424 CHAPTER 17 1954 Guide'Ss' ..Vafi- Example 3: Determine.if a 13-ft, 8 x 8-in. nominal-size flue is sufficient for a coalA heating unit rated at 0.03 in. of water draft at 400 F inlet temperature, fuel rate being '; 10 lb per hr of bituminous coal, with 10 percent CO,. . ' Solution: From Fig. 9, a flue-gas rate of approximately 180 lb per hr is obtained. The available draft for a 180 lb per hr-fuel-rate, ana an.inlet temperature of 400 F, obtained from Fig. 6, is 0.056 in. of water. This indicates that the chimney is ade-' quate. The selection of chimney areas for liquid- and solid-fuel-burning devices is difficult because of the variability in efficiency of different models, the possibility that soot on the lining will restrict the chimney area, and the variation in combustion air requirements of different solid fuels. Figs. 6 and 7 show that a given chimney produces a maximum available draft and a maximum efficiency for some intermediate mass flow rate for any selected inlet flue-gas temperature. For mass flow rates lower than the optimum the greater cooling of the gases in the chimney causes lower available draft, whereas for mass flow rates above the optimum the greater friction losses reduce the available draft. A chimney for a given heating system should probably be designed to'operate at its point of maximum efficiency and maximum available draft for its full rated output. A chimney would have an accelerating effect10 on the combustion rate of a solid-fuel burning device if it were operating to the left of the optimum point in Fig. 6 because an additional increment in mass flow rate would increase the available draft a small amount and tend to increase the mass flow still more. On the other hand, a chimney operating to the right of the optimum point in Fig. 6 would tend to decelerate the combustion rate for any small increase in mass flow rate. Data are not complete for the selection of proper chimney areas for heating plants of different capacities, but some information on the effect of cross-section area on the capacity of masonry chimneys is provided by recent tests8,11 on several chimneys with liners having nominal outside dimensions: 9 in. diameter, 12 in. diameter, 9X9 in-, and 9 X 13 inThese tests showed that for flue gas rates up to 200 lb per hr, and entering flue gas temperatures from 200 to 1000 F, the 9-in. round liner provided an available draft equal to, or greater than, that produced by the other three larger liners. When the flue gas rate was increased to 320 lb per hr, the three larger liners produced a little more'draft than the smallest one for entering flue gas temperatures above 600 F. Other data9 show that metal chimneys with an internal diameter of 6 in. should not be used for mass flow rates greater than 130 lb per hr. Table 2 shows approximate values of the mass flow rates and flue-gas velocities at the chimney inlet that produce the maximum available draft for masonry chimneys8 of several conventional sizes and with'-an effective height of 15. ft. This table shows that a 9-in. round chimney15 best suited to mass flow rates from 130 to 170 lb per hr, a 9 X 9-in, chimney performs best for flow rates from about 200 to 300 lb per hr, and a 9 XT" in. and 12 in. round chimneys are best suited to flow rates above 300 lb per hr. These results were obtained with clean chimneys, so that conclusions about chimney areas require some modification if soot deposits are taken into consideration. Soot deposits in chimneys reduce the effective area of the liner an<J may in some cases entirely close the passage. Soot deposits are likely to be greater in the horizontal passages in the heating plant, the breeching,.a? the smokepipe, than in the vertical chimney liner. An increase in tn liner diameter of one inch above that required for a clean chimney ^ probably make adequate allowance for soot deposits in all but the wo/?1, Chimneys and Draft Calculations 425 cases. Where smoky combustion is likely to occur and the mass flow rates on a .clean chimney basis approach those listed in Table 2, the next larger commercial size liner should be used. Smoky combustion with oil-burning devices, particularly with vaporizing oil burners, is likely to be caused , by inadequate draft which is often due to. insufficient chimney height. For coal, inadequate chimney height or. chimney area may be a- contributing cause, but smoky combustion with coal is related to fuel -characteristics and firing methods. Therefore, an increase in chimney area will usually not cure smoky combustion of a coal-burning device, but can be expected to lengthen the interval between cleanings. ; New standard sizes of clay flue linings were recently developed by . the industry and approved by tha American Standards Association, in order to effect economies, that can be derived from coordination of the dimensions of building materials. These linings are known as modular clay flue Table 2. Approximate Flue-Gas Flow Rates fob Maximum Available Draft in Masonry Chimneys Nominal External Liner Dimensions 9 in. Dia. 9 in. x 9 in. 12 in. Dia. 9 in. x 13 in. Floe Gas Temperature at Chimney Inlet, Fahb. 200 GOO 1000 200 600 1000 Maas Flow Rate, LB/HR 170 150 130 215 306 334 290 Above Above 320 320 295 Above Above 320. 320 Flue Gas Velocity at Chimney Inlet, FPM linings, and the dimensions and tolerances are summarized in ASA Stand ard A62.4-47. As the effective areas of these liners are somewhat smaller than those of the corresponding linings used previously, they cannot be used in certain municipalities where building codes specify minimum areas based on the older dimensions.- DRAFT REQUIREMENTS OF APPLIANCES Typical flue-gas temperatures and drafts required at. rated output for several kinds of domestic heating appliances12 are contained in Table 3. Chimney height and chimney area for cast iron boilers are specified in the J = B = R Testing and Rating Code of the Institute of. Boiler and Radiator Manufacturers. Mechanically-fired devices such as oil bumers and stokers are equipped with blowers, and therefore, the chimney is not required to overcome the resistance of the fuel bed or burner. Nevertheless, a draft in the firebox, f about 0.03 in. of water is desirable so that leakage, if any, will be into fue firebox rather than outward from it. Insufficient draft for natural-draft-appliances is likely with installations ln attics or-in one-story basementless houses. Automatic oil-burning space heaters, floor furnaces, and warm air furnaces employing naturaldraft vaporizing burners require a draft of 0.06 to 0.08 in. water for outdoor temperatures of 60 F. Coal-burning heaters and furnaces which attain design rating of 0 F would require about the same draft. For such require- roents, data from Figure 8 and Table 1 show that an effective chimney "eight, above chimney inlet, should be a minimum of 8 to 12 ft. Because