Document gD6p3bp31GOGObKNw30RpB6nN

so Chapter 1 1945 Guide Example 18. If dry saturated steam at 20 lb per square inch absolute is injected into air initially at 60 F and 30 per cent saturation to raise the temperature to 70 F, what is, the final degree of saturation and how much water is added per pound dry air? (See Fig. 7.) Solution. The initial humidity ratio is 0.30 X 0.01103 = 0.00331 lb water per. pound dry air (or direct from chart). The initial enthalpy is'14.39 + (0.30 X 11.98) = 17.98 Btu per pound dry air .(table) or 14.67 + (1000 X 0.00331) = 17.98 (chart). A pre-" liminary calculation shows that the final mixture contains liquid. The final weight of water per pound of dry air is determined from 33.96 + (W -- 0.01574) X 38.0 - 17.98 W - 0.00331 = 1156.3 where the specific enthalpy of the injected water is 1156.3 Btu per pound. The answer is W -- 0.01718 lb water per pound dry air. Therefore, the weight of water added is 0.01718 -- 0.00331 = 0.01387 lb per pound dry air as shown in Fig. 7. Adiabatic Saturation Any case of adiabatic mixing in which the resulting mixture is saturated may properly be called adiabatic saturation. For example, if enough water at 352 F be sprayed into dry air at 80 F to produce a saturated mixture, the resulting enthalpy will be hs = 19.19 + (Ws -- 0) 324; and since As and Ws are functions of the same temperature, this temperature is determined by the equation to be 53.0 F. Thus, adiabatic saturation of dry air at 80 F by injecting liquid water at 352 F results in a tempera ture of 53.0 F when saturation is reached. But in practice, much more is usually read into the term adiabatic saturation, it being generally understood that saturation is to be pro duced by injecting liquid water at such a temperature as will coincide with that at which the saturation curve is reached. With this under-, standing it may be said that thermodynamic wet-bulb temperature is the result of adiabatic saturation. Thus, if liquid water at 48.26 F instead of 352 F be injected into dry air at 80 F a saturated mixture at 48.26 F instead of 53.0 F will be produced. Therefore, 48.26 F is the thermo dynamic wet-bulb temperature of dry air at 80 F. It is possible to produce adiabatic saturation, interpreting the' term literally, by mixing two air streams neither of which is itself saturated. In order for this to be possible, the straight line connecting the repre sentative points on the Mollier diagram must cut the saturation curve twice. Cooling' Load In the calculation of the cooling load for an air conditioned space, the problem usually reduces to determining the quantity of inside air that must be withdrawn and the condition to which it must be brought by cooling, separating and possibly reheating so that return of the conditioned' air will have the net effect of removing given amounts of energy and water from the air conditioned space. Let m denote the weight of dry air withdrawn per hour. With it will be withdrawn energy of amount mhi Btu per hour and water of amount mWi pounds per hour, where hi and Wi denote enthalpy and humidity ratio, respectively, of inside air. The weight of dry air returned per hour will be the same as that withdrawn but with it must be returned a smaller amount of energy, mh Btu per hour, and a smaller quantity of water, mW pounds per hour, where h and W denote enthalpy and humidity ratio of conditioned air. Thermodynamics of Air and Water Mixtures 31 With this understanding, the requirements of the cooling load problem e, mh -- mh\ -- AQ mW = mW\ -- A W where AQ and A IF are the given amounts of energy and water, respect ively, to be removed simultaneously. Eliminating m from these equations, ,h - hi _ AQ _ W -- Wi AW ~ 2 (25) which says that all possible states for the conditioned air lie on a straight line, on the Mollier Chart, which passes through the state point of the Inside Air with a slope determined by the ratio q (Btu per lb water) of the quantities of energy and water to be removed simultaneously. This straight line is called the condition line for the given problem. If. the condition line crosses the saturation curve the intersection is called the apparatus dew-point (Chapter 20). For, if the air conditioning apparatus is set to produce a saturated mixture having the temperature corresponding to this point, the introduction of this saturated mixture Fig. 8. Diagram Illustrating Example 19 into the conditioned space will result in the simultaneous removal of the required amounts of energy and water. Graphical solution of a cooling load problem is facilitated by the border scale on the Mollier Chart. The numbers around this border.scale may be regarded as values of the ratio q (Btu per lb water), each number deter mining the direction of the corresponding condition line. Example 19. A condition of 80 F dry-bulb, 67 F wet-bulb is to be maintained in a certain clothing store, outside conditions being 95 F dry-bulb, 75 F wet-bulb. The energy gain from normal heat transmission is estimated at 16,000 Btu per hour, that from solar radiation at 48,000 Btu per hour. The energy generated by lights, fans, etc., is estimated at 13,900 Btu per hour. The ventilation requirement is 30,000 cu ft of Outside Air per hour. The number of occupants is 50. Find the apparatus dew-point and the cooling load as analyzed in Fig. 8. Solution. The thermodynamic properties of Outside Air are: v = 14.29 cu ft per pound dry air, h = 38.26 Btu per pound dry air, and W = 0.01402 lb water per pound dry air. Therefore, the weight of dry air entering with the Ventilating Air is 30,000 -r14.29 = 2099 lb dry air per hour. This brings with it energy of amount 2099 X 38.26 = 80,300 Btu per hour and water of amount 2099 X 0.01402 = 29.43 lb per hour. An equal weight of dry air must be displaced from the store. The thermodynamic properties of Inside Air are: hi = 31.41'Btu per pound dry air, and Wi = 0.01115 lb water per pound dry air. Therefore, the energy leaving the store