SYSTEM
HEATING LOW-PRESSURE STEAM OR HOT WATER
CONCRETE ROOF,
APPROVED VENTILATION
VENT- __ (URDCRQ ROUND
METAL PLATE
(ORAIN TO UFt LOCATION)
tV;
, FROM (V,___ UNDERGROUND vi------STORAGE TANK
TYPICAL INSIDE FLAMMABLE LIQUID STORAGE ROOM
Fic 42-12 --A flammable liquids storage and mixing room, Type A, following NFPA design
sack or blanket The file should be attacked with carbon
dioxide, foam, or dry chemical extinguishers, or water Burning liquid may be flushed away to a safe place, if a supply of water is available, but not into a public sewer, dram, or public wateiway
Where burning vapors are escaping from leaks or vents, it may be better to let them bum until the source of escaping liquid or vapor can be controlled
In all cases of fire, the fire conti ol squad or the local fire department should be informed quickly Procedures on what to do m case of fires should be prepared and, m the actual emergency, followed
Storage
Class I and Class II liquids should not be kept or stored in a building used for public
assembly, such as a school, church, or theater, except in approved containers (Fig 42-11) within either a storage cabinet or a storage room that does not have an opening which communicates with the public portion of the building They should not be stored so as to limit use of exits, stairways, or areas normally used for the safe egress of people Neither should they be stored close to stoves or heated pipes, nor exposed to the rays of the sun or other souices of heat
Storage of flammable liquids m open con tainers should not be permitted Approved containers for flammable liquids should be closed after each use and when empty Warn ing labels should be removed from flammable hquid containers when empty (vapor free)
Bulk Class I liquids should be stoied in an underground (buned) tank or outside a build ing No outlet fiom the tank should be inside a building unless it terminates in a special
1303