIPMENT HONS 002052 z-l* ATTENTION PCBCONTAINS CONTIENT DES polychlorinated biphenyls 8IPHENYLES POLYCHLOHES A TOXIC environmental CONTAMINANT SCHEDULED UNDER THE ENVIRON MENTAL CONTAMINANTS ACT IN CASE OF ACCIDENT SPILL OR FOR DISPOSAL INFORMATION. CONTACT THE NEAREST OFFICE OF THE ENVIRONMENTAL PROTECTION SERVICE ENVIRONMENT CANADA PROOUITS TOXIQUES MENTION NES DANS L ANNEXE DE LA LOI SUR LES CONTAMINANTS DE L ENVIRONNEMENT EN CAS D ACCIDENT, OU DE OEVERSEMENT OU POUR SAVOlR COMMENT LES ELIMINER. CONTACTER LE BUREAU OU SERVICE DE LA PROTECTION DE L ENVIHONNEMENT MINISTERS DE L ENVIRONNEMENT LE PLUS PRES FOR USE ON ELECTRICAL ROOM, TRANSFORMER VAULT, CHAIN LINKED AREA AND STORAGE COMPOUND HONS 002053 2-15 2.6 APPENDIX HONS 002054 2-16 ENVIRONMENTAL PROTECTION SERVICE OFFICES lwtai Pacific Northwest Ontario Quebec Atlantic Address Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 686-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5840 Environmental Protection Service 4th Floor 1550 de Maisonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J 1M5 Emergency (902) 426-6200 Office (902) 426-6141 HONS 002055 \ i i Booklet 3 HONS 002056 BOOKLET 3: PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT Prepared by: Contract OSB77-0828S for: Stothert Engineering Ltd. Vancouver, B.C. Environmental Protection Sendee, Department of Fiaheriee & Environment March 1979 MONS 0CU05 7 CROSS - REFERENCE INDEX BOOKLET 1; BOOKLET 2: BOOKLET 3: INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1. S Federal Government Legislation On PCB 1.8 The Future 1.7 Appendix PAGE 1-2 i-3 i-* i-s l-e 1-8 1-9 IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix z-2 2-3 2- 2-8 2-10 2-15 PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program ForTransformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program ForCapacitors 3.8 Appendix 3-2 3-3 3-? 3-9 3-13 3-14 3-15 3-17 HONS 002058 PAGE BOOKLET 4i HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4-2 4.2 Safe Handling 4-3 4.3 Collection of Askarel 4-9 4.4 Containment For Disposal - Capacitors 4-7 - Transformers 4-9 - Askarel Liquid 4-9 - Solid Wastes 4-9 4.5 Labelling of PCB Wastes and Discarded Equipment 4-10 I 4.S Appendix 4-12 BOOKLET 5; STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5.1 General 5.2 Selecting A Storage Site 3.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 3-4 5-7 5-8 5-9 5-13 5-17 BOOKLET 6: CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB S. 1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-5 6-9 6-13 HONS 002059 BOOKLET 7: BOOKLET 8! TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGE 7-2 7-3 7-4 7-6 7-7 7-9 s-2 8-3 8-* 8-7 HONS 002060 3-J FOREWORD This booklet is number 3 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "asliarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies Thaae Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or asaistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002061 3-2 3.1 GENERAL A well-designed askarel transformer should be depended upon for over 30 years of reliable operation. This is especially true of modern transformers because of their superior design and construction. In spite of these important distinctions, the lifetime of a transformer can be cut short or plagued with troublesome problems, depending upon these and other critical factors: - The power handling capability of the transformer in its particular application. Is it operating near its rated kVA capa city? - Its operating temperature on a day-to day basis. - The amount of physical abuse it receives. Is it in a high traffic area? If a transformer should fail in operation, not only could it create an environmental hazard, but it could also become a very expensive proposition to remedy. The cost of rebuilding a transformer -- which includes de-tanking, rewiring, and refill ing, can be as much as 2/3 of the cost of a new transformer and would require some 3 - 4 months to complete. Alternatively, transformers are not usually off-the-shelf items so the delivery of a new transform er could take up to 1 year. One of the ways to prevent this cost, inconvenience, and possible environmental hazard from happening is through preven tive maintenance. It applies to both transformers and capacitors. That is the theme of this booklet. HONS 002062 3-3 1.2 ANATOMY OF A TRANSFORMER Most power transformers are externally quite similar in appearance. Their primary difference is in physical size, the location of the monitoring gauges, and the presence of optional features such as fan cooling or special bushing connections. The following sketch for a pad-mounted transformer shows the type of equipment that can be found on many askarel-filled transformer (and many oil-filled types as well). Most of the items shown here are standard accessories for larger transform ers. ANATOMY OF A TRANSFORMER Pressure-Relief Valve Upper Drain Valve -- Bushings Transformer Gauges Identification Nameplate Cooling System Lower Drain Valve MONS 002063 3*4 High Voltage Protection The primary purpoaa of a transformer is to convert electrical power from one operating voltage to another. Whether the voltage is 13.8 kV, 4160 volts or 600 volts, the application is still the same - a power transformer is used to convert high voltage. Askarel is well suited to this type of application since it is an excellent insulat ing medium. By immersing the transform er core and coil windings in a tank of askarel, the electrical insulating factor that results between the coil windings is much better than with any other type of liquid. Sparks inside a transformer are not an unusual occurrence. They occur as a result of lightning strokes, switching surges, and transient fault conditions on the power line. Normally they last only a fraction of a second and the current flow is so small that the disturbance is not even detected by protective relays on the power system. This is what happens when a spark occurs in a tank of askarel. It occurs almost instantaneously: 1. High voltage sparks between con ductors generate tremendous heat and decompose askarel in the vicinity of the spark. Hydrogen chloride gas, carbon dioxide, askarel vapour, carbon particles, and other hydrocarbon gases are produced as a result of this decomposition. 2. Gases bubble out of the askarel, creat ing pressure in the container. 3. The gases slowly condense over a period of time, and the pressure in the container gradually reduces back to normal. As the gas condenses, it forms a weak concentration of hydro chloric acid which recombines with the askarel liquid in the tank. This sequence of events can happen hund reds of times a year, without creating enough pressure to cause a release of the pressure relief valve on the transformer. HONS 002064 i 3-S Details on Transformer Accessories The gauges installed on the side of the transformer tank can provide important information on the transformers internal performance and might possibly avert an environmental hazard. Details on the transformer gauges and the pressurerelief valve follow. They should be periodically checked for any change. 1. Dial-type Thermometer Gauge This gauge measures the temperature of the askarel liquid inside the trans former tank. Some small change in the temperature reading can be expected because of variations in the electrical load of the transformer. For example, certain motors in a plant may be switched on only at certain times of the day, resulting in the transformer windings, and therefore askarel, becoming hot ter. Normally the temperature of the askarel should remain much less than 105C. Excessive temperatures indicate the transformer is overheat ing, possibly due to a loss of askarel. The rate of deterioration of the insul ating materials in the transformer can double for every 8C rise in tempera ture, therefore, it is important to take action as quickly as possible to remedy the situation. 2. Liquid Level Gauge This gauge measures the level of the askarel inside the transformer tank. There is approximately a 2-inch air gap in the space between the surface of the askarel and the underside lid of the tank. The reading of this gauge will also change with variations in the electri cal load because higher temperatures cause expansion of the askarel liquid and a subsequent rise in its level. Temperature Liquid Level Gauge HONS 002065 3-6 Cheek with the transformer manufac turer to determine the minimum acceptable level of askarel for the design of the transformer. Mark it on the dial of the gauge. Any lower reading indicates that there is not sufficient askarel inside to conduct heat away from the windings or to keep them insulated. Both situations are dangerous so It should be topped up immediately. TTCB can be used in limited quantities as a topping up fluid for askarel transformers. 3. Pressure-Vacuum Gauge This gauge measures the amount of built up pressure, or vacuum, in the air space between the top level of the askarel and the underside cover of the transformer tank. Some nominal change in reading can be expected due to variations in the electrical load. Larger electrical loads cause more internal heating of the transformer and some expansion of the askarel liquid. As the liquid expands, it will compress the air space above the liquid, producing a higher reading of the gauge towards the PRESSURE end of the scale. If the gauge reading never moves, then there is an air leak into the transformer, probably through one of the gaskets. An abnormally high pressure indicates that there is a Build up of pressure inside, probably due to internal short circuits and arcing. The PressureRelief valve should release this pres sure before it strains or ruptures the transformer tank. Check with the transformer manufac turer to determine the maximum acceptable reading for the gauge (usually around 10 psi). Mark it on the gauge. Any reading above this amount indicates the Pressure-Relief valve is not functioning properly and should be repaired. Vacuum/Pressure An abnormally high vacuum reading on an energized transformer indicates that the level of the askarel is low, probably due to a loss of askarel. Transformer burnout will occur as soon as the level of the askarel drops below the top part of the transformer wind ings. In addition, the vacuum condi tion can draw air, moisture and dirt into the transformer tank through weak gaskets and contaminate the askarel. Check with the transformer manufacturer for the maximum ac ceptable vacuum reading under normal operation. With a normal vacuum reading the level of the askarel will be low, but still adequate to cover the transformer coils. 4. Pressure-Relief Valve This device is calibrated at the factory so as to release abnormally high inter nal pressure at a set limit. It is mechanically automatic and self-re setting. The valve is fitted with a visible signal to indicate when it is open. It should reseal itself after every operation to keep moisture, dirt and other contaminants from entering the transformer tank. HONS 002066 3-7 3.3 TYPICAL PROBLEMS WITH TRANSFORMERS This section of the booklet contains a partial listing of some common transform er problems. Opposite each is a descrip tion of what can happen if the problem goes unnoticed for a long period of time. It is important to realize that simple inspections could prevent most of these problems from becoming serious because most involve gradual rather than sudden change. PROBLEM Gradual contamination of the transformer liquid by moisture, dirt, carbon or chemicals resulting from arcing inside the transformer. WHAT CAN HAPPEN Insulating quality of askarel liquid weakens. High voltage sparks will occur inside the transformer, causing a build-up of internal pressure. Excess pressure will force askarel out of the transformer through the pressure-relief valve or through weakened gaskets. Possible contamination of the environment. Weakening of transformer seals and gaskets due to aging. Leaks develop. With substantial loss of askarel, transformer will overheat, even burn out. Loss of askarel allows electric arcs to occur inside the transformer since it is no longer properly insulated. A catastrophic failure may result. Physical damage or rusting of the cooling radiators. Structural damage to transformer tank. Leaks develop. With substantial loss of askarel, transformer will overheat, even burn out. Loss of askarel allows electrical arcs to occur inside the transformer since it will no longer be properly insulated. MONS 002067 3-a Over-heating of transformer due to being undersized for its application (overloading), or because of loss of askarel. Lightning surges and short circuits on the power line. Insulation on electrical windings and insulation materials will deteriorate, allowing short circuits and internal sparks to occur between windings. Decrease in life expectancy and possible loss of askarel to the environment. High voltage sparks are produced inside the transformer, causing a build-up of internal pressure. Excess pressure will force askarel out through pressure-relief valve or through weak gaskets. Pressure-Relief Valve I HONS 002068 3-9 3.4 PREVENTIVE MAINTENANCE PROGRAM FOR TRANSFORMERS This maintenance program is presented in four parts. Parts 1 and 2 need only be done once, while Part 3 should be carried out once every 6 months to a year. Part 4 concerns professional services that might be required on an occasional basis. Part 1 - Check Transformer Siting and Location Sizing - Have an electrician check whetner the transformer is normally oper ated at or near the power level rated on its nameplate. Additional loads might have been connected to the circuitry since the transformer was first installed. If the transformer is operating near its power rating, consider investing in another transformer to share the power handling requirements. Alternatively, consider whether part of the load can be shed at peak load times. Operation at the rated power level does not leave much safety factor for the transformer in the event of a fault condi tion on the power line. Location - Is the transformer located close to a source of excessive heat, such as a furnace? If so, consider installing forced air cooling to reduce the trans former's operating temperature. Are the transformer tank or radiator fins likely to be damaged by vehicle traffic? If so, install a protective fence around the unit. Allow for free air ventilation through the fence. Part 3 - Consider Installing Alarm Circuits The gauges on many power transformers are fitted with mechanical contacts to provide re note warnings or to de-energize the transformer automatically in the event of an abnormal situation. In most cases, de-energizing the transformer will protect it from serious damage. Consider connecting the contacts to alarm systems or to control circuitry, if they are not already connected. These are some of the more common alarms and protective devices available for power transformers: Dial-Type Liquid Thermometer Alarm Contacts dose when the temperature rises above a set limit. Liquid Level Gauge Alarm - Contacts close when the askarel level drops below a set limit. Pressure-Vacuum Gauge Alarm - Contacts close under abnormal conditions. Pressure-R slief Valve - Contacts close every time the valve operates. Sudden Pressure Relay - Contacts operate whenever there is an abnormally rapid change in internal pressure due to internal faults in the transformer. Such rapid changes would not cause the pressurerelief contacts to operate. Winding Temperature Indicator - This device is equipped with several sets of contacts, preset to operate at increasing temperatures. They might control the cooling equipment, the alarm circuits and the circuit breakers, in that order. HONS 002069 3-10 Part I - Routln* Inspections 1. Appoint one person in charge of trans former inspections. It is recommended that inspections be done on a regular basis once every 6 months. 2. Develop a separate record-keeping sheet for each transformer and keep track of all observations on each tour. The observations might predict a serious problem before It happens. 3. Check these items on each tour: INSPECT__________________________ WHAT TO LOOK FOR Condition of gauges Are an/ faceplates cracked or the gauges damaged? Consider installing a plexiglass sheet over the gauges for protection against damage. Reading of gauges Have the readings changed much since the last tour? Are they near an unacceptable reading? Corrosion on tank and radiator fins Check radiators very carefully. They are manufactured of thin gauge steel to obtain maximum cooling and win rust through more quickly than the rest of the transformer, especiaUy in a caustic environment. Clean them to bare metal and paint with primer and finish coats if rusted. Paint finish of tank and radiator fins b paint starting to weather away? AU paints wiU weather eventually. Repaint as often as necessary to prevent rusting. HONS 002070 3-11 Leakage or weep of askarel from: - tank - radiator fins - top cover (if gasketed) - manhole cover - top or bottom drain spout - high and low voltage bushings Pressure-relief valve High and low voltage bushings Colour of askarel Wet slickness and gummy residue. Do the gaskets or seals appear to be deteriorating? Important - if there has been leakage, take steps to clean It up promptly! Refer to Booklet 4 for clean-up instructions. Are the gaskets displaced so the valve is not seating properly? Are they cracked or chipped? Low voltage bushings are larger, therefore, they are more likely to leak first. Take a small sample. Is the colour changing from clear to a blue, green, red or blackish cast? If so, it is picking up impurities and becoming contaminated. Consider a laboratory test to check its quality. Rusted Cooling Fin Askarel HONS 002071 3-12 Part 4 - Professional Services Professional services might occasionally be required for a transformer, depending upon the performance indicated by its gauges. These services might be required: 1. Removal of an askarel sample (1-2 pints) to test the quality of the askarel in the transformer. 2. Filter pressing or Fuller's earth treat ment to remove moisture and other contaminants from the askarel. These are the steps that a professional laboratory will follow when taking an askarel sample for laboratory analysis: 1. The sample will be taken on a dry day when the humidity is less than 75% and the transformer is warm. 2. The 1/2" sampling valve at the top of the transformer will be wiped dean of any dirt. (A sample from the top spout is more representative of the condition of the askarel than from the bottom spout.) 3. About 1 to 2 pints of askarel will be run into a metal catch bucket to flush away any dirt lodged inside the spout. 4. A one-quart sample bottle and Rakelite screw cap will be rinsed 2 or 3 times with askarel from the trans former and then filled with a sample. 5. The bottle will be capped tightly with an aluminum or tin oapliner to keep out moisture and dust. 6. The bottle will be labelled as contain ing askarel. 7. After a number of samples have been taken over a period of time, the transformer will have to be topped up with tri/tetrachlorobenzene (TTCB) or some other suitable make-up fluid to replenish the lost liquid. If the composition of the insulating liquid is not known, it should be determined before any significant amounts of TTCB are added. See Booklet 8 for further information on topping up of transformers. In addition, after each test the askarel liquid that is released in steps 3 and 4 will have to be properly disposed of as indicat ed in Booklet 4. HONS 002072 3-13 3.5 ANATOMY OF A CAPACITOR An askarel capacitor is a hermetically sealed unit which contains only metal foil, paper, plastic film, and askarel. There are no moving parts inside. In spite of this simple design, an askarel capacitor haa a lifetime of at least 10 to 20 years. Since the unit is sealed, there is no provision to add or remove fluid or perform internal maintenance for increas ing this lifetime. I As with transformers, a capacitor could create an environmental hazard when it I fails. I Datails on Capacitor Conatnietion Most capacitors are equipped with fusing to de-energize the capacitor in the event of a breakdown. One type of breakdown failure, an internal short circuit, can create enough internal pressure to burst the case seams open if the power is not disconnected. Some types of capacitors are constructed with a number of individually fused cells. Under this arrangement, the defective capacitor cell removes itself from the circuit when a fuse melts. This allows the remaining capacitors to still provide a certain amount of power factor correction to the plant. ANATOMY OF A CAPACITOR HONS 002073 3-14 3.8 TYPICAL PROBLEMS WITH CAPACITORS Her* is partial listing of some common capacitor problems. Opposite each is a description of what can happen. PROBLEM Rusting of casing, damage to insulator bushings WHAT CAN HAPPEN Leaks develop. With loss of askarel, capacitor will overheat and internal insulation will fail. Internal short-circuits will develop and build up pressure inside casing. A rupture of the casing may contaminate the environment. Physical damage to capacitor casing Internal insulation may be damaged. Internal short-circuits can develop and build up pressure inside casing. Over-heating of capacitor due to loss of askarel or proximity to sources of heat Internal insulation will deteriorate. Internal short-circuits can develop and build up pressure inside casing. End of lifetime Internal insulation will faiL The capacitor will draw large amounts of current and pressure will be built up inside the casing. HONS 002074 3-15 3.7 PREVENTIVE MAINTENANCE PROGRAM FOR CAPACITORS This maintenance program is presented in two parts. Part 1 need only be done once while Part 2 should be carried out on a periodic basis every 6 months. Part 1 - Cheek the Capacitors Location________________ ___ Properly functioning capacitors are normally warm to the touch. The temper ature of the casing should not exceed S5C., under normal operating conditions. Such conditions are defined as the name plate voltage and line frequency for which the capacitor was designed. Any conditions above these will increase the temperature of the capacitor and decrease its lifetime. Check the following: 1. The Operating Voltage - The operating voltage will be especially high during periods of light loading of the power system. If the operating voltage is 10% or more above the capacitor's rated voltage, consider improving the regulation of the power system or disconnecting the capacitors during such periods. 2. Proximity to sources of heat such as furnaces or direct sunlight. 3. Adequacy of freely circulating air ventilation around the capacitors. The ambient air temperature should always be less than 40C. 4. Are the capacitors likely to be damag ed by vehicle traffic? If so, install a cage around the capacitors. Allow for free air ventilation through the cage. Part t - Routine Inepectlows 1. Appoint one person in charge of capacitor inspections. It is recom mended that inspections be done on a regular basis once every 8 months. 2. Check these items on each tour: HONS 002075 3-16 INSPECT Corrosion on casing; Physical damage Leakage or weep of askarel Melted fuses Temperature of the capacitor casing WHAT TO LOOK FOR Rusting is more likely to occur in a caustic environment. Dents, broken insulator bushings. Wet slickness and gummy residue. Important - if there is leakage, remove and dispose of the capacitor! Some capacitors with external fuses have a visual indicator to signal that the fuse has melted. Conduct a continuity teat on the capacitor. If defective, dispose of the capacitor. Alternatively, replace the fuse and if it melts again, dispose of the capacitor (see Booklet 4 for disposal instructions). The casing should be warm to the touch. If it is cold, check the fuse. If it is hot, check for the cause of the excassive temperature. HONS 002076 3-17 I I 3.8 APPENDIX HONS 002077 3-ia ENVIRONMENTAL PROTECTION SERVICE OFFICES Ration Pacific Northwest Ontario Quebec Atlantic Address Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue Eaat Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (418) 986-5840 Environmental Protection Service 4th Floor 1550 de Maiaonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J IMS Emergency (902) 426-6200 Office (902) 426-6141 HONS 002078 HONS 002079 BOOKLET HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL Prepared by: Contract OSB77-08285 for: Stotltert Engineering Ltd. Vancouver, B.C. Environmental Protection Service Department of Fiaheriea and Environment March 1979 HONS 002080 CROSS - REFERENCE INDEX BOOKLET li BOOKLET 2; BOOKLET 3i INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1.5 Federal Government Legislation On PCB 1.6 The Future 1.7 Appendix EASE. 1-2 1-3 i-* 1-5 i-* l-e 1-* IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix z~2 2~3 2~a *-io *-is PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program ForTransformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program ForCapacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-14 3-is 3-17 HONS 0020B1 BOOKLET 4: BOOKLET 5-. BOOKLET 6s ------------------ HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4-2 4_3 4-7 4_8 4-9 4-9 4-10 4-t2 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5.1 General 5.2 Selecting A Storage Site S. 3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix s-2 5-3 s-4 5-7 5-8 s-9 5-13 s-17 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-5 6-9 6-13 MONS 002062 BOOKLET 7s BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGE 7-2 7-3 7-4 7-6 7-7 7-9 6-2 6-3 8-4 8-7 HONS 002083 4-1 FOREWORD This booklet Is number 4 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PC8 chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002084 4-2 4.1 GENERAL The subject of askarel disposal is very controversial because of public concern over the effectiveness of any disposal method. Scientists have found that askarel can be almost completely destroyed by tempera tures above 1000 C, however, there are presently no approved sites for such special incineration in Canada. The Federal Environmental Protection Service recommends that any liquid askarel or askarel-contaminated material which needs to be disposed of should be held in storage by its owner until govern ment approved landfill sites or special incineration plants become available to the public. Ordinary landfill dump sites are inappropriate to control contamina tion to the environment due to the danger that leaking containers may contaminate ground water or surface runoff. This booklet, and Booklets S and 6 in this series, provide information on how to store askarel properly in the meantime and how to avoid any risk to the environ ment. Ensure that your employees are familiar with the contents of these book lets. It should be remembered that individuals who discharge askarel, or who allow askarel to be discharged into waters frequented by fish, can be prosecuted under the Federal Fisheries Act. Further more, discharge of askarel into the environment may be in violation of other statutes, specifically the proposed control on PCB release under the Environmental Contaminants Act and certain provincial pollution control statutes. HONS 002085 4-3 4.2 SAFE HANDLING Askarel can be handled safely by observ ing routine precautions. Such precautions should apply whether the purpose of the job is to work on a piece of equipment containing askarel or simply to move a drum of askarel from one location to another. Wear proper clothing to protect against the hazard of splashes or spills. These garments are considered appropriate for handling askarel: - coated gloves or an industrial-type barrier cream on the hands. Gloves are preferable. - a face shield or safety glasses fitted with side guards. - a splash apron made of PVA, Viton material by Dupont, or Teflon. - disposable clothing which can be discarded after handling askarel. - boots or rubbers and a safety hat. Rubber or neoprene garments are not recommended since they are slowly dis solved by askarel and will no longer provide adequate protection. Store all garments in a separate locker and use them only for working with askarel and askarel equipment. Provide additional air ventilation, when working with askarel hotter than 55 C. The fumes from hot askarel (55C) can be very irritating to the eyes and lungs. Askarel at room temperature (25 C) is not so Irritating. If maintenance is required on a transform er, de-energize it, let it cool, and ensure that there is adequate air ventilation in the work area before beginning main tenance. Opening all doors would be helpful. The same procedure should be followed when working with askarel kept in storage. The recommended unloading, handling and pumping temperature for the most widely used types of askarel are: Askarel Product Handling Temperatures Pyranol A13B3B-3 Inerteen 70-30 Inerteen 100-42 20 - 55C 20 - 55C 35 - 75C Boots or Rubbers HONS 002086 4-4 If exposure to hot sskarel (55C or above) is necessary, such as under emergency conditions, wear an approved gas mask with an organic cannister or wear a selfcontained breathing apparatus. An application of castor oil will help to provide a barrier against the irritation of askarel fumes on unprotected skin. Also, provide forced air ventilation in the work area. Exhaust the air to the outside of the building to prevent other people in the building from becoming irritated by the fumes. Some other precautionary measures when handling askarel arei 1. Pump, do not pour askarel into con tainers or equipment. This will mini mize the possibility of splashing and spills to the ground. 2. Frequently inspect pumps, hoses, noz zles, pump motors, and wiring of equipment used to handle askarel. Replace them at the first sign of deterioration. 3. Do not use askarel pumps and hoses for any other purpose, otherwise other liquids will become contaminated. 4. Centrifugal pumps recommended for handling hot oil are acceptable for use with askarel. Gear-type pumps are not. These are some details on the most appropriate centrifugal pumps: - All wetted surfaces of the pump should be made of stainless steel. - The shaft seal should be an external carbon ring type to eliminate the packing material being exposed to the deteriorating effects of askarel. - Acceptable valves are brass or stain less steel-lined. - Suitable hoses are flexible metal or lined with tetrafluoreoethylene or silicone polymers for protection against deterioration. HONS 00207 4-5 Become familiar with the steps of first aid for askarel. Have a first aid kit handy in ease of accidents. A portable eyewash kit is also useful. What to do: IN CASE OF Askarel on skin FIRST ACTION Wash in usual manner with warm water and soap. SECOND ACTION Apply cold cream to reduce any feeling of irritation. If askarel was hot, treat like any burn. Askarel in eyes Askarel swallowed Strong askarel fumes inhaled Flush eyes with gentle stream of lukewarm water for 15 minutes, keeping eyelids apart. Add a drop or two of castor oil, opthalmic anesthetic solution, or orthalmic cortisone acetate solution to reduce irritation. Have eyes examined by physician. Press down at back of tongue to cause vomiting. Do not give victim anything to drink. Write down details about the liquid and take victim to hospital emergency room or physician immediately. Get victim into fresh air. If discomfort does not clear up, take victim to physician. After working with askarel, wash hands in usual manner with soap and water before eating, drinking, smoking or using toilet facilities. HONS 002088 4-6 4.3 COLLECTION OF ASKAREL These guidelines should be kept in mind when collecting askarel and collecting materials contaminated by askarel: 1. Never spill askarel down drains or on the ground. Follow the procedures recommended in this booklet Cor disposal. 2. All containers used for askarel should be clearly marked as containing PCB, even if they are presently empty. 3. Any askarel collected in open drip pans under transformers should be transfer red into storage drums as soon as possible. This will minimize the amount of askarel left sitting in open containers. 4. Move askarel from one location to another only in sealed containers. 5. Other liquids should never be mixed with askarel since other liquids will not need the same storage precautions as askarel. This will minimize the size of containers needed to store askarel. 6. Containers used for the collection of askarel should never be used for any other purpose since the containers will be contaminated after one use with askarel. 7. Plastic containers should not be used for catching drips under transformer spouts since plastic can be dissolved by askarel. Use metal containers of good quality only. Empty them into storage drums promptly. 8. Spilled askarel should be cleaned up immediately, using absorbing materials such as sawdust and wiping rags. Dispose of all wipe-up materials as recommended in the next section of this booklet. For more instructions on cleaning up spilled askarel, see Booklet 6 in this series. i l rF ' ' ' Separate Metal Containers for Askarel and Oil HONS 00^089 4-7 4.4 CONTAINMENT FOR DBP08AL Anything which comes into contact with ukarel should be contained for disposal using the procedures recommended in this section of the booklet. Items to be disposed of can include: discarded capa citors and transformers, contaminated askarel, earth and gravel, clothing, clean up materials, pieces of wood, etc. Items contaminated by askarel should never be burned. Ordinary incineration will allow PCB to become airborne. Flaming and Preparation Before moving any askarel items, plan the route that will be followed. Then prepare the area along the route by ensuring all floor cracks are well-caulked, by checking the seal of floor drains, and by laying down absorbent blankets to catch any accidental leakage or spills which might occur. Be overly cautious in this planning and preparation stage. Containment of Capacitors 1. When a failed capacitor must be removed from service, leave the case unopened. If it is leaking already, ensure all leakage is wiped up (see Booklet 6 for clean-up instructions). 2. Wrap each capacitor in a heavy duty plastic bag and tie it shut. 3. Place the wrapped capacitor directly into a 45-gallon steel drum fitted with a removable steel lid and a gasket made of PCB-resistant material. (Store with capacitor terminals up to prevent eventual leakage from capa citor bushings.) A heavy-construction drum of Number IS gauge or heavier is suitable for storage. This drum should preferably be the first and last that the capacitor is put into in order to minimize accidents in handling. HONS 002090 The drum should be new and free from corrosion or defects so as to ensure long term storage and eventual trans portation for disposal. Reconditioned drums are not recommended, nor are plywood, fiberboard or plastic drums, due to insufficient durability. 4. Pack the drum well with sawdust to prevent shifting around inside. The sawdust will also absorb any leaks which may develop. Sand should not be used for this purpose since it will make the drum too heavy for conven ient handling. 5. Seal the drum, label it, and move it to the storage area using routine material handling precautions. See this booklet for labelling instructions and Booklet S for storage instructions. Be careful when moving askarel! Most spills occur during the movement of askarel equipment and containers. Ensure any drums will not fall from the transport vehicle. Scrapping a Transformer 1. DO NOT dismantle a transformer for the purpose of selling it for scrap. A drained askarel transformer still con tains enough askarel saturated in its core to still be considered a threat to the environment. In fact, a new regulation is being considered by the Federal government which will prevent the re-sale of askarel transformers and capacitors because of this hazard. It should be mentioned that mineral oil transformers are sometimes topped up with askarel during servicing so be very sure that a non-PCB transformer is indeed free from askarel contami nation before disposing of it. Have it professionally tested if necessary. See Booklet 2 for Trace Test details. 2. Before moving any askarel-filled transformer, pump the contents into a good quality double-bung, 45-gallon steel drum of Number 16 gauge or heavier, using a pump and hoses devot ed specially to handling askarel. Keep clean-up materials handy in case of an accidental spill. 3. If a transformer must be partially dismantled before it can be moved, it should first have a triple rinse with a suitable solvent. This will remove most, but not all, of the askarel from the transformer. The transformer should still be considered a possible source of contamination. These are the instructions to follow: Step 1 - Place a containment system under the transformer. See Booklet 6 for details. Step 2 - Pump the askarel from the transformer into drums. Step 3 - Fill the transformer with a flushing solvent such as trichloroben zene, kerosene, or fuel oil. Step 4 - Let the transformer sit for 18 hours or more so that the solvent can soak into the transformer core. Step 5 - Pump the askarel-contaminated solvent from the transformer into drums. See Booklet 5 for instruction in storing drums. Also refer to Section 2.5 of the Guideline for the Manage ment of Waste Materials Containing Polychlorinated Biphenyls, which is published by the Environmental Protection Service. This document provides information on the treatment of contaminated equipment and contain ers for disposal. HONS 002091 4-9 Step 6 - Repeat steps 3, 4 and 3. Step 7 - Repeat steps 3, 4 and 5 again. Step 8 - Commence dismantling of the transformer. Step 9 - Wipe up all drippings in the area and properly dispose of wastes. 4. Build a protective crate around the transformer for moving. Ensure the drain spouts are protected against damage since they can be easily broken off during moving. The cooling tubes can also be easily crushed or punctured, allowing askarel contami nants to leak out. 5. Move the transformer to the storage area using routine material handling precautions. Be careful when using a fork lift truck. Transformers have been reported to have fallen from them during transport. 6. See Booklet 5 for storage instructions. USE CAUTION . . . Other types of waste liquicfc such as oils, etc., should be kept in separate drums since they will not need the same storage precautions as askarel. Containment of Solid Wastaa 1. Wrap any contaminated clothing, clean-up materials, lighting ballasts, or pieces of contaminated wood and metal in a heavy duty plastic bag and tie it shut. 2. Place the plastic bags in a good quality 45-gallon steel drum of Number 16 gauge or heavier, fitted with a remov able steel lid and a gasket with a screw-lug tightening ring. Pack the drum well with sawdust. 3. Shovel any soil, gravel, snow, etc. contaminated by askarel directly into the same type of 45-gallon drum. 4. Seal the drums, label them, and move them to the storage area using routine material handling precautions. 5. See Booklet 5 for storage instructions. Tied Plastic Bag Containment of Askarel Liquid Askarel liquid and other liquids which have been contaminated by askarel should be stored in a good quality, double-bung, 45-gallon steel drum of Number 16 puge or heavier. The bungs should provide a leakproof seal. Leave at least a 3" - 4" air space inside the drum to allow for expansion of the liquid. PCB Label HONS 002092 4-10 4.5 LABELLING OF PCB WASTES AND DBCARDED EQUIPMENT Drums containing waste PCB liquid, materials contaminated by askarel, and scrapped electrical equipment should each be labelled with the Number 4 - Severe Hazard label which is available from the Environmental Protection Service. It is a non-serialized label which is used for many different types of chemicals. When used with PCBs, it should be filled out as follows: HEALTH -4 FIRE -1 ENVIRONMENT -4 REACTIVITY - 1 CONTENTS - PCBs are contained inside DISPOSAL - (lpave blank) HANDLING - Class 9 ORIGINATOR - (your company name) TELEPHONE - (your telephone number) DATE -(the date) The label will then contain the informa tion that is neeeesary for a PCB container either being stored or later being shipped to a disposal site. The code numbers that are written into the top line of the label indicate the severity of PCB in that particular situa tion. For example: PCB is a high health hazard because of its effect on the food chain, it will not burn easily, it is a high hazard to the environment, and it does not react very easily with other chemicals or materials. The handling classification is a special coding system pertaining to the handling and transportation of hazardous goods. See Booklet 7 if details are required. How to Apply tlw Label Peel the protective backing from the label and press it firmly against a clean, dry area where it is most likely to be se<m by personnel. Rub the surface of the label well to ensure it is securely attached. HONS 002093 4-a 4 SEVERE HAZARD EXTREME DANGER HEALTH SANTE 1 INCENOIE CONTENTS /CONTICNT (environment I ENVIRONNEMENT reactivity | REACTIVITE OISPOSAL ELIMINATION ORIGINATOR / EXPEDITEUR 04-1914 (01 77) HANDLING MANIPULATION T6l. TEL OATE FOR USE ON PCB WASTES AND DISCARDED EQUIPMENT HONS 002094 4-12 4.6 APPENDIX HONS 002096 4-13 ENVIRONMENTAL PROTECTION SERVICE OFFICES Beaton Pacific Northwest Ontario Quebec Atlantic Address Teleohone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 2S St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5640 Environmental Protection Service 4th Floor 1550 de Maisonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J 1M5 Emergency (902) 426-6200 Office (902) 426-6141 HONS 002096 HONS 002097 BOOKLET 5: STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS Prepared by: Contract OSB77-08285 for: Stothert Engineering Ltd. Environmental Protection Sendee, Department of Fisheriee end Environment March 1979. HONS 002098 BOOKLET 1: BOOKLET 2; BOOKLET 3i CROSS - REFERENCE INDEX INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1.5 Federal Government Legislation On PCB 1.6 The Future 1.7 Appendix PAGE Z-2 1-3 1-4 1-5 1-6 i-e 1-9 IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCS 2.6 Appendix 2-2 2-3 2-6 2-8 2-10 2-15 PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program ForTransformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program For Capacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-t* 3-15 3-17 HONS 002099 BOOKLET 4t BOOKLET 5i BOOKLET 6: PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Sale Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4-2 4-3 4- 4-7 4-8 4-9 4-9 4-10 4-12 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 3.1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 5-4 5-7 s-s 5-9 5-13 S-i7 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-S 6-9 6-13 HONS 002100 BOOKLET T: BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.S Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAST 7-2 7-3 7-* 7-6 7-7 7-9 -2 8-3 S-4 8-7 HONS 001101 5-1 FOREWORD This booklet is number 5 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002102 5-2 5.1 GENERAL Askarel storage is an ongoing concern. When askarel liquid and materials contaminated by askarel are placed in storage, they just cannot be forgotten about. There is an ever present environ mental hazard with this chemicaL Putting them in storage is only the begin ning. The next step is periodic inspections to ensure that the integrity of all contain ers of askarel remains in good condition. This will ensure that there is no danger of askarel leakage to the environment. These are the sort of contaminated articles that will require conscientious effort in order to provide safe and effect ive storage. Information on how to store them are Included in this booklet: Maw articles - Spare askarel capacitors - Spare transformers filled with askarel Discarded articles - Used capacitors - Scrapped transformers - Scrapped lighting ballasts Askarel wastes - Askarel drained from equipment - Askarel collected in drip pans placed under askarel equipment Contaminated materials - Earth, asphalt, snow, gravel, etc. contaminated by askarel - Absorbent material used for clean up of askarel leakage and spills Clothing - Clothing worn when working with askarel Askant-Handling Equipment - Pumps and hoses used to transfer askarel from equipment to containers It should be remembered that individuals who discharge askarel, or who allow askarel to be discharged into waters frequented by fish, can be prosecuted under the Federal Fisheries Act. Further more, discharge of askarel into the environment may be in violation of other statutes, specifically the proposed control on PCB release under the Environmental Contaminants Act and certain provincial pollution control statutes. Note Companies or individuals intending to construct commercial collection or stor age facilities for PCB wastes should also refer to the Guideline on Central Collec tion and Storage Facilities for Waate Materials Containing PCBs, published by the Environmental Protection Service. This document outlines the requirements, in addition to those presented here, con cerning the bulk storage of PCB wastes and the requirements for the operation of such a commercial facility. MOMS 002103 5-3 5.2 SELECTING A STORAGE SITE Th first matter to consider is, "Where can askarel and askarel contaminated articles be safely stored?" These factors should be kept in mind when selecting a site: 1. Indoor storage is preferable to outdoor storage. This will eliminate the danger of rain water runoff and contamination of melting snow. If outdoor storage is absolutely neces sary, contact the Federal Environ mental Protection Service for inform ation on how to assess the leaking potential, geological conditions, and surface water runoff possibilities of the outdoor storage area. 2. One large storage site is better than several small sites. This will minimize the amount of supervisory effort required to monitor the askarel. 3. A special building or separate storage area with no vehicle traffic is ideal. This will minimize the potential for mechanical damage. The site should also be handy enough for regular inspections. 4. The storage area should be large enough: -For future askarel storage require ments. -To enable aisleways to be set up between rows of containers for periodic inspections. -To segregate containers which are used frequently from containers which are never used once filled. This will minimize the amount of handling in the storage area and the possibility of accidental spilling. 5. An ideal indoor storage area should be located where there is: -Non-corrosive atmosphere to prevent rusting of containers. -Air ventilation to the outside. -Fresh air make-up in case of emergencies. -Normal room temperatures (about 25C) or cooler. -A concrete floor with no floor drains. If floor drains are present, they should be properly stoppered. -Very dry surfaces. 6. Above all else, select a site that can be used for many years to come. Make-shift interim sites are hazardous because of the additional material handling which will be required to transport the askarel to a final site. HONS 002104 5- 5.3 IDBAL STORAGE FACILITIES Moor Storage Atm A storage area which is located indoors would ideally have these features: IDEAL INDOOR STORAGE AREA Fresh Air Inlet % No open floor drains in vicinity All floor cracks sealed HONS 002105 5-5 (A) Security fence of chain-link con struction. (B) Padlocked door. (C) Concrete floor, with no floor drains. All cracks and expansion joints between slabs sealed with com pound. Floor painted with epoxy paint to prevent askarel from work ing its way through the concrete. Note: certain paints and compounds deteriorate in PCB. Check with the manufacturer before using. (D) Concrete curb around perimeter of storage area. Inside of curb painted with epoxy, same as the floor. See Booklet 8 for more information on constructing such containment systems. (E) Sealing compound (grouting) at earner of curb to prevent leakage under the curb. (P) Ramp over concrete curb, into storage area. (G) Drums containing used askarel, used capacitors, and contaminated materials. Stored on pallets for mobility. (H) Drums containing unused askarel stored on pallets. ) Spare drums for askarel materials. (J) Uncontaminated clean-up materials stored in bin and labelled. <K) Locker for garments worn when working with askarel. (L) Pumps and hoses for use with askarel laid in an open pan to catch drips. (M) Scrapped transformer in protective crate. (N) Spare new capacitors stored on pallets. (0) First aid kit. (P) PCB label on door. HONS 002106 5-6 Outdoor Storage Area As mentioned earlier in this booklet, outdoor storage of PCB containers and equipment is definitely not recommended. The potential for escape to the environ ment is Just too great. In a situation where there is not any room to store a scrapped transformer inside a building, however, it may have to be stored outside regardless. These are some of the factors that should influence the design of a suitable outdoor storage facility: - Will the transformer be stored full or empty? The containment system for an empty transformer can be sized much smaller. There is only a small amount of askarel retained in the core of the transformer. - Is the paint finish of the transformer suitable to protect the transformer without the need to shelter it against weather, fly ash, etc? Check with the manufacturer of the transformer for the durability of the paint finish. - Would the transformer be vandalized or tampered with if not enclosed? - Is the transformer being stored in a high traffic area where it might accidentally . be backed into by vehicles? - If the contents of the transformer did leak into its containment system, how would maintenance personnel clean up the contamination? The drawing on this page shows an outdoor storage facility constructed of fiberglass sheeting. The transformer is mounted on a concrete floor to keep if from shifting, and a concrete curb is integrated into the floor to provide containment of any leak age from the transformer. Both the floor and the curb are painted with an appropriate sealer. The sealer paint must be resistant to askarel or any other solvents used for flushing the trans former. See Booklet 8 for more inform ation on designing containment systems. OUTDOOR STORAGE FACILITY FOR DE-ENERGIZED TRANSFORMER PCB Label MetalGuard Post MONS 002107 5-7 5.4 PRECAUTIONARY GUIDELINES By following these precautionary guide lines, problems associated with askarel storage should be avoided: 1. Appoint one person as the official custodian in charge of the askarel storage area. Ensure that all transfers of items into and out of this area are authorized by this one person. 2. Check that the custodian is familiar with the contents of this booket and ' other booklets in this series. I 3. Display emergency procedures for I cleaning up spilled askarel in an obvious location in the storage area. 4. Post several large and obvious signs in the storage area to inform workers that askarel is being stored on the premises and that caution is necessary in the area. Keep the door locked for security. 5. Keep a first aid kit handy in the storage area, for askarel treatment. B. Store askarel liquid and askarel contaminated materials in steel drums of heavy construction to avoid leak age. Number 16 gauge and heavier gauge drums are suitable. See Booklet 4 for packing instructions when filling the drums. Liquids should be stored in a double bung, dosed top, 45-gallon drum. Solid items such as discarded capa citors should be stored in a 45-gallon drum fitted with a removable steel lid and PCB resistant gasket (with a boltj type closure), i 7. Do not stack containers of askarel or askarel contaminated material. They may fall and break open. 8. Ensure all containers for askarel are always well-painted to prevent rusting. 9. Scrapped transformers which require movement to the storage site should be drained of askarel and flushed out first. Follow the 9 steps in Section 4.4 of Booklet 4 for flushing instructions. 10. While a transformer is in storage, hang a metal catch bucket from the drain spouts to localize any small leakage from the spouts of the transformer. This is a precaution in case the seals of the valve deteriorate. More exten sive leakage will be contained by concrete curbs, etc. Also, remove the handles from the valves. 11. Ensure that all containers, boxes, etc. in the storage area are well labelled. See Section 5.6 of this booklet for labelling instructions. Keep clean-up materials handy at the storage site. 12. Install smoke detectors around the storage area and in the vicinity of askarel equipment. They may provide an early warning of a fire and thereby enable it to be extinguished before there is any damage to the askarel containers or to the environment. 13. Seal all openings, ventilation duets, cracks around doors, cables passing through walls, etc., between rooms containing askarel and other parts of the building. This precaution will localize the dispersion of any contami nated soot or fumes resulting from a fire, thereby making clean up after a fire much more complete (see Booklet 6 for clean up instructions). 14. Set up a record-keeping system to keep track of all itema entering and leaving the storage area and of their whereabouts. See Section 5.7 of this booklet for details. MONS 002108 5-e 15. Maintain an inspection program for the storage area. All containers should be periodically checked for signs of leak age, and any sskarel leakage cleaned up immediately. See Booklet 6 for clean-up instructions. 5.5 FIRE FIGHTING SAFETY If a fire does break out in a building or area where askarel is being stored or being used in transformers or capacitors, inform the Fire Department to take special precautions. There are two factors to emphasize: 1. Personal Safety Askarel will not burn easily, but the askarel vapours heated in a fire can be extremely irritating. The safe handling techniques of Book let 4 still apply. In particular, the firemen should be informed that a self-contained breathing apparatus is required, as well as conventional fire fighting clothing with coated gloves. The garments may be contaminated by askarel vapours and soot so they should be disposed of later. See Booklet 8 for Instructions in clean up after the fire. 2. Environmental Safety Water runoff should be minimized to prevent contamination to the environ ment. A concrete curbing already in place or sandbag diking would help to contain runoff. If at all possible, foam or dry chemicals rather than water should be used to extinguish the fire. HONS 002109 5-9 5.6 LABELLING STORAGE AREA Entrances to Storage Area Each entrance way into a chain link area or storage compound containing PCBs should be posted with the non-serialized version of the 6 inch by 6 inch blaek-andwhite PCB label. This will properly inform personnel in the area that PCB is being stored and caution is necessary. With such information, they might also notice a situation which could otherwise go unreported until an authoriz ed employee make his formal inspection rounds. PCB Wastes and Discarded Equipment Drums containing waste PCB liquid, materials contaminated by askarel, and scrapped electrical equipment should each be labelled with the Number 4 - Severe Hazard label, also available from the Environmental Protection Service. It is a non-serialized label which is used for many different types of chemicals. When used with PCBs, it should be filled out as follows: HEALTH -4 FIRE -1 ENVIRONMENT -4 REACTIVITY - 1 CONTENTS - PCBs are contained inside DISPOSAL - (leave blank) HANDLING - Class 9 ORIGINATOR - (your company name) TELEPHONE - (your telephone number) DATE - (the date) The label will then contain the informa tion that is necessary for a PCB container either being stored or later being shipped to a disposal site. The code numbers that are written into the top Hne of the label indicate the severity of PCB in that particular situa tion. For example: PCB is a high health hazard because of its effect on the food chain, it will not burn easily, it is a high hazard to the environment, and it does not react easily with other chemicals or materials. The handling classification is a special coding system pertaining to the handling and transportation of hazardous goods. See Booklet 7 if details are required. Spare PCB Equipment and Unused PCB Liquid Spare askarel transformer, spare capa citors, and unused PCB liquid should each be labelled with the serialized versions of the black-and-white PCfi label. Use the 6 inch by 6 inch label tor transformers and drums of unused askarel. Capacitors should be labelled with the 3 inch by 3 inch label. How to Apply the Labels Peel the protective backing from the label and press it firmly against a clean, dry area where it is most likely to be seen by personnel. Rub the surface of the label well to ensure it is securely attached. HONS 002110 5-10 ATTENTION PCBCONTAINS CONTIENT DES POLYCHLORINATED BIPHENYLS BIPHENYLES POLYCHLORES A TOXIC ENVIRONMENTAL CONTAMINANT SCHEDULED UNDER THE ENVIRON MENTAL CONTAMINANTS ACT IN CASE OF ACCIDENT SPILL OR FOR DISPOSAL INFORMATION. CONTACT THE NEAREST OFFICE OF THE ENVIRONMENTAL PROTECTION SERVICE ENVIRONMENT CANADA PRODUITS TOXIQUES MENTION NES DANS L ANNEXE DE LA LOI SUR LES CONTAMINANTS DE L ENVIRONNEMENT EN CAS D ACCIDENT OU DE D6VERSEMENT OU POUR SAVOIR COMMENT LES ELIMINER. CONTACTER LE BUREAU DU SERVICE DE LA PROTECTION DE L ENVIRONNEMENT MINISTERE DE L ENVIRONNEMENT LE PLUS PRES FOR USE ON ELECTRICAL ROOM, TRANSFORMER VAULT, CHAIN LINKED AREA AND STORAGE COMPOUND HONS 002 111 5-n 4 SEVERE HAZARD EXTREME DANGER HEALTH $ANTE i Fine | INCENOIE CONTENTS /CONTIENT 1 ENVIRONMENT 1 ENVIRONNEMENT I REACTIVITY | REACTIVITE DISPOSAL ELIMINATION ORIGINATOR / EXPEOITEUR 04*1914 (01 T7) HANDLING MANIPULATION TEL.-------------------------------TEL OATE FOR USE ON PCB WASTES AND DISCARDED EQUIPMENT HONS 00<U12 5-12 ATTENTION PCBCONTAINS CONTIENT OES POLYCHLORINATED BIPHENYLS BIPHENYLES POLYCHLORES A TOXIC ENVIRONMENTAL CONTAMINANT SCHEDULED UNDER THE ENVIRON MENTAL contaminants ACT IN CASE OF ACCIDENT. SPILL OR FOR DISPOSAL INFORMATION. CONTACT THE NEAREST OFFICE OF THE ENVIRONMENTAL PROTECTION SERVICE ENVIRONMENT CANADA PROOUITS TOXIQUES MENTION NES DANS L ANNEXE DE LA LOI SUR LES CONTAMINANTS DE L ENVIRONNEMENT EN CAS D ACCIDENT. OU OE DEVERSEMENT OU POUR SAVOIR COMMENT LES ELIMINER. CONTACTER LE BUREAU DU SERVICE DE LA PROTECTION OE L ENVIRONNEMENT MINISTERE DE L ENVIRONNEMENT LE PLUS PRES PR 20108 HONS 002113 5-13 S.7 RECORD-KEEPING A properly kept record system is advisable for the storage area. It should be updated each time an item is taken out or brought into the storage area. By keeping track of all askarel contami nated articles, it will minimize the possiblity that anything from the storage compound might be left lying around to contaminate the environment. Information Recommended The following types of information are recommended for the storage area. The Federal Government is presently consider ing new regulations on this topic: Date - The date that the goods are removed from or brought into the storage area. Description - A description of the goods that are being transferred. Include name plate description, serial numbers, PCB label registration number, and quantity. Destination/Source - An indication of where the goods are being taken to or where they have come from. Storage Code - For outgoing goods, an identification number indicating where the goods were stored in the storage area. For example: a barrel number or box number. Alternatively, if goodb are being brought Into the storage area, an Identification of where they are being stored. For example: a barrel number or pallet number. Authorization and Department - The name and department of the person in charge of the transfer of the goods. This listing may be modified to suit individual situations. A typical Askarel Storage Record sheet is shown following this section of the booklet. It may be duplicated directly from this booklet or modified. The two sheets following the Askarel Storage Record form show an example of how the form may be used for the transfer of a discarded capacitor from the plant area to the storage room. In this example, the barrel is removed from the storage area and taken to the location of the capacitor. Another sheet would also be required to record the transfer of other materials such as plastic bags, wipe-up materials, special clothing, etc. Setting Op the System Step 1 - Record all items in the storage area on its appropriate Askarel Storage Record sheet. Step 2 - Update the record sheets immediately when askarel gooth are being taken out or brought into the storage area. Step 3 - Occasionally double-check the records against the items in the storage area. HONS 00 iH4 I1 OATS 5-14 askarel storage: record FOR DRUMS, CAPACITORS, TRANSFORMERS, OTHER DESCRIPTION DESTINATION/ SOURCE STORAGE CODE AUTHORIZATION t DEPARTMENT i HON.i 002115 5-15 ASKAREL STORAGE RECORD 5-16 OATS ASKAREL STORAGE RECORD foai drums, (Capacitors} transtormers, othb* 11 DESCRIPTION OESTt NATION/ SOURCE STORAGE CODE AUTHORIZATION & DEPARTMENT So mvHA c*.p*t^f**-O9I&C900AO FV*-- -m-1 RuJL WadU-* Psj p^v^p - fife v 3. fV, <LL*W CH ^<vt, cov ! HONS 002117 5-17 5.8 APPENDIX nous 002118 5-18 ENVIRONMENTAL PROTECTION SERVICE OPP1CE3 Pacific Northwest Ontario Quebec Atlantic Address Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604)666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5840 Environmental Protection Service 4th Floor 1550 do Maisonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J IMS Emergency (902) 426-6200 Office (902) 426-6141 MONS 002119 Booklet 6 HONS 002120 BOOKLET 6: CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB Prepared by: Contract OSB77-08285 for: Stothert Engineering Ltd. Vancouver, B.C. Environmental Protection Service, Deportment of Fisheries and Bnironmant March 1979 HONS 002121 I CROSS - REFERENCE INDEX BOOKLET 1; INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? i 1.4 Is PCB Still Available? l.S Federal Government Legislation On PCB ! 1.6 The Future 1.7 Appendix PAGE i-2 1-3 1-* 1-5 i-e l-e i- BOOKLET 2: IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix 2-2 2-3 2-e 2-6 2-10 2-15 BOOKLET 3: PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3-2 3.2 Anatomy Of A Transformer 3-3 3.3 Typical Problems With Transformers 3-7 3.4 Preventive Maintenance Program For Transformers 3-9 3.5 Anatomy Of A Capacitor 3-13 3.6 Typical Problems With Capacitors 3-ia . 3.7 Preventive Maintenance Program For Capacitors 3-1S 3.8 Appendix 3-17 HONS 002122 BOOKLET 4i BOOKLET 5; BOOKLET 6: PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix ,_2 *_3 4_6 4.7 *_a 4_9 *_9 *_I0 _l2 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5. 1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix s-2 5-3 s- 5-7 3-8 5-9 s-13 5-17 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-z 6-3 6-5 6-9 s-13 HONS 002143 BOOKLET 7: BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGE 7-2 7-3 7-4 7-6 7-7 7-9 -2 8-3 8-4 8-7 HONS 002144 6-1 FOREWORD This booklet is number S in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002125 6-2 6.1 GENERAL Molt of the recommendations and proce dures presented in this series of booklets have been concerned with the prevention of emergency situations involving PCBs. Unfortunately, regular maintenance, con scientious handling, safe storage, and regular inspection programs are but a first line of defence against the prevention of PCB emergencies. These practices cannot guarantee that an emergency situation will never occur. For this reason, a second line of defence is a wise pre caution! That is the subject of this booklet. The emphasis in this booklet will be to provide a second line of defence for PCB transformers and capacitors which are already installed and in service. Details on clean-up procedures for askarel are also included for reference purposes. It should be remembered that individuals who discharge askarel, or who allow askarel to be discharged into waters frequented by fish, can be prosecuted under the Federal Fisheries Act. Further more, discharge of askarel into the environment may be in violation of other statutes, specifically the proposed control on PCB release under the Environmental Contaminants Act and certain provincial pollution control statutes. In the event of a spill, the onus is on the responsible parties to ensure that the contamination is cleaned up properly. HONS 002126 6-3 S.2 WHAT KIND OF ASKAREL RELEASES CAM OCCUR? This section describes the type of situa tions that should be protected against. Transformers 1. Catastrophic Failure This can only happen to a transformer which is energized. It is a rupturing or splitting open of the transformer due to a combination of factors: a build up of internal pressure caused by a power supply problem, failure of the pressure relief valve opening quickly enough, and failure of the electric power being disconnected in sufficient time. As a result, an opening can force itself through the weakest point in the trans former casing, gaskets, or cooling fins. Alternatively, the sides of the trans former may just balloon out slightly, provided the pressure is not excessive and there are no weak spots in the transformer. Either of two types of askarel releases can occur, depending upon whether the rupture of the weak point is above or below the level of the askarel liquid in the transformer: (1) If the opening is above the level of the askarel, a mixture of hydrogen chloride gas, askarel vapour, and askarel droplets will be sprayed out through the rup ture and away from the trans former. (2) If the opening is below the level of the eskarel, the pressure will force a spray of askarel liquid out through the rupture. As the pressure is reduced, the askarel will drain out down to the level of the rupture. Rupture ABOVE Askarel Level Rupture BELOW Askarel Level Either of these situetions may be avoided by ensuring that the transfor mer has an adequate design safety factor, by carrying out regular impac tions to detect weak points, and by checking that presawe-relief valves and protective disconnect switches ere in good working order. See Booklet 3 in this series for an inspection plan for transformers. 2. Controlled Pressure Baleses This can only happen to a transformer which is energized. It is a release of pressure through the pressure-relief MOMS 002127 6-4 valve. The situation is due to a buildup of internal pressure caused by a power supply problem and failure of the electric power being disconnected in sufficient time. As a result of the release, a momen tary burst of hydrogen chloride gas, aslcarel vapour, and askarel droplets will be sprayed out through the valve. Depending upon the pressure, the sskarel droplets may spray away from the transformer rather than run down the outside of the casing. 3. Askarel Leakage This can occur to a transformer which is either energized or in storage. It is a leakage through deteriorating gaskets, rusted-through cooling fins or casing, broken high voltage bushings or physically punctured cooling fins and casing. The drain spouts on a trans former are also very fragile. Askarel will drain or drip out down to the level of the opening in the transformer. If the level of the liquid in an energised transformer becomes too low, a controlled pressure release or catastrophic failure may then occur because the transformer will no longer be properly cooled or insulated. Capacitors 1. Catastrophic Talks* This can only happen to a capacitor which is energised. It is a rupturing or splitting open of the capacitor casing due to a build-up of internal pressure and failure of the power supply being disconnected in sufficient time. As a result of the excessive pressure, an opening can force Itself through the weakest point in the easing, and askarel will be sprayed out. Alterna tively, the sides of the capecitor may Just balloon out slightly if the pressure is not excessive and there are no weak spots in the casing. Routine inspections to detect weak spots, dented cases, and leakage are a good practice to prevent cataatrophic failure. See Booklet 3 in this series for an inspection plan for capacitors. 2. Leakage This can occur to a capacitor which is either energized or in storage. It is a leakage through a rusted or physically damaged casing. Askarel will drain or drip out down to the level of the opening. If the level of the liquid in an ener gized capacitor becomes too low, a catastrophic failure may then occur because the capacitor will no longer be properly cooled or insulated. HONS 002128 6-5 6.3 CONTAIMMKNT SYSTEMS Custom-designed containment systems, sized for the shape and location of each piece of askarel equipment, are the most viable alternative for coping with the accidental release of askarel from elec trical equipment. These systems may not catch all of the askarel escaping in a release, but they will likely trap enough askarel to prevent a serious situation from becoming a major hazard to human health and the environ ment. Containment should be considered in all situations, but especially im - food processing plants grain handling facilities - downtown core areas of cities - locations close to waterways and drainage facilities Materials Compatible with Askarel Askarel is a powerful solvent. Although askarel is a powerful solvent, these materials will not react or deterior ate in the liquid. They may be incorporat ed into the design of a containment system: - Wood, paper, paperboard - Asbestos, glass, ceramic, bakelite, sand - Aluminum, brass, stainless steel, lead, tin, copper, galvanized iron, black iron - Cork, nitrile rubber, cork-nitrile material (satisfactory for a limited period of time) - Vlton material (by DuPont), Teflon, Silastic SO material (by Dow Coming) - Many silieone elastomer materials (verify resistance to askarel first) - Glyptal 1276 cement (by General Electric) - Epoxy cement (such as Scotehcast Resin #4 by 3M) - Dewaxed orange shellac - Paints with an epoxy-urethane resin (such as APC 60-410 and APC 60-411 by Argosy Industrial Coatings) - Certain grouting compounds (check with manufacturer first) Materials Not Compatible with Askarel These materials should definitely mt be used in any askarel containment system since their ability to withetand the solvent action of askarel is limited or negligible. They will eventually soften and weaken: - .'Otauiic materials other than wood ailil (iafiifc,,. For example: vaifpee, laOlgaaafe, and common peinp/giMald not M 9SS&,unless tested f|gpi:" - Natural rUMkMr^neoprfm;jr&ber, butyl rubber ...... " - Lucite (mthyIieOtheSirylets) - Hypalon (ehMflWWliltai) polyethy lene) - PVC (phttyl eMorlfcfc. polyvinyl formal!:.!-:'-' - KnnMpsfl. Hycar P > HONS 002129 6--6 Dssip Principles Bearing In mind the type* of askarel releaiee that can occur from electrical equipment (e.g. sprays, drips, large ruptures), these design principles should be considered when designing suitable containment facilities! 1. An energized transformer requires adequate air circulation to keep it from overheating. Do not construct the sides of a containment facility so high that they block the flow of air to the cooling fins of the transformer. Also, leave sufficient room around the base of the equipment to enable inspections and clean-up to be carried out. 2. If splash walls are constructed around a capacitor to contain an askarel spray, allow for sufficient entry of circulating air and room to carry out maintenance functions on the cepaeitor. Design the splash walls so that any spray will drip down into a eontainment system located beneath the capacitoris). 3. An entire room can be used as a containment facility provided the floor is concrete, all floor cracks are plugged and the floor is well-sealed. The doorway will have to be blocked off with concrete curbing. Grout the Joint at the base of the wall and the floor. The walls of the room should be painted with a sealer paint to prevent askarel from an askarel spray from penetrating into the concrete surface. 4. Metal and concrete containment systems are more durable and reliable than sand-bagging. Sand-bag dikes should only be considered for emergency containment of a spill. 5. The containment system should be sized to hold the full contents of the transformer (or capacitor) plus an allowance for the volume of the trans former base sitting inside the contain er. 1 Imperial gallon of askarel occupies roughly 1/6 of a cubic foot of volume, therefore, a transformer containing 12S gallons will contain almost 21 cubic feet of askarel (1 litre of askarel occupies roughly 1/2S of a cubic foot of volume). If containers of askarel are being stored inside the containment facility, each 45 gallon drum will contain roughly 7-1/2 cubic feet of askarel. Size the containment facility to hold future requirements also. 6. Allow sufficient work space for clean ing up askarel which has been released from equipment or containers. 7. If metal trays are being fabricated for use under individual transformers or capacitors, ensure the weld is continuous, not spot welded. The trays can be very simple in design since they will not be subjected to mechanical stress. They can be home-fabricated or purchased from transformer manu facturers. 8. It is advisable to hang metal catch buckets from transformer drain spouts to localize small amounts of leakage from the spouts. This makes clean up and disposal much easier. 9. If a transformer requires Jscking in order to slide a metal tray underneath, Jack only at approved bearing surfaeea on the transformer. This will prevent damage to the transformer tank. HONS 002130 6-6 (A) 10. Where severe! transformers are located In a common area it is advisable to provide each with a containment system to reduce the area to be cleaned in the event of a spill. .11 Rain water accumulating in a containment system located outdoors will not seriously defeat the purpose of the container. Askarel is much heavier and will displace the water. However, to avoid container flooding as well as corrosion of the transformer it is i recommended that a roof be erected over askarel-filled transformers located outdoors. 12. Askarel transformers located indoors are not required to have the protection of a concrete vault, and as such are more vulnerable to damage from a fire in the building. If the fire risk is present, a containment system constructed of plywood covered with fibreglass would not be desirable. 13. The pressure relief vent on top of a transformer may release a mist of askarel amounting to several litres on sudden transformer failure. If a ventilation duct from the pressure vent is provided at all it should direct the mist down into the containment system rather than to the atmosphere exterior to the building where the dispersal of askarel would be uncontrolled. HONS 002131 6-7 Soma Designs The following 3-stage drawing shows a de energized transformer being raised so that a partially fabricated metal tray can be slid underneath. A fork lift truck could also be used for lifting, provided there is sufficient room to manoeuvre. After the end piece is welded on, the entire tray should be painted with an askarel-resistant paint to prevent rusting and make clean up easier. MQNS 002X32 6-8 The following drawing shows a design using concrete curbing around a concrete floor. If several transformers were locat ed in the same compound, it would be advisable to construct concrete curbing around and between each transformer to confine an askarel release to as small an area as possible. This would make clean up much easier. Paint the concrete to seal it against the penetration of askarel. OUTDOOR CONTAINMENT SYSTEM FOR ENERGIZED TRANSFORMER Curbing between Transformers These guidelines are also helpful: 1. Concrete surfaces should be thorough ly cleaned of all dirt, grease, etc. before plugging cracks or applying any sealing paint. Use an industrial strength cleaner if necessary. 2. The adhesion between new concrete curbing and an old concrete floor can be insured by: (1) Chipping down the old concrete to a fresh level. (2) Installing 5/S" self-drilling anchor pins on 3 foot centers along the perimeter for the new curb. Leave 3" - 4" exposed above the surface of the floor. (3) Preparing the mating surface with a concrete bonding agent. Approach concrete accessory suppliers for the necessary sup plies. 3. All cable-entries to a transformer via the floor should be well-sealed at the floor entrance with a caulking com pound. 4. Roof-water drainage should be direct ed away from the inside of the con tainment facility to prevent a build-up and possible runoff of contaminated water. 5. Drain spouts incorporated into the base of concrete curbing are not recommended for leading off aakarel collected inside the containment area. They may leak and will certainly allow spillage onto the ground during the drainage process. HONS 002133 6-9 6.4 CLEAN OP PROCEDURES General A variety of absorbent materials are suitable for soaking up askarel (PCB) collected in containment systems and for cleaning up larger types of spills. Many of them are also suitable for use with oil spills. The following types of materials should be obtained and kept available in case of an emergency involving PCBs: - Sawdust - Vermiculite - Sorbent-C (by McAllister Pollution Control, Montreal) - Imbiber Beads (by Dow Chemical, Sarnia) - Hy-Dry (by Tennier Chemicals, Hamilton) - Diaaorb (by Diamond Shamrock, Cleveland, Ohio) - Stay-Dry (by Waverly Mineral Produots, Philadelphia) - Oil-Dry (by Waverly Mineral Products, Philadelphia) - Oil-Sorb (Seneca Paper Products, Oakville, Ontario) - Activated charcoal - Soil with a high humus content. Products such as Diasorb by Diamond Shamrock are packaged in the form of one-half cubic foot pillows and can pick up and retain most types of hazardous chemicals at a ratio of one gallon of chemical per one pound of Diasorb mater ial. Solvents suitable for wiping up and decon taminating surfaces exposed to askarel are: - Varsol - Kerosene - Turpentine - *2 Fuel Oil - Trichlorobenzene - Trichloroethane - Toluene Acetone is not recommended because of the flammability danger with this type of solvent. Leakage Into Containment Systems In the event there is contamination to the environment, have someone notify the Environmental Protection Service as soon as possible. See the phone numbers listed in the back of this booklet. These are the steps to follow for clean up and decontamination of the area: 1. Be safety conscious to avoid personal contamination. Observe the routine safety precautions and handling guide lines prescribed in Booklet 4. 2. Use a pump to transfer large volumes of askarel into storage drums. Alternatively, soak up the leakage using the absorbent materials listed at the beginning of Section 6.4. Drop these soaked materials directly into storage drums. 3. Wipe up the remaining askarel using a mop, cleaning rags and paper towels. 4. Wet rags with one of the solvents listed at the beginning of Section 6.4 and wipe down the containment area to remove traces of askarel contami nation. 5. Dispose of all contaminated materials and waste askarel as indicated in Booklet S. RONS 002134 6-10 Spills on Concrete and Asphalt With this type of spill, the askarel will flow to low lying areas and collect in pools. If the surface has not been treated with PCB resistant paint, there will be some penetration of askarel into the surface. In the event there is contamination to the environment, have someone notify the Environmental Protection Service as soon as possible. See the phone numbers listed in the back of this booklet. These are the steps to follow for clean up and decontamination of the areas 1. Be safety conscious to avoid personal contamination. Observe the routine safety precautions and handling guide lines prescribed in Booklet 4. 2. Plug or dike all drains to sewers. If spillage occurs on a roadway, dike the area to prevent askarel from soaking into the shoulder of the road or from running into nearby bodies of water. 3. Soak up the askarel using absorbent materials listed at the beginning of Section 8.4. If the absorbent material is a loose fill type, sweep it around the area to soak up askarel. Drop the soaked absorbents directly into storage drums. 4. Wipe up the remaining askarel using a mop, cleaning rags and paper towels. 5. Wash and wipe up the area using the solvents listed at the beginning of Section 8.4. Use additional absorbent materials for wiping up. Repeat this procedure to decontaminate the sur face. 8. Dispose of all contaminated materials, S.gravel and soil as indicated in Booklet 7. Obtain one inch deep core samples of the concrete or asphalt to determine how far the askarel has penetrated into the surfaae. The surface material will have to be removed to the level of the contami nation. In the meantime, block off the area to pedestrian and vehicle traffic. Cover the area with plastic sheeting to shed rainfall until the excavation work is complete. Spills on Soil With this type of spill, the askarel will soak into the ground and cling to individual particles of soil. It may also flow to low lying areas if the ground is hard packed. During rainfall, the soil particles and askarel wtn be csrried down stream to larger bodies of water. Have someone notify the Environmental Protection Service as soon as possible that contamination has occtrred. See the phone numbers listed in the back of this booklet. These are the steps to follow for clean up and decontamination of the area: 1. Be safety conscious to avoid personal contamination. Observe the routine safety precautions and handling guide lines prescribed in Booklet 4. 2. Build dikes or trenches to contain the askarel to as small an area as possible. This will also help to keep it from flowing into bodies of water. Use plastic sheeting, temporarily, to prevent askarel from soaking into the ground. 3. Use a pump to transfer pools of askarel into storage drums. Alternatively, soak up the pools of spilled askarel by using the absorbent materials listed in the beginning of Section 8.4. Be gentle to minimize the penetration of askarel deeper into the soil. Drop the soaked materials directly into storage drums. MONS 002135 6-11 4. Remove all soil which is visibly stained with askarel. Shovel it directly into storage drums. 5. Dispose of all contaminated materials and drums of soil as indicated in Booklet 5. Decontaminate earth-hand ling equipment by rinsing and wiping using solvents. 5. Obtain 2 feet deep core samples in the spill site to determine how far the askarel hes penetrated vertically and horizontally beyond the excavated area. This contaminated soil should also be removed for disposal. In the mean time, block off the area to pedestrian and vehicle traffic and cover the area with plastic sheeting in a manner which will shed rainfall. 7. After the second excavation is complete, obtain another set of core samples of the area as a safety check of the completeness of the excava tions. Dispose of all additional con taminated soil. Decontaminate earth handling equipment by rinsing and wip ing using solvents. 6. Wells and other bodies of water in the vicinity should then be monitored for traces of eakarel contamination. SpiBs into Water Since askarel hes a higher specific gravity than water, askarel in a body of water will settle to the bottom -- provided the water is not flowing or agitated by waves. In a still body of water, the askarel will collect in pools on the bottom or soak into the sediment material. Have someone notify the Environmental Protection Service as soon as possible that contamination has occurred. See the phone numbers listed in the back of this booklet. This is the initial step to taka if an askarel spill has reached a waterway: Take action to minimize agitation of the water. Close off the body of water to all boat traffic, and dam the contaminated area upstream and downstream (the incoming water should be by-passed around the con taminated section). The next step is clean up. The Environ mental Protection Service can best advise on the clean up proeedires appropriate for the particular situation. A variety of techniques are possible, such as the use of suction dredges to collect pools of askarel and contaminated sediment, and the use of absorbent materials to soak up askarel collected in pools. Clean Up After a Fire A fire involving askarel will produce a contaminated soot which will cling to all surfaces in the area. All other materials directly exposed to askarel liquid will also be contaminated. These are the steps to follow for clean up and decontamination of the area: 1. Do not begin clean up until the temperature in the area has reduced to normal temperatures. 2. Be safety conscious to avoid personal contamination. Observe the routine safety precautions and handling guide lines prescribed in Booklet 4. 3. Wipe down all impervious surfaces to remove the contaminated soot. Rinse and wipe several times using rags and the solvents listed at the beginning of Section 6.4. 4. Collect all contaminated liquith, materials, soil, clothing etc. and dispose as indicated in Booklet $. HONS 002136 6-12 S. Obtain core samples of concrete sur faces, asphalt surfaces, and soil to determine the extent of contami nation. Follow the same procedures as for Spills on Concrete and Asphalt and Spills on Soil. Excavate the contami nated material. HONS 00213? 6-13 6.5 APPENDIX MONS 002138 I 6-14 ENVIRONMENTAL PROTECTION SERVICE OFFICES Pacific Northwest Ontario Quebec Atlantic Address Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604)866-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 23 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5840 Environmental Protection Service 4th Floor 1SS0 de Maisonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 18th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J 1M5 Emergency (902) 426-6200 Office (902) 426-6141 HONS 002139 MOWS 002140 Booklet 7 BOOKLET 7: TRANSPORTATION PROCEDURES FOR PCB Prepared by: Contract OSB77-08285 for: Stothert Engineering Ltd. Environmental Protection Service Department of Fiaheriee and Environment March lB7t HONS 002141 CROSS - REFERENCE INDEX BOOKLET I; BOOKLET 2: BOOKLET 3i INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1.5 Federal Government Legislation On PCB 1.6 The Future 1.7 Appendix PAGE 1-2 i-3 i-a i-s i-e l-a 1-9 IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix 2-2 2-3 2-6 2-8 2-10 2-IS PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program For Transformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program For Capacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-1* 3-is 3-17 HUNS 002142 BOOKLET 4: BOOKLET 5! BOOKLET 6i PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4_2 4_3 4_6 _7 4_g 4-9 4-9 4-10 4-12 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS S. 1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling In Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 5-4 s-7 s-e 5-9 5-13 5-tr CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-5 6-9 6-13 MOMS 002143 BOOKLET 7; BOOKLET 8: TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix PAGE 7-2 7-3 7-4 7-- 7-7 7-9 8-2 8-3 8-4 8-7 MOMS 002144 7-1 FOREWORD This booklet is number 7 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies nisse Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories - Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002145 7-2 7.1 GENERAL This booklet concerns the transportation of askarel wastes and askarel equipment. The point of origination for these mater ials might be a plant where askarel equip ment is being used, a storage location for askarel or the site of an askarel spill. The transportation of all hazardous products is of such tremendous concern that a bill has been introduced into Parlia ment to legislate an act which will "promote public safety and (result in) the protection of the environment in the transportation of dangerous goods". The act will be termed the Transportation of Dangerous Goods Act and will cover many types of hazardous goods. Once the act is passed, it will be regulat ed by the Transportation of Dangerous Goods Code which is presently in its third draft form. It is intended that both the provinces and the Federal Government will be responsible for administration of the regulations. Information from the code is included in this booklet. It is recommended that the procedures be adopted at this time even though the Act is not yet passed. Under the transportation code, Polychlor inated Biphenyls (PCBs) are listed as United Nations number UN2315. This is a permanently assigned number which will enable containers of PCBs to be recogniz ed internationally. MONS 0021A6 7-3 7.2 NECESSARY ARRANGEMENTS These are the sort of arrangements that should be made before transporting a load of PCB materials inside the province, between provinces or across an inter national border: 1. Receiver Check that the receiver will accept the shipment. The receiver may not accept the shipment due to not having the appropriate facilities for handling or storing askard safely. 2. Transport Company Ensure that the transport company, whether a private trucking or waste handling company, has the knowledge, ability and proper equipment to move the contaminated materials off your premises and to the destination safely. 3. Provincial Government Contact the Provincial Government and obtain the necessary permits, way bills and placard information in obser vance of Provincial transportation regulations. This information is not included here due to the varying trans port regulations for each province. 4. Federal Transportation Dapertmeat For inter-provineial or international shipments, contact the Federal Government and obtain the necessary permits, waybills and placard inform ation in observance of Federal regula tions. Until the Transportation of Dangerous Goods Act is passed, the Canadian Transport Commission regulations must be followed for rail shipments. As a point of interest, the Marine Administration of the Department of Transport presently regulates ship ments of hazardous goods by ship. The Air Adminstratlon of the Department of Transport regulates shipments by air. It is doubtful whether PCB mater ials would require transport by ship or air. 5. Environmental Protection Service For inter-provincial or international shipments, contact the Environmental Protection Service Emergency office in each province along the route (see the back of this booklet for listings). Contact them ten working days before the shipment. Provide the emergency offices with information concerning the date of the shipment, the route, name and quantity of PCBa, name of carrier company, name of driver, vehicle identification and vehicle licence numbers. (1) Any changes in the above inform ation should be brought to the attention of the nearest emer gency office as soon as possible. That office will notify all other emergency offices along the route. (2) The Environmental Protection Service requires that the driver notify the nearest emergency office in the event of a delay en route, an accident or a spillage of PCB contamination. Precise details on the event are required. HONS 002147 7-4 7.3 PACKAGING AND TRANSPORT METHODS Th following guidelines have been select ed from the Transportation of Dangerous Goods Code. Once the Traiwportation of Dangerous Goods Act is legislated, these recommended methods will become regulations under the Act. Packaging 1. Remove any spouts fitted to drums and replace with leak-proof bungs. 2. No drums of askarel liquid or materials should be transported unless they are free from mechanical defects. 3. Drums should be strapped vertically to pallets and horizontally to each other. They should also be braced to prevent movement during transport and to withstand shocks resulting from sudden changes in speed or direction of the vehicle. The end, sides or doors of the truck body should not be relied upon to prevent shifting of the containers. 4. The load on the transport vehicle should be arranged to take account of the floor strength and the centre of grevity. 5. Solid materials which are transported on the same vehicle should be braced to prevent puncturing the containers. 6. Transformers should be wrapped in plastic and secured to pallets before being transported. Transport 1. Containers, equipment, etc., should not be subjected to any unnecessary rough handling such as dragging, drop ping, etc. 2. Ensure there is no tampering with the containers and that there has been no discharge of contents between the point of origin and the point of final destination. 3. Label each container on at least two sides. See Section 7.S for labelling instructions. 4. Place placards on the transport vehicle if the quantity of PCB being transport ed is greater than the minimum acceptable quantity under tha Danger ous Goods Act. See Section 7.3 for placarding instructions. As an exception, a vehicle which is loaded with PCB material but is not placarded can be moved, provided: (1) The driver is accompanied by a Federal, Provincial or Municipal Government representative or (2) The driver has the permission of the Ministry of Transport or (3) Movement of the vehicle is neces sary to protect life or property. 5. Ensure the driver of the vehicle is fully informed of: (1) The nature of the load. (2) The location of emergency equip ment and its use. (3) The reporting procedures to be followed in the event of an accident or incident. (4) The need to replace placards and labels which are damaged or lost in transit. Keep an extra supply in the vehicle. MOMS 002148 7-5 (5) The requirement to notify the receiver of the goods immediately that PCBs are being transported. 6. A qualified person should always be present at on-loading and off-loading. A qualified person is considered to be a person who is familiar with the emergency equipment for askarel and with recommended procedures. He should have the means and ability to move the containers safely. 7. Ensure that askarel containers are not on-loaded or off-loaded unless the handbrake of the vehicle is securely set and that precautions have been taken to prevent motion of the vehicle. 8. Any vehicle which shows signs of leakage from containers should be decontaminated after unloading but before it is returned to service. See Booklet 6 for clean-up instructions. HONS 002149 7-6 7.4 PRECAUTIONARY GUIDELINES These precautionary guidelines are also recommended to prevent contamination of the environment: 1. See Booklet 4 for instructions on how to contain askarel wastes for storage or shipment. 2. Transport clean-up materials in the same vehicle as the containers of askarel. See Booklet 6 for a listing of suitable absorbents and solvents. 3. Also transport empty containers which might be required in the event of a container developing a leak or in case of an accidental spill. Pack appropriate clothing for handling askarel. See Booklet 4. 4. Metal-lined truck boxes are preferable to flat bed trailers or wooden box trucks. It will help to contain any askarel leakage and make decontami nation of the vehicle easier. The bed of the truck should be lined with plastic sheeting for added protection. 5. In case of an askarel leak, stop the vehicle immediately to prevent spreading askarel. Use some other form of transportation to notify the Environmental Protection Service office. Follow the procedures in Booklet S to contain leakage until clean-up can begin. If leakage cannot be contained inside the truck box, spread vinyl sheeting underneath the truck to prevent leak age from soaking into the ground. HONS 002150 7-7 7.5 LABELLING PCS Wastes and Discarded Equipment Drums containing waste PCB liquid or materials contaminated by askarel, and scrapped electrical equipment should each be labelled with the Number 4 - Severe Hazard Label. This label is available from the Environmental Protection Service. It is a non-serialized label which is used for many different types of chemicals. When used with PCBs, it should be filled out as follows: HEALTH -4 FIRE -1 ENVIRONMENT -4 REACTIVITY - 1 CONTENTS - PCBs are contained inside DBPOSAL - (leave blank) HANDLING - Class 9 ORIGINATOR - (your company name) TELEPHONE - (your telephone number) DATE - (the date) The label will then contain the inform ation that is neeeseary for a PCB contain er or discarded equipment being shipped. The code numbers that are written into the four boxes on the top line of the label indieate the severity of PCB In that particular situation. For example: PCB is a high health hazard because of its effect on the food chain, it will not burn easily, it is a high hazard to the environment, and it does not react easily with other chemicals. The handling classification is a coding system pertaining to the handling and transportation of Polychlorinated Biphenyls under the Dangerous Goods Code. An identifying placard is required on each side of the transport vehicle. It can be made of tag board, plastic, metal or some other material and should be at least 250 millimeters (10 inches) by 250 milli meters. Ensure the placards are clearly visible from every direction but mounted in an area that is separate from advertising on the truck. Such advertising might reduce the effectiveness of the placard. The illustration on the next page shows a typical arrangement of placards for a truck transporting PCBs. MQNS 002151 7-e MONS 002152 7-9 7.6 APPENDIX HONS 002133 7-10 ENVIRONMENTAL PROTECTION SERVICE OPPICES Pacific Northwest Ontario Quebec Atlantic Address Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta TSK 2JS Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416) 966-5840 Environmental Protection Service 4th Floor 1550 de Maisonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J 1M5 Emergency (902) 426-6200 Office (902) 426-6141 HONS 0021*54 HONS 002155 BOOKLET 8: SUBSTITUTE CHEMICALS FOR PCB Prepared by: Contract OSB77-08285 for: Stothert Engineering Ltd. Environmental Protection Service Department of FWieriee and Environment Hard) 1979 HONS 002156 CROSS - REFERENCE INDEX BOOKLET 1; BOOKLET 2i BOOKLET 3i INTRODUCTION TO PCBs 1.1 What are PCBs? 1.2 Hazards of PCB 1.3 How Does PCB - Contamination Occur? 1.4 Is PCB Still Available? 1.5 Federal Government Legislation On PCB 1.6 The Future 1.7 Appendix EfifiE. 1-2 1-3 1-* l-S i-e i-e 1-9 IDENTIFYING PCBs 2.1 Brand Names For PCB 2.2 Identifying PCB Transformers 2.3 Identifying PCB Capacitors 2.4 Identifying PCB Liquids 2.5 New Labelling System For PCB 2.6 Appendix 2-2 2-3 2- 2-8 2-10 2-15 PREVENTIVE MAINTENANCE FOR PCB EQUIPMENT 3.1 General 3.2 Anatomy Of A Transformer 3.3 Typical Problems With Transformers 3.4 Preventive Maintenance Program ForTransformers 3.5 Anatomy Of A Capacitor 3.6 Typical Problems With Capacitors 3.7 Preventive Maintenance Program ForCapacitors 3.8 Appendix 3-2 3-3 3-7 3-9 3-13 3-1* 3-is 3-17 HONS 002157 BOOKLET 4: BOOKLET 5: BOOKLET 6! PAGE HANDLING OF PCB LIQUID, EQUIPMENT AND MATERIALS FOR MAINTENANCE AND DISPOSAL 4.1 General 4.2 Safe Handling 4.3 Collection of Askarel 4.4 Containment For Disposal - Capacitors - Transformers - Askarel Liquid - Solid Wastes 4.5 Labelling of PCB Wastes and Discarded Equipment 4.6 Appendix 4.2 4-3 4-6 *-7 4-s *-9 4-9 4-10 4-12 STORAGE OF PCB LIQUID, EQUIPMENT AND MATERIALS 5.1 General 5.2 Selecting A Storage Site 5.3 Ideal Storage Facilities 5.4 Precautionary Guidelines 5.5 Fire Fighting Safety 5.6 Labelling in Storage Area 5.7 Record-Keeping 5.8 Appendix 5-2 5-3 5-4 :-7 s-e 5-9 s-13 5-17 CONTAINMENT SYSTEMS AND CLEAN-UP PROCEDURES FOR PCB 6.1 General 6.2 What Kind Of Askarel Releases Can Occur? 6.3 Containment Systems 6.4 Clean-Up Procedures 6.5 Appendix 6-2 6-3 6-3 6-9 6-13 MONS 002156 BOOKLET 7i BOOKLET 8i TRANSPORTATION PROCEDURES FOR PCB 7.1 General 7.2 Necessary Arrangements 7.3 Packaging and Transport Methods 7.4 Precautionary Guidelines 7.5 Labelling 7.6 Appendix SUBSTITUTE CHEMICALS FOR PCB 8.1 General 8.2 Alternatives Available 8.3 Factors to Consider 8.4 Appendix 7-2 7-3 7-4 7-6 7-7 7-9 a-2 6-3 6-4 6-7 MONS 002159 FOREWORD This booklet is number 8 in a series of 8 that have been written to answer the questions of the public concerning the proper management of PCB chemicals, particularly as they are used in electrical equipment. PCB is also known as "askarel" when used in such equipment. This series will be of special interest to the following companies since they will at some time be working with PCBs. Companies These Booklets Are Written For - Owners of PCB Equipment - Electrical Testing Laboratories Garbage and Waste Collection Companies - Transportation Companies - Scrap Metal Dealers - Salvage Companies Under proper control, the equipment using PCBs can provide an important benefit to man, but without proper control they can also pose a serious threat to human health and the environment. For general enquiries or assistance in emergency situations, contact the nearest Environmental Protection office listed in the back of this booklet. HONS 002160 0-2 8.1 QENBRAL Retrofilling The removal and replacement of askarel fluid In electrical equipment with other types of insulating liquids is termed "retrofilling". As stated in the Guideline for the Management of Waste Materials Contain ing Polychlorinated Biphenyls, retrofilling of askarel-fiUed transformers is not recommended by the Environmental Protection Service. As an exception, if a transformer is already in service and its contents must be drained for some reason, then retrofil ling may be appropriate. A careful study should be made of the effects of the new fluid on the transformer's insulating qualities and heat transfer properties. The manufacturer of the transformer should be consulted for a detailed investi gation. Other important factors to consider are highlighted in this booklet. Topping Up Another term referred to in the servicing of electrical transformers is "topping up". It is an adding of liquid to replenish askarel which is lost due to leakage or sample testing. Under the regulations of the Environ mental Contaminants Act, topping up with askarel is prohibited. Tri/tetrachlorobensene (TTCB) or some other suitable make-up fluid such as refined paraffinic oil may be used to replenish the volume of the coolant. Check with the transformer manufacturer for the maximum allowable make-up fluid that can be added (likely 25-40% of the tank size). Excessive quantities of make up fluid may alter the performance of the transformer or soften the insulation on the transformer windings. Large quantities of make-up fluid should not be added quickly. Add it slowly to allow for proper mixing with the askarel. Capacitors Capacitor casings are not designed for retrofilling or topping up so the question of substitute chemicals for installed capa citors is not a consideration. Under the regulations of the Environ mental Contaminants Act, PCB-fiUed capacitors may no longer be manufactured in Canada or imported into the country. As a result, once suppliers' inventories of PCB capacitors deplete, PCB capacitors will no longer be available in Canada. Substitute chemicals will then be needed for the many applications requiring capacitors. In recent years, many of the manufactur ers of PCB capacitors have developed capacitors which contain alternative fluids. The merit of each manufacturers' capacitors should be investigated when new capacitors are required. Such an analysis is beyond the scope of this book let. HONS 002161 8-3 .2 ALTERNATIVES AVAILABLE Material suppliers are frequently asked, "Do you have a liquid that can be used to replace askarel in transformers?" Unfor tunately, there is no simple answer to this question. There are several liquids which could be considered for use in an askarel trans former. These include: - Transformer oil - Silicone fluid - Refined paraffinic oil - TTCB fluid The problem is that none of these liquids are totally acceptable from an environ mental, technical, cost and safety point of view. For that matter though, neither is PCB liquid because of its environmental hazard. The next section of this booklet includes a comparison of some of the characteristics of these fluids. HONS 002162 8-4 8.3 FACTORS TO CONSIDER Environmental Hazard The removal of PCB from an askarel transformer and several flushings with a solvent will not be sufficient to declare the transformer free of PCB contami nation. There will still be enough askarel retained in the windings of the transform er to contaminate the new fluid. A retrofitted transformer is still considered to be fitted with PCB. If PCB levels in the insulating fluid exceed 100 ppm, the transformer will still require labelling and consideration as a PCB transformer. There is also the problem of storing the large quantity of drained askarel and flushings safely. Technical and Economic Factors This is a summary of some of the technical and economic factors for alter native transformer liquids. Additional details are provided after the table: Factor Flammability Transformer Oil Very flammable Silicone Fluid Maybe affected Loadability Okay Reduced Insulation reliability Action of tap changers Sc pumps Approximate cost per gallon Okay Okay $1 May be reduced May be affected $24 Refined Paraffinic Oil Maybe affected May be reduced Okay Okay TTCB Fluid Okay Okay May be reduced Okay *10 $11 1 V i `l NGNS 002103 I 8-5 1. Flaminability Taits have demonstrated that in the event of a high power are inside a transformer filled with oil, hydrogen gas will be produced in large quanti ties. If ignited by the arc, the gas will explode, causing the oil to burn con tinuously. With silicone fluid, large quantities of hydrogen gas will also be produced, but the liquid will not continue to burn. Silicone fluid apparently has the tendency to prevent the ignition from spreading. The flammability index for several fluids are as follows. The index for water is included for comparison: Water 0 Askarel 2-3 Silicons 4-5 Transformer Oil 10-20 Ether 100 The flash points for some transformer fluids are: Transformer Oil Approx. 160C Silicone Approx. 285C Refined paraffinic Oil Approx. 285C From a safety point of view, fireproof vaults may have to be constructed around an indoor transformer instal lation in order to gain compliance with electrical codes. From an insurability point of view, insurance companies are tending to evaluate retrofilled transformers on an Individual basis. 2. Loadability Loadability represents the ability of an askarel transformer to maintain its nameplate rating with an alternative fluid inside. Since silicone fluid is a highly viscous fluid, it does not have the same cool ing efficiency as transformer oil or askarel. For this reason, the power handling capability of the transformer may have to be reduced by up to 10% after retrofilling. 3. Insulation Reliability Both silicone fluid and TTCB have a higher coefficient of thermal expan sion than askarel (silicons is 1-1/2 times that of askarel). This means that at low temperatures the volume of the level in the trans former will drop significantly. It may drop so much that internal parts of the transformer are exposed and electric arcs can occur. A transformer filled with TTCB should not be energized when the temper ature of the liquid is below 0C, for this reason. 4. Action of Tap Changers A Puaapa Silicone exhibits poor lubrication qualities. This may cause tap changes and pumps of askarel transformers to seize or fail. Maintenance would be required. Furthermore, some askarel transform ers use silicone rubber gaskets. This material win swell and weaken when exposed to silicone liquid. Leaks wUl develop. MOMS 002164 8-6 5. Approximate Coat Par Gallon Sevoral flushings with a solvent will be required to cleanse the transformer of most of its askarel. Added to this the cost of labour for Gaining, flushing and filling, plus the cost of insuring and transporting the solvents and askarel, retroflU becomes a very expensive proposition to implement. 6. Othar Factors Silicone vapours released from a pres sure relief valve on a transformer will cling to surfaces and inhibit such activities as maintenance painting of transformer cooling fins. In order to obtain good adhesion of the paint, special additives will have to be added. The vapours released from a silicone filled transformer located in a mine may activate methane detectors. 7. Conclusions As mentioned earlier in this booklet, retrofitting of askarel filled transform ers is not recommended as a viable alternative. . It should be emphasised, however, that in the ease of new transformers, the unit will be designed to minimize the shortcomings of the selected transformer fluid. Transformer manufac turers are very willing to discuss how their product compares against the performance of askarel fluid. . J i MONS 002165 8-7 8.4 APPENDIX HONS 002166 8-8 ENVIRONMENTAL PROTECTION SERVICE OFFICES Pacific Northwest Ontario Quebec Atlantic ' AddrM Telephone Environmental Protection Service Kapilano 100 Park Royal West Vancouver, B.C. V7T 1A2 Emergency (604) 666-6100 Office (604) 666-6711 Environmental Protection Service Room 804 9942 - 108th Street Edmonton, Alberta T5K 2J5 Emergency (403) 425-5128 Office (403) 425-5128 Environmental Protection Service 7th Floor 25 St. Clair Avenue East Toronto, Ontario M4T 1M2 Emergency (416) 966-5840 Office (416)966-5840 Environmental Protection Service 4th Floor 1550 de Malsonneuve Blvd. West Montreal, Quebec H3G 1N2 Emergency (514) 283-2333 Office (514) 283-2345 Environmental Protection Service 16th Floor, Bank of Montreal Tower 5151 George Street Halifax, N.S. B3J IMS Emergency (902) 426-6200 Office (902) 426-6141 HONS 002167