638 CHAPTER 32 1949 Guides angularity and in the shape of the blades. Characteristic, curves of these') types showvarying degrees of similarity to the curves in Figs. 2 and-3. SYSTEM CHARACTERISTICS Any ventilating system consisting of duct work, heaters, air washers, filters, etc., has a system characteristic which is individual to that system and is independent of any fan which may be applied to the system. This characteristic may be expressed in curve form in exactly the same manner that fan characteristics may be shown. Typical system characteristic curves are shown as A, B and C in Fig. 4. These curves are drawn to follow the simple parabolic law in which th& static pressure or resistance Fig. 4. Parabolic System Characteristic Curves to flow of air varies as the square of the volume flowing through the sys-; tern'. Heating and ventilating systems follow this law very closely and . no serious error is introduced by its use. When a-constant speed fan curve for a given size fan is super-imposed upon a .system characteristic curve, the relation between the two is at once apparent- The only point common to the two curves is the point at the intersection of the system characteristic curve and the fan character- istic curve, and it is at this point that the combination will operate. In Fig. 4, system characteristic curves A, B and C cross the fan character istic curve at points X, Y and Z. The fan whose curve is shown, when' applied to systems having characteristic curves A, B and C, will deliver1 10,000, 13,000 or 16,400 cfm respectively. > ! ' The curves in Fig. 4 also illustrate the effect of errors which.may be' made, in calculating the resistance of a ventilating system. For instance,' if a given- system requires 13,000 cfm and the resistance to flow of the system has been computed as 1.25 in. static pressure, such a system would' , bO represented by system characteristic curve B in Fig. 4. If a 100 per Fans 639 cent error had been-made and the resistance were:2.5 in. instead of 1.25 in., then the system characteristic would be as shown in curve A and would cross the fan curve at 10,000 cfm. Such an error would cause the flow of air to be decreased from a design volume of 13,000 cfm to 10,000 cfm. If the resistance to flow had been over estimated and the resistance actually were 0.625 in., the system characteristic curve would be as shown in curve C and the fan would deliver 16,400 cfm to the system instead of the design volume of 13,000 cfm. In this example extreme errors have been selected to emphasize the effect the square function of the system characteristic has in maintaining the fan performance within comparatively narrow limits. In the first example a system estimated at half what it should have been, resulted in ' a drop of 23 per cent in volume; and in the second example, a system es-; timated at twice what it should have been resulted in an increase of 26 per cent in volume. In some instances fans may be applied to variable flow systems. Insuch cases the limiting systems may be plotted and the effect on fan per formance examined. For instance, a system might have a characteristic curve between A, shown in Fig. 4, as one limit, and B as the other limit. The fan performance will then fall between points X and Y on the fan curve at a point determined by the system characteristics at that particular time. If A and B are the limiting characteristic'curves of the systems, the fan performance will never be outside the points X or Y. SELECTION OF FANS The following information is required to select the proper type of fan: 1. Cubic feet of air per minute to be moved. 2. Static pressure required to move the air through the system. 3. Density of air to be moved. 4. Type of motive power available. - 5. Whether fans are to operate singly or in parallel on any one duct. 6. What degree of noise is permissible. 7. Nature of the load, such as variable air quantities or pressures. In order to facilitate the choice of apparatus, the various fan manu facturers'supply fan tables or curves which usually show the following factors for each size of fan operating against a wide range of static pres sures : (1) volume of air in cubic feet per minute (68 F, 50 per cent rela tive humidity, 0.075.1b per cubic foot), (2) outlet velocity, (3) revolutions per minute, (4) brake horsepower, (5) tip or peripheral speed, and (6) static pressure. The most efficient operating point is usually shown by either bold-face or italicized figures in the capacity tables. Other important factors to be considered in selecting fans are: (I) efficiency, (2) space ocupied, (3) sound emission, (4) first cost, and (5) speed (both peripheral and revolutions per minute). These factors are not necessarily shown in the order of importance. In some installa tions, space, occupied may be of first importance; in others lowest power consumption is desirable. In many cases quietness of operation of the entire system is essential. Practically all fans operate at their, lowest sound level when selected at or near the peak of the static efficiency so that in selecting a fan for highest static efficiency the quietest operating