Chapter 14
1945 Guide
------For rating purposes4 vacuum-pumps- are classified as low vacuum-and high vacuum. Low vacuum pumps are those rated for maintaining in. Hg vacuum on the system, and high vacuum pumps are those rated to maintain vacuums above 5J4 in.
Manufacturers of vacuum pumps specify that the standard capacity of pumps shall be 0.3 to 0.5 cfm of air removal and 0.5 gpm of water per 1000 EDR served. This capacity is at 5J4 in. of vacuum and with con densate at 160 F. The larger air capacity is for smaller systems and the . smaller capacity for the larger systems.
1 Some manufacturers, however, specify more air capacity than standard where higher vacuums are desired and where air leakage is. suspected.
The vacuum that can be maintained on a system depends upon the relationship of the air leakage rate into the system to the operating air capacity of the hydraulic evacuator when operating at any given return
Fig. 18.
Method of Discharging High-Pressure Apparatus into Low-Pressure
Heating Mains and Vacuum Return Mains through a Low Pressure Trap
line temperature. The hotter the returns, the lower will be the possible vacuum for a given air leakage rate into the system. It is particularly essential on high vacuum installations to see that the entire system is tight in order to reduce the amount of inward air leakage and, further more, to see that relatively higher temperature steam is prevented from entering the vacuum return lines through leaky traps, high pressure drips, etc. It is for this reason that the condensate from equipment using steam at high pressures should not be connected directly to a vacuum return line but should drain to a receiver through a high , pressure trap. The receiver should have an equalizing connection to a low pressure steam main and drain through a low pressure trap to the vacuum return main as indicated in Fig. 18.
Vacuum Pump Controls
In the ordinary vacuum system, the vacuum pump is controlled by a vacuum regulator which cuts in when the vacuum drops to the lowest point desired and cuts out when it has been increased to the highest point, these points being varied to suit the particular system or operating conditions. In addition to this vacuum control, a float control is included
A.S.H.V.E. standard Code for Testing and Rating Return Line Low Vacuum Heating Pumps. (A.S. H.V.E. Transactions, VoI. 40. 1934, p. 33).
Steam Heating Systems and Piping
277
whichwillaUtomatically start the pump whenever sufficient condensation accumulates in the receiver, regardless of the vacuum on the system. A selector switch is usually provided to allow operation at night as a con: densation pump only, also to give manual or continuous operation when desired.
There are several variations in the control of the vacuum maintained on the system by the pump. In some sub-atmospheric systems where orifices are used, the vacuum pump control maintains a pressure difference between the supply and the return piping, which Is held within relatively close limits. There are other sub-atmospheric systems which utilize special temperature-pressure actuated controls for maintaining the desired conditions in the return lines. Where various zones are connected to the same return main, the return vacuum must be controlled to meet the requirements of the zone operating at the lowest steam supply pressure.
Piston Displacement Vacuum Pumps
Piston displacement return vacuum heating pumps may be either elec tric or steam driven. Their piston speed in feet per minute should not exceed 20 times the square root of the number of inches in their stroke. They are usually supplied with an air separating tank, open to atmos phere, placed on the discharge side of the pump and at an elevation sufficiently high to allow gravity flow of the condensate.to the boiler. If the boiler pressure is too high for such gravity feed then an additional steam pump for feeding the boiler is desirable. The extra pump is some times avoided by using a closed separating tank with a float controlled vent. In both arrangements, the air taken from the system must be discharged against the full discharge pressure of the vacuum pump. In the rase of high or medium pressure boilers, it is better to use the atmos pheric separator and the second pump.
In figuring the required displacement for such pumps, a value of from 6 to 10 times the volumetric flow of condensation is used for average vacuums and systems.
TRAPS
Traps are generally classified as to function as (a) separating traps, (o) return, lifting or vacuum traps, and (c) air traps. Separating traps may be either float operated, thermostatically operated, or float and thermostatically operated. Return traps for low pressure service are referred to later as alternating receivers in this chapter. Return traps may also operate to receive condensate under a vacuum and return it to atmosphere or a higher pressure. Air traps are generally float operated.
Separating traps are used to release water of condensation but to retain
steaTM- The thermostatic, and float and thermostatic types release both condensate and air but retain steam. Separating traps are used for draining condensate from radiators, indirect air heaters, steam piping systems, kitchen equipment, laundry equipment, hospital equipment, drying equipment and many other kinds of apparatus. Air traps release aiJ". retain water. Devices known as air vents are, in principle, traps wnich allow the passage of air but prevent the passage of either water or stCcim.
Return traps are used for returning condensate either by gravity, by
?* am Pressure, or by both, to a boiler or other point of disposal, and for condensate from a lower to a higher elevation, or for handling
ondensate from a lower to a higher pressure.