HEATING VENTILATING AIR CONDITIONING GUIDE 1940
load a starting resistor NBMA classification No. 15 may be used. For speed regulation resistor, classification No. 93 should be selected. On a compressor drive using an unloader, a constant torque resistor classi fication No. 15 should be used. If the compressor is started under load, NBMA classification No. 56 or 76 are used. For constant torque speed regulation, resistor No. 95 is used.
SINGLE PHASE MOTOR CONTROL Where three phase current is not available or where single phase opera tion is preferred, then single phase repulsion induction, capacitor type or multispeed single phase motors may be used. Since the starting currents of all single phase motors are required to be within the starting-current limits established by the local power-supply company, a suitable type of starter may be chosen from the following selection: 1. Enclosed two pole manually operated motor starters with thermal overload protection. 2. Enclosed two pole automatic motor starter operated by a push button, thermostat or similar device, with thermal overload relay and low voltage protection. 3. A manual or magnetic resistance type starter with low voltage protection. 4. A manual or magnetic control for pole changing motors and for adjustable varying speed motors using an auto-transformer or resistance in the primary circuit to obtain line (or terminal) voltage drop. In selecting across-the-line control for single phase capacitor type motors it is usually very desirable to use three pole across-the-line starters. Control for multispeed, single phase capacitor motors may be selected from tables on three phase rating when consideration is given to the increased current and the necessary switching of connections.
682
Chapter 40
PIPE AND DUCT INSULATION
Heat Transmission by Radiation and Convection, Heat Losses from Bare and Insulated Pipes, Heat Losses from Ducts, Lou> Temperature Insulation, Insulation of Pipes to Prevent Freezing, Economical Thickness of Pipe Insulation, Under
ground Pipe Insulation
HEAT is transmitted to or from pipes and ducts by radiation and convection. The radiant heat transfer per unit area is independent of the geometrical shape, whereas the convected heat depends to a considerable extent on the shape factor. In many cases, it is desirable to calculate the rate of heat transmission from a surface by radiation and convection, as the total rate of transfer is different, for instance, from a heating installation than from a cooling installation with an equal difference in temperature between the surface and the surrounding atmosphere.
HEAT TRANSMISSION BY RADIATION AND CONVECTION
The heat transmission by radiation from a surface to the surrounding surfaces can be calculated from the well-known Stefan-Boltzman formula:
where
Sr = 17.4 X 10-" X P (TV - TV)
(1)
Sr = heat transmission by radiation, Btu per square foot per hour. p -- effective emissivity of surface and surroundings. Ti = temperature of hotter surface, degrees Fahrenheit absolute. T, -- temperature of cooler surface, degrees Fahrenheit absolute.
The heat transmission by free or natural convection can be determined from the formula:
9' = cu/ 1 )\o. (/rT1v.\)0.131
where
qc heat transmission by convection, Btu per square foot per hour. C * a constant depending upon the surface shape. D = diameter of pipe or circular duct or height of vertical wall, inches.
(effect of diameter or height becomes constant at 24 in.) T av. = average wall surface and surrounding air temperature, degrees Fahrenheit
absolute. dt = temperature excess, between wall surface and surrounding air, degrees
Fahrenheit.
683