Monsanto DIVISION `'rganic INSTRUMENT FUNCTION OUTLINE plant w* G- Krummrich BLOG/DEPT 811.00 AUTH NO. . 2417 CEO LOOP NO. FIC-406-1 & Existing FICA-7 ISSUED BY C. J. Hans DATE PLANT LOOP NO. 7/23/71 REV. BY DATE REV 1 SHEET OF #6 CHLORINATOR BIPHENYL FEED CONTROLLER 1.0 NEED FOR LOOP This loop is needed to assure that the proper amount of Biphenyl is added to the_ chlorinator. The parallel feed controller is needed to maximize the production of "mono" in the column system. The flow through-put of the existing FT-7 was too small to perform this function. 1.1 FUNCTION j 1.1.1 Function . . j i i The function of.this loop is to control the rate of flow of Biphenyl j into the chlorinator and sound an alarm on low flow. j i 1.1.2 System Performance Required | ' j The flow rate should be maintained + 1/8 GPM of set point. \ 1.1.3 Accomplishment of Function f The Biphenyl flow rate is controlled by measuring the rate of flow in the line and transmitting an air signal proportional to this rate ! to an indicating controller; the measuring and transmitting is done i by one of two differential pressure transmitters. One measures the [ flow across an orifice plate in the line for the "mono" operation ! and the other has an integral orifice for measuring the smaller flow I in the 1016 operation. The indicating controller compares the air i signal with a set point flow rate and sends a varying 3-15 psigsignal to the Biphenyl control valve to compensate for variations from the : set point. The transmitter also needs an air signal to a pressure : switch which activates an alarm on low flow. The flow is also field i indicated at #6 chlorimator and at the Biphenyl feed pump pushbutton. i ( I f, II;: rts r i r? rii F t PCB-ARCH-EXT0372697 Monsanto DIVISION Organic INSTRUMENT FUNCTION OUTLINE plant w- G- Krummrich BLDG/DEPT AUTH NO. 811.00 2417 CED LOOP NO. . FIC-406-1 & Existing FICA-7 ISSUED BY C. J. Hans DATE PLANT LOOP NO. 7/23/71 REV. BY DATE REV SHEET OF 3.0 OPERATION 3.1 NORMAL OPERATION a. 1016 Operation 1. Set selector switch in field to " 1016' 1 portion 2. Close valve to FT-406-1 3. Open valve to FT-7 4. Set controller set point to flow rate desired and place controller in "auto"position. 5. Open block valves in feed line b. "Mono" Operation ' . 1. Set selector switch in field to "Mono" position fvy % ~ 2. Close valve to FT-7 3. Open valve to FT-406-1 . 4. Set controller set- point to desired flow rate and place controller in "auto" position. 5. Open block valves in feed line. 3.1.1 Start-up - . Same as above plus alarms should be checked. ' . 3.1.2 Shutdown a. Set FIC-7 set point to 0. b. Close block valves in Biphenyl feed line 3.1.3 Manual Operating Instructions a. Set FIC-7 on manual and control flow through FV-7 to #6 chlorinator by adjusting air output to valve. 3.2 INTERLOCKS None. 3.3 ABNORMAL OPERATIONS' 3.3.1 Air Failure Air failure to the loop will cause control valve FV-7 to close. 3.3.2 Power . Power failure will cause the annunciator to be inoperative. The control valve will continue to operate. PCB-ARCH-EXT0372698