Document gDE5k7K1pebZoMJxngjdVwRa
C H E C K D E P E N D A B IL IT Y !
when youw
RELIABILITY
INIMUM MAINTENANCE
ASKAREL-TYPE
transformers
oiobl^fa
TOWOLDMONOQ22715
Sometimes a "must" ...but often preferred by electrical engineers who know!
Askarel-type transformers have se-ved industry, insti
tutions, commercial housing, the military, electric
utility companies and electric railrmds safely, reliably,
economically . . . for over d() years * They tire supplied
built to exact, specification
>y all major electri
cal manufacturers. Hut only a relatively few engineers
and electrical architects have dug into chemistry to learn
Win the askarel transformer is so lire safe, so reliable in
operation, requires so little maintenance. Not too many
electro-technologists know that ; shared transformers
(even when they cost a little more compared KY for
KV with mineral oil transformers! can actually save
money on the installation as a whole, and save money
over years of use!
Askarel transformers are quite unit.lie. And the "tradesecret" is the fluid. If you would like to join the "inner circle" of astute electrical architects and engineers who for the past dt) years have known just how, where, and why an askarel transformer should be installed . . . just check the fads (and factors) n the following few pages.
Monsanto lias manufactured and supplier: askarel fluids since ttn* askarel-type transformer was first introduced. Askarel type trans formers were first made by General Hectic, in H.lO. the askarel fluid insulation was supplied under the trade mark I'yrariol. Other
trade marks for ttie askarel fluid, such as l-ierteen (Westirrp.house). Chlorextol (Allis Chalmers). Noflamol (Wa.;nor Hectnc): Ashestnl (Amertran Corp.); Saff-Kuhl (Kuhlrnan t ectnc). Many manufac turers, however, simply use ttie generic name, askarel.
0108177
TOWOLDMONOQ22716
THE FIRESAFE LIQUID INSULATION
THAT MAKES ASKAREL TRANSFORMERS YOUR BEST INVESTMENT!
M inoral-oil transformers can catch fire. Dry, opentype transformers can start a fire. Gas sealed trans formers require pressure and their cost is high! But askare) transformers quietly handle their load, under surge and drop, delivering a steady power flow year after year. The secret of this quiet, fire safe service is the askarel fluid . . . the finest, liquid insulation that chemistry has developed. Askarel fluid cannot, be ignited by a blow torch! In ad dition, this dielectric liquid will not. oxidi/.e or sludge; will not attack or corrode metals; remains chemically stable when subjected indefinitely to temperatures at least as high as 150* O. The unique values of the askarel-type transformers all stem from the chemical, electrical, and physical proper ties of the askarel fluids.
0108178
TOWOLDMONOQ22717
CHECKPOINTS FOR CHOOSING
5 ASKAREL-TYPE TRANSFORMERS
fire safely
economy
dependability
easy maintenance
low noise level
FIRE SAFETY
Askarel fluids, unlike- mineral oil, cannot, he ignited . . . even by the heaviest are, such as might. accidentally he caused hy lightning. Squally important., askarel transformers cannot carry or add burning oil hazards to fires that may start from other causes. The fluid does not deteriorate when exposed to heat, hot metal, nor docs it decompose over One use to ac cumulate electrically unstable contaminants. Since askarel fluid won't hum, and gases formed by arcing do not sup) ort combustion, the use of askarel transformers eliminates the possibility of fire and secondary explosion. Fire mfe askarel transformers tire tin- choice of far-sighted engineers for hospitals, hotels, schools, institutions, under ground networks, military bases, mines, shopping centers, electrical railroad systems, rocket sites.
0108179
C H E C K D E P E N D A B IL IT Y !
ECONOMY
Askarel type transformers cost alumt the saint- nr very s ightlv iiioi'c than open dry types, cost rnucdi less than scaltd dry -'pas. transformers, While askarel units cost up to 15% more than equal-eapaeitv mineral oil units, this initial cost is only pari of the economic picture: askarel transformers can usu ally he inst ailed wit hout t he cost ly vaults, fire walls, or sprink ler systems required by safety codes for mineral oil units. Further savings accrue in the design of the power transmis sion system. Since askarel units can he placed in congested, closed areas without danger to workers, askarel units (an be r/osc In the pom! of jmnrr tisane, i See Performance Compari son Table - In addition, fire insurance rates tire usually lower when askarel units are used.
DEPENDABILITY
A properly designed and installed askarel transform! r will give trouble-free service for a minimum of .`10 years. Since their introduction in Iflfitl, the manufacturers report f tiding the overall failure rale to he less than 0,5% for all units under leu! and uernre ronddianu. The Hdison Klectric Insti tute's last report i.1 95fi-1 !)5Ki on their member utilities pub lishes the failure rate for askarel transformers as u.i.l per hundred bunk* per year! Kven these rare reported failures are found to be due to improper sealing that allowed tie isture to enter. Modern design requirements for askarel transformer seals eliminat.es possible failure.
EASY MAINTENANCE
Askarel transformers are easiest, to maintain! Most of the askarel transformers in service today have received little or no maintenance in decades of operation. Kven tin* accumu lation of relatively large amounts of non-ionic contain mints has little effect upon askanTs excellent dielectric strength. The only contamination that seriously affects the askarel's dielectric* strength is water. Proper sealing banishes this source of contamination. Five simple periodic tests [three of them, visual; will check out the askarel insulation. Motisant > and the transformer manufacturers furnish guidance literature on this easy-to-follow maintenance. Unlike oil typo trans formers, with askarel units there* is no chance of fluid oxi dation or sludge formation, and therefore, less need for replacing the fluid.
LOW NOISE LEVEL
Askarel transformers operate quietly! Where open dry type transformers in office buildings, hospitals, schools and insti tutions require a sound suppressing room or locating far from point, of use, askarel units are so quiet that no sound problem arises. Wherever a fire safe transformer is warrantee, the askarel type unit operates at a significantly lower noise level than dry types and offers a significantly superior in pulse rating over the dry type.
Askarel-Type Transformers Offer Five Important Advantages Over Other Type Transformers
Eliminate Fire Hazard More Economical to
Install and Operate
Proven Dependability Less Maintenance, Easier Upkeep More Quiet Operation
0108180
TOWOLDMONOQ22719
BASE UNIT CO
MINERAL OIL
010818L
TOWOLDMONOQ22720
ST & ADDITIONAL EXPENSE COMPARISON
I .the ,,<lditiun.>l ,MSI.ill i (I .ill , ,t HUl : one.ui.,1 u ut
. ny other type
Icdliu ti.il i ni, r,: 11.111 < j n : ost. m. .i< 1 (1 j11mn,11 1111 . t 1M.", needed
lot bre ..... I
i 'plosion ,, 111 I y -
1 i 11 If.' .iclel it IOf 1.11 f ' I Vi t. 111 11 !f;f] cost [U I i ; i. onr mt bo
xcessiye 111 niospliolie dust, dut. moisture, or whom hmh noise
level will Culise Niterfoienc.e.
CHECK THE COST!
ASKAREL
OPEN DRY TYPE
SEALED, GAS DRY TYPE
oioaiai.oi
TOWOLDMONOQ22721
Here are
four important reasons
why engineers choose askarel
transformersi
SAFETY! Freedom from fire and sec ondary explosion.
USE FLEXIBILITY! Tightly sealed askarel trans formers can be used in at mospheres contaminated with dust, lint, corrosive vapors and moisture.
DEPENDABILITY! Askarel fluid does not oxi dize or sludge.
LOW NOISE LEVEL! Askarel transformers ean be installed close to power sup ply outlets without causing objectionable noise.
FOUR IMPORTANT ADVANTAGES FOR INDOOR USE, AND FOR OUTDOOR INSTALLATIONS, TOO!
RANGE OF ASKAREL
TRANSFORMERS
Askarel transformers art* available in all capacities, in size ratings exceeding 1 ;'>,()()() KVA. Most askarel transformers in use to day fall in the da to 2,000 KVA range, the majority ranging between 100 and 1,000 K YA.
The following transformer comparison chart is devised to show the economics of askarel units in the do to d.OOO KVA range, which art* used primarily for their superior safety leal arcs.
010blb2
TOWOLDMONOQ22722
compare- llic performance advantages...
ASKAREL
OPEN DRY TYPE
MINERAL OIL TYPE
/CLOSED { 1 GAS
SEALED
Transmission & Service Costs
NORMAL RANGE
HIGH
HIGH
HIGH
Supplemental Installation Costs
NEGLIGIBLE
HIGH (if noise damping or shield ing from atmos phere, contamina tion & water is needed)
HIGH (when used indoors, requires vaults, fire walls, sprinklers and noise damping)
NEGLI GIBLE
Operational
EXCELLENT
Dependability
Affected by cor rosive atmosphere, moisture, water flooding, dirt and dust.
GOOD
EXCEL LENT
Amount of Maintenance Required
LITTLE OR NONE
CONSIDERABLE
FAIR due to oil's NONE tendency to degrade in service.
Operating Noise Level
VERY LOW
HIGH
MEDIUM
HIGH
Impulse Levels
HIGH
LIMITED
HIGH
LIMITED
Safety from Fire
EXCELLENT AND COMPLETE
FAIR can cause ignition
POOR can cause ignition and propagate fire
FAIR
01081B3
TOWOLDMONOQ22723
HERE'S WHERE AN ASKAREL TRANSFORMER 1-------- 1 IS YOUR BEST CHOICE
INDUSTRIAL LOAD CENTERS
In factory areas where maximum safe ty from fire is required and atmos phere contamination may [ire' ail.
UTILITY NETWORKS
Where location underground or al ove the surface requires protection l"om water and other elements, and where maximum safety against fire is needed,
INSTITUTIONS AND OFFICE BUILDINGS
1 n schools, hospitals, govern merit buildings, hotels, airports, shopping centers, sport stadiums, etc., where maximum safety and lowest noise levels are required.
WATER FRONTS AND BOAT DOCKS
Where fin* and weather resistance are the prime requirements.
ELECTRIC RAILROAD SYSTEMS
Transformers on electric trains md throughout the system require maxi mum safety features and assurance against faulty operation din* to we, th-
MISSILE SITES
When* surface and underground struci tires demand reliable performance and complete protection from we; fli er, fire and explosion.
CONGESTED OUTDOOR INSTALLATIONS
Where safety from fire and explosion are required for crews working close to transformer units.
01081B',
TOWOLDMONOQ22724
Ski nr engi r ] < ( * is who have had no upper l unity I o act] u ire actual opera! iii).' experience with askarei transformers and who have received little i i] for n ta I m 11 about lliem sometimes harhor mis!aken opinions that are contrary to the facts. Here are the three 111 iscoiieept ions that, however infrequent, (lave been occasionally encountered :
"Askarei fluids are `poisonous.' " The facts: askarei fluids ha\e been manufactured, handled, and used for over do veto's without encountering toxic or ill-effects. It is well accepted by transformer makers and utilities that askarei fluids are not hazardous when handled under standards of normal good housekeeping ,oid the ordinary personal precautions used wilh other inert industrial materials.
"Askarei transformers can explode." The facts: there is no instance, in the whole use history of askarei units, of sec ondary explosion because gases formed by arcing are non explosive and non-combustible,! Kven under strong arcing, the possibility of primary explosion in a properly designed aid escape- vented askarei transformer is very remote. Modern di-'-ign matures, such as cable connection seals, completely protect askarei 1 ransformers from possible explosion.
"Askarei fluids run a high power factor." The fuels: Kngmeers experienced with askarei transformers know Unit it
i,lor an askarei transformer to show a higher power tad or t ban a mineral ml unit.
It is technically unsound to compare the insulating efficiency of oil and askarei by simply measuring power factor. A high power factor in mineral oil /s cause for alarm; HUT it is norma! for askarei to show a power factor as high as 20 to Mi per cent at 100 (00 cycles i 2-8` , at 20''('; with absolute ly no danger of ellicienry loss or impairing normal operation.
\(>TK: Thi' most- significant and reliable measurement, of transformer askarei is its 1 >1 Kl .KCTKIC STKKN CiTH . As karei will maintain its high dielectric strength unless there ;s significant moisture contamination or breakdown of the fluid from an unusually severe exposure to arc.
0108185
TOWOLDMONOQ22725
Askarel fluids iboth Jnorteen ami i'yiunol 1 y pe; arc manufactured by Monsanto and shipped promptly to users anywhere in the world. Askurel transformer fluids, unlike naturally formed oils, are manufactured and quality-checked for consistency and shipped with an extreme care that is snivel to few industrial materials, Tins means asl-are! fluids can lie depended upon to be unitonn and provide the optimum service of any liquid insulation.
Operating with askarel units is the sa'est, easiest, often lowest cost way to distribute electrical power. Monsanto will he happy to send you a copy of the pamphlet "Care and Grooming of Askarel Transformer Fluid" or request a copy from the transformer manufacturer of your choice. And if you do . ASK HIM to check the facts on askarel transformers described on the >recediny' pages.
MONSANTO CHEMICAL COMPANY Aviation and Special fluids Department Organic Chemicals Division St. I ouis 00, Missouri
Askarel transformer fluids can be ordered directly from any one of these Monsanto sales service centers Atlanta Boston Chicago Cincinnati Cleveland Detroit Houston l os Angeles Minneapolis New York f'lttsb urgli St. I o u i s San ( rancu.co Seattle Syracuse Wilmington
oioeiat
TOWOLDMONOQ22726