Document gZdNwGwxJN1y0obEa3mJ4bYa
Monsanto
DIVISION
`'rganic
INSTRUMENT FUNCTION OUTLINE
plant w* G- Krummrich
BLOG/DEPT
811.00
AUTH NO. .
2417
CEO LOOP NO.
FIC-406-1 & Existing FICA-7
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/23/71
REV. BY
DATE
REV
1 SHEET OF
#6 CHLORINATOR BIPHENYL FEED CONTROLLER
1.0 NEED FOR LOOP
This loop is needed to assure that the proper amount of Biphenyl is added to the_ chlorinator. The parallel feed controller is needed to maximize the production of "mono" in the column system. The flow through-put of the existing FT-7 was too small to perform this function.
1.1 FUNCTION
j
1.1.1 Function
. .
j
i i
The function of.this loop is to control the rate of flow of Biphenyl
j
into the chlorinator and sound an alarm on low flow.
j
i
1.1.2 System Performance Required
|
'
j
The flow rate should be maintained + 1/8 GPM of set point.
\
1.1.3 Accomplishment of Function
f
The Biphenyl flow rate is controlled by measuring the rate of flow
in the line and transmitting an air signal proportional to this rate
!
to an indicating controller; the measuring and transmitting is done
i
by one of two differential pressure transmitters. One measures the
[
flow across an orifice plate in the line for the "mono" operation
!
and the other has an integral orifice for measuring the smaller flow I
in the 1016 operation. The indicating controller compares the air
i
signal with a set point flow rate and sends a varying 3-15 psigsignal
to the Biphenyl control valve to compensate for variations from the
:
set point. The transmitter also needs an air signal to a pressure
:
switch which activates an alarm on low flow. The flow is also field
i
indicated at #6 chlorimator and at the Biphenyl feed pump pushbutton. i
(
I
f,
II;:
rts
r
i
r?
rii
F t
PCB-ARCH-EXT0372697
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w- G- Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO. .
FIC-406-1 & Existing FICA-7
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/23/71
REV. BY
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
a. 1016 Operation
1. Set selector switch in field to " 1016' 1 portion 2. Close valve to FT-406-1 3. Open valve to FT-7 4. Set controller set point to flow rate desired and place
controller in "auto"position. 5. Open block valves in feed line
b. "Mono" Operation
'
.
1. Set selector switch in field to "Mono" position
fvy % ~
2. Close valve to FT-7
3. Open valve to FT-406-1
.
4. Set controller set- point to desired flow rate and place
controller in "auto" position.
5. Open block valves in feed line.
3.1.1 Start-up
-
.
Same as above plus alarms should be checked. '
.
3.1.2 Shutdown
a. Set FIC-7 set point to 0.
b. Close block valves in Biphenyl feed line
3.1.3 Manual Operating Instructions
a. Set FIC-7 on manual and control flow through FV-7 to #6 chlorinator by adjusting air output to valve.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS'
3.3.1 Air Failure
Air failure to the loop will cause control valve FV-7 to close.
3.3.2 Power
.
Power failure will cause the annunciator to be inoperative. The control valve will continue to operate.
PCB-ARCH-EXT0372698