Document gaRV4Yj5ERzpKdrJ9XnZ6eKQL
!
\
# M
SPIRAL WOUND
World's Most Popular Type Metal-Asbestos Gasket
Spirally wound Type Gaskets deserve their popularity because they offer a built-in resiliency, for safe seals with lighter bolt loads, that no other gasket type offers. Ajax Spiralwound Gaskets are made for all standard pipe flanges and for manholes, handholes and tube caps of all makes of stationary and marine boilers, waterwalls, economizers, and other boiler accessories. They are available in plated low-carbon steel or stainless with fillers of Canadian or blue African Asbestos or chemically inert duPont Teflon. Ask your Industrial Distributor or write--
BOILER SCALE
Continued from page ;$
result of too wet a steam leaving th,
boiler drum. An overburdened boiler! inadequate mechanical facilities, ab^
normally high water concentrations c__ all bring on spasmodic priming or a
continous carryover of water into steam areas. Often a boiler lacks adequate' purifying equipment for these condi-'
tions. Boiler-water droplets carried over evaporate along the steam passages and leave their scale-forming deposits b hind. Superheater or equalizing tub fail for this reason.
A little soluble sodium silicate in the
boiler water tends to hydrolize into'
sodium hydroxide and silicic acid, Fi,,
4. The latter is an insoluble, colloidal
product. At fairly high temperatures^^
this colloidal acid volatilizes with
steam and its carryover increases with
rising temperatures and soluble silica;
concentrations in the boiler water. Si-^
licic acid becomes more noticeable at
operating pressures above 600 psi. But
with excessive silica concentrations thejgj&S
acid occasionally carries over as lowSI*;
as 400 psi.
jfis
In a well superheated steam this acidjKg is harmless. But as the steam expands gw . in the late stages'of a turbine, the acidjgj5|
condenses out on the blades to leave e water-repellent, glossy and extremely sticky mass that greatly decreases tur-gfc bine efficiency. You have to resort to a^"
caustic soda bath to remove it.
AIR POLLUTION
Continued from page 76
with pulsating rather than with direct sg,
voltages. Further, the highest possible'^
peak voltages on discharging electrodes u*-.
produce the best results, Fig. 3. But.lpr
backing up these peak power surges
must be an adequate transformer and.^
rectifier capacity. What's more, the^.
higher the applied voltages, the more^-
bus sectionalization becomes attractive.
With greater sectionalization two major
advantages develop: (I) Whatever^
troubles appear are isolated. (2) Fields g?-
of electric energy through `"which the Af..'
gas passes are more uniform. "
#''
Contrary to earlier ideas, peak col*
lection efficiency comes from setting the &}:
precipitator voltages high enough to Pr0'^.
duce sparking, about 100 sparks per
minute per precipitator section.
New designs meet this requirement as^
fully as possible. Current and voltage
ratings of rectifier sets, commonly used
for flyash applications, are 150 to 300
mva, and 70 to 100 kv. Power inputs
may run up to 9 kw for 100.000-cfm Jj
gas flows to achieve a 97% collecting
efficiency. Exact peak-voltage values w
POWER APRIL 1953 .A