VENTILATION MEASUREMENT OF WELDING EXHAUST
The elephant trunk exhaust ventilation in the welding booth in the Carpenter Shop was measured on January 11 using an Alnor Thermo Anemometer, Type 8500. The average face velocity of the trunk was between 1500 and 2000 ft/min. Since?the surface area of the trunk opening is approximately 0.0985 -ft , the total exhaust' is 147.75 cfm. According to Du Pont Standard H1U and 0SHA, given this exhaust rate, the point of weld.ing can be no further than 4.45 inches from the end of the trunk.
Mechanical local exh-aust ventilation is required when welding on galvanized. However, the welding room may be defined as a confined space (less than 10,000 ftJ of space per welder and ceiling less than 16 feet high), which requires mechanical venti lation even when welding on non-toxic metals. Some improvement in exhaust rate may be had by plugging the hole in the ceiling-at the base of the trunk. Also, a conical or flanged piece on the end of the'trunk should increase exhaust removal from the area of welding.