Document g2brmOqzxDzQmV7LyrjkXbbb9

CHG uiox-' PLAINTIFF'S EXHIBIT e champlin [ , ,,, | ^ A SuDS a ar / ot un on Pac **C CO'OO*at on INTER-OFFICE CORRESPONDENCE 0GAY / - / TO: M. A. Hawkinson PERRYMAN..^ OFFICE: Ft. FROM: G. T. Westbrook DATE: October'T3'L 198A Tn SUBJECT: ARKWRIGHT-BOSTON INSURANCE RECOMMENDATIONS FOR BOILER 561-B-2 . --....... ;......; & In the Loss Prevention Report dated August 13, 1986, tCDNTROLrecommendation was made to repair the rear wall of this boiler as soon as possible. The rear of the boiler wall refractory had begun to lean inward causing some minor deformation of the water wall tubes. Since that report, this boiler was removed from service and the rear wall repaired by completely removing the rear wall and adding additional reinforcement. No repairs were made to the water wall tubes. Deformation was minor and did not warrant repair at this time. cc: R. E. Schneck R. W. Arey J. H. Tansey R. D. Madigan Arkwright-Boston Insurance Inspection File: 561-B-2 mcwwm saifflw & UDWWlj- [USPT CH/W-002584