Document gE5ZO7XVMdBznYeMpppR52mjV
464
CHAPTER 25
1965 Guide And DataBook
Table 4 .... Average Air Changes per 24 hr for Storage Rooms due to Door Openings and Infiltration*-* (Room Temp above 32 F)
Vo/tOB# <V ft
Air Change* per 24 Hr
Volume cu ft
Air Change* per 24 hr
200 44.0 300 34.5 400 29.5 500 26.0
6,000 8,000 10,000 15,000
6.5 5.5 4.9 3.9
600 800 1,000 1,500
23.0 20.0 17.5 14.0
20,000 25,000 30,000 40,000
3.5 3.0 2.7 2.3
2,000 3,000 4,000 5,000
12.0 9.5 8.2 7.2
50,000 75,000 100,000
per barj gwga, multiply the *bo*e nhM by X. Far tasg ttermta, multiply tbs above value* by 0.6.
2.0 1.6 1.4
practical and effective. From Fig. 7D and 7E, it was indicated
that the infiltration through a revolving door (except a small
portion past the door seals)] is almost"unaffected by the
height of the building, the difference in pressure between the
indoors and outdoors, and fan operation.'
From the typical examples for swinging door and revolving
door, aforementioned, it may be of interest to note that the
infiltration rate through a swinging door is about 900 cu ft per
person for a single-bank entrance, and 550 cu ft per person for
a vestibule-type entrance.
Under the same conditions, the infiltration is about 60 cu ft
per person for a manually revolving door and 32 cu.ft. per
person for a motor-driven type. In other words, the revolving
door is essentially a good air lock. The infiltration rate is pri
marily the amount of the displacement of air produced by the
revolving of the doors.-
However, it has been observed during field tests of some
23 tall commercial buildings in Cleveland and .Pittsburgh,
and a few other buildingB in New York and Chicago, that the
revolving door has many drawbacks which offset the service
of handling the large volume of entrance traffic provided by
the swinging doora..
'
Cold Storage Rooms
Each time the door of a storage room is opened some air
from the outside enters. This warm outside air must be're
duced to the. temperature of the refrigerated space thus add
ing to the refrigeration load. It is difficult to determine the
load accurately. .The traffic in a refrigerator usually varies
with its sise-or volume and the number of door-openings is
dependent upon the volume rather than the number of doors.
The air changes listed in Table 4 are based on experience and
have proven practical.
--
- -!
Table 4 does not apply, if additional ventilation is required. When fresh air is provided, it causes the refrigerated space
to be under an air pressure slightly above atmospheric. Under
these conditions, cold air-will leave the'refrigerated space
whenever the door, is opened. The ventilating load under these
conditions will replace the door opening load, if greater.
Effect of Supply and Exhaust Systems ..
Buildings are sometimes pressurized to redue* or eliminate infiltration by providing a substantial excess of outside supply
air over exhaust. The variation in pressure difference due to ' wind greatly complicates the application of such a system. Unless the excess air supply is automatically adjustefi, the inside pressure will often be either greater or sniallej than -required. When the pressures on the windward ride are bal anced the supply air required will be about equal to the infil tration that would otherwise occur due to exfiltration on the `leeward rides unless the building spaces are tightly sealed -from one another. This is further complicated in tall buildings by the variations in pressure difference across the walls with height due to temperature forces. If the normal pressure dif ferences at levels furthest from the neutral zone are to'be Overcome a total outride air supply much in excess of the in
filtration that would otherwise occur must be provided unless -the various floors are isolated from one another. In tall build.ings at least, pressurizing to the extent required to overcome .infiltration will result in a substantial increase in heating or cooling loads except for those buildings with very tight en closures. ' Where mechanical ventilating systems are designed to pro duce positive or negative pressures in an enclosure, if the specified rate at which air is to be supplied or removed exceeds 'the calculated infiltration rate, it is common practice to use :the greater value in calculating heating or cooling require-
; Infiltration and Air for Combustion
Infiltration in buildings normally supplies the air required for combustion by fuel-burning appliances, but in some eases weatberstripping, filling, and calking may reduce infiltraj tion to the point that special openings must be provided to supply adequate air to the heating appliances..This need for combustion air is recognized in various building codes. - For instance, the State Building Construction Code of New York State for One- and Two-Family Dwellings" requires that an air inlet area not less than the area of the smoke ' pipe connection be provided if adequate air supply at all : timaft is not assured. Similarly, the same code for multiple ` dwellings requires a permanent opening to the outdoor air for rooms containing fuel-burning appliances having a gross capacity in excess of 250,000 Btuh.
NATURAL VENTILATION
Ventilation by natural forces finds application in indus. trial plants, public buildings, schools, dwellings, garages,
and io farm buildings. . The natural forces available for moving air into, through, i and out of buildings are: (a) wind forces, and (5) the
difference in temperature between the air inside and out ride a building. The air movement may be caused by either of these forces acting alone, or by a combination of the -two, depending upon atmospheric conditions, building de sign, and location. The ventilating results obtained will vary, from time to time, due to variation in the velocity and direction of the wind, and the temperature difference. The . arrangement, location, and control of the ventilating open ings should be such that the two forces act cooperatively ~ rather than in opposition.
In problems of heat removal, knowing the amount of heat to be removed and having selected a desirable tempera ture difference, the amount of air to be passed through the building per minute, to maintain this temperature difference, nan be determined by means of Equation 4.
c, X p X 60(4 - O 1.08(1; - 4)
.Infiltration and Ventilation
465
toilers
Q m air removed, cubic feet per minute. ff beat removed,3tu per hour. tf specific heat of air at constant pressure, 0.24. p density of standard air, 0.075 pounds per cubic foot. k --'4 b indoor-outdoor temperature differences, -Fahrenheit.
How doe to Wind
In considering the use of natural wind forces for pro-' /frying ventilation, account must be taken of: (1) average wind velocity; (2) prevailing wind direction; (3) seasonal and daily variations in velocity and direction; and (4) local wind interference by nearby buildings, hills, or other obstructions of similar nature.
Values are' given in Table 1, Chapter 27, for the average wind velocities for the months June to September in various localities throughout the United States, while Table 1, Chapter 26, lists similar .values for the winter. In almost aD localities, the summer wind velocities are lower than those in the winter, and in about two-thirds of the localities the prevailing direction is different during the summer and winter.' While the tables give no .average , velocities below 5 mph, there will be times when the velocity is lower, .even in localities where the seasonal average is considerably above 5 mph. There are relatively few places where the velocity - falls below one-half of the average for many hours per month.' Consequently, if the natural ventilating system is designed for wind velocities of one-half of the average seasonal velocity, it should prove satisfactory in almost every case.
Equation 5 may be used for calculating the quantity of air forced through ventilation openings by the wind, or for determining the proper size of such openings to produce -given results:
Q = BAV
"(5)
when
-
Q air flow, eubic feet per minute. 4 = free area of inlet openings, square feet. V " wind velocity, feet per minute, miles per hour X 88. B -- effectiveness of openings. (B should be t*lr<n at 0.50 to
0.60 for perpendicular winds, and 0.25 to 0.35 for diagonal winds.)1*
The precision of results obtained by the use of Equation 5 depends upon the placing of.the openings,-as the formula assumes that ventilating openings have a flow .coefficient riightly greater than that of a square-edged orifice.: if the openings are not advantageously' placed with respect to |he wind, the flow per unit area of the openings will be less and, if unusually well placed,-the flow will be slightly more than that given by the formula. Inlets should be placed to face directly into the prevailing wind, while out lets should be placed in one of the five places listed:
1. On the side of the building directly opposite (V direction of the prevailing wind.
2. On the roof in the low pressure area caused by the jump of the wind.
3. On the sides adjacent to the windward face where low pressure areas occur.
4. In a monitor on the side opposite from the wind. 5. In roof ventilators or stacks.
Row Due to Temperature Differences
The flow due to stack effect <*-n be calculated from Equa tion 6, which is based on the flow equation for a sharp edged
Fig: 8 .... Increase in Flow Caused by Excess of One Opening Over Another
orifice, and Equation 2, assuming the indoor and outdoor temperatures are close to 80 F.
Q " 9.44 Vh(ti -4~)
(6)
where
Q s air flow, cubic feet per minute.. -4 = free area of inlets or outlets (assumed equal), square feet h ~ height from inlets to outlets^ feet. 4 " average temperature of indoor air in height h, Fahrenheit. 4 ** temperature of outdoor air, Fahrenheit9.4 -- constant of proportionality, including a value of 65
percent for effectiveness of openings. This should be reduced to 50 percent (constant = 7.2) if conditions are not favorable.
>' Equation 6, is applicable only if there is no significant re sistance to flow within the building from inlets to outlets.
.The importance of maintaining the greatest possible height between inlets and outlets is obvious.
Effect of Unequal Openings
The largest flow per unit area of openings is obtained when inlets and outlets are equal, and Equations 5 and 6'are based on this condition. Increasing outlets over inlets,' or vice versa, will increase the air flow, but not in proportion to the added area. When solving problems having an unequal distribution of openings, use the smaller area, either inlet or outlet, in the equations, and add the increase as-determined from Fig. 8.
Row Due to Combined.Wind and Stack Effect.
_ Equations have already beer given for determining the air flow due to temperature difference and wind. It must be remembered that when both forces are acting together, even without interference, the resulting air flow 'is', not equal to.the sum of the two.estimated quantities. -The flow through any opening is proportional to the square root of the sum of the heads acting on that opening; . -
When the two heads are about equal in value, and the ventilating openings are operated so as to coorijinate.-them,' the total air flow through the building is about 10 percent greater than that produced by either; head acting independ-