DETERMINING REFRIGERATION LOAD
The following determination of the refrigeration load shows a division of the true sensible and latent heat loss of the air, which is accurate within the limitations of the data. These divisions will not correspond to load determination obtained from approximate factors or constants.
The total refrigeration load g, of a cooling and dehumidifying coil (or air washer) is indicated on Fig. 13 and consists of the following components:
Fig. 13 .... Psyehrometric Performance of Cooling Coil in Central System
1. The sensible heat q, removed from the dry air and moisture in cooling from entering temperature <i to leaving tempera ture ft.
2. The latent heat q, removed to condense the moisture at the dew-point temperature t* of the entering air.
3. The heat of subcooling qm removed from the condensate in cooling it from the condensing temperature f to the leaving condensate temperature f.
Items 1, 2, and 3 may be related by
fli TM 9* + ? + q
(5)
If only the total heat value is desired, it may be computed by
qt =* (hi -- h*) -- (w, -- tr*)h-
(6).
where
ht and h * enthalpy at points 1 and 2 respectively. tc>i and tci humidity ratio at points 1 and 2 respectively.
hw => enthalpy of saturated liquid at the final tem perature, tj.
If a breakdown into latent and sensible heat components is desired, the following relations may be used:
The latent heat may be found from
where
q. -- (ti -- toi)h/#
(7)
h/H B enthalpy at the condensing temperature, U .
The sensible heat may be shown to be
9. + " (hi -- hi) -- (uH -- u>t)hr<
where
-f (tt>| -- 10l) (hw4 - h.) (8)
hlt > enthalpy at the condensing temperature, t* . Ah = enthalpy of saturated liquid at condensing tempera
ture, U .
The last term in Equation 8 is the heat of subcooling the condensate from the condensing temperature U to itB final temperature U. Then,
9 = fwi -- wo (Ah -- hm)
(9)
' AHvalues for solving the foregoing equations may be found on the ASHAE Pbtchrometric Chabt and Tables 2 and 3 of Chapter 3.
Example 1: Air enters a coil at 90 F dry-bulb, 75 F wet-bulb; it leaves at 61 F dry-bulb, 58 F wet-bulb; leaving water is assumed to leave at a temperature between the leaving air dew point and coil surface temperature of 54 F. Find the total, la tent, and sensible cooling loads on the coil.
Solution: From the ASHAE Pbyckbometbic Chaht, find the following:
hi " 38.42 Btu per lb of dry air. hi " 25.10 Btu per lb of dry air. f " 69 F wet-bulb of entering air. 101 " 0.01525 lb per lb of dry mr. 10b =* 0.00960 lb per lb of dry air.
From Table 3, find:
hw* " 37.11 Btu per lb. -- 22.12 Btu per lb.
h/M - 1054.27 Btu per lb. 1091.34 Btu per lb.
The total heat from Equation 6 is
q, - (38.42 - 25.10) - (0.01525 - 0-00960) X 22.12 - 13.32 - (0.00565 X 22.12) = 13.32 -- 0.12 = 13.20 Btu per lb dry air.
The latent heat from Equation 7 is
q. - 0.00565 X 1054.27 - 5.96 Btu per lb of dry air.
The sensible heat by difference, is
9> + 9 * ffi -- q, TM 13.20 -- 5.96 = 7.24 Btu per lb of dry air.
Or the sensible heat may be computed from Equation 8 as
q, + 9* - (38.42 - 25.10) - (0.00565 X 1091.34) + 0.00565 (37.11 - 22.12)
- 13.32 - 6.16 + 0.00565 X 14.99 -- 13.32 -- 6.16 + 0.08 -- 7.24 Btu per lb of dry air.
The subcooling of the condensate as a part of the sensible heat is indicated by the last term of the equation, 0.08 Btu per lb of dry air.
CHAPTER 24
AIR CLEANING
Atmospheric Air Cleaners: Airborne Particulate Matter, Viscous-Impingement Filters, Dry Air Filters, Electronic Air Cleaners, Air Filter Performance, Selection, Maintenance, Installation, Adsorption of Vapors; Industrial Air and Gas Cleaners: Degree of Cleaning, .Selection, Types, Application, Inertial Separators, Scrubbers, Wet Collectors, Filters, Electrostatic Precipitators, Adsorbers, Absorbers, Combustion Devices
AIR cleaning devices remove contaminants from an air it is desirable to pass air through a series of two or more dif L or gas stream. They are available in a wide range of ferent types to obtain optimum results. . dcrigna to meet various air cleaning requirements. Degree of
removal required, quantity and characteristics of the con
AIRBORNE PARTICULATE MATTER
taminant to be removed, and conditions of the air or gas stream will have a bearing on the device selected for a given application. Definitions and a discussion of contaminant char acteristics are given in Chapter 7, together with some consid eration of their origin.
Air cleaning devices are divided in this chapter into two basic groups: Atmospheric Air Cleaners, described in Part I, and Industrial Air and Gas Cleaners, described in Part II.
Atmospheric Air Cleaners are ordinarily used to remove particulates such as are found in outdoor air, and are em ployed in ventilation, air conditioning, and heating systems where dust content seldom exceeds 4 grains per 1000 cu ft of air.
Industrial Air and Gas Cleaners are ordinarily used for the heavier concentrations encountered in local exhaust ventila tion where the particulate content (loading) ranges from 100 to 20,000 grains per 1000 cu ft of air. Because of these heavier loadings, atmospheric air cleaners can seldom be used for the control of process aerosols in industrial applications.
Suspensions of particulate matter in the air are called aero- sols and consist of smokes, dusts, mists, and fumes. The
characteristics of the aerosols which affect the performance of an air cleaner include particle size, concentration, shape, den
sity, velocity, and surface characteristics. One of the most im portant of these is size.
The rate of settling of particles varies approximately as the square of the diameter. Particles larger than 10 microns in diameter settle so rapidly that the concentration of such particles decreases rapidly as the distance from the source increases. Particles less than 1 micron in size settle so slowly that the ordinary convection currents prevent sustained downward motion, and consequently such particles remain in the air for long periods.
If particles could be examined through a super microscope having a magnification of 250,000 diameters, a tobacco smoke' particle of 0.1 micron would appear to be 1 in. in diameter, or approximately the size of a golf ball; a soft coal smoke particle 03 micron in diameter would appear like a baseball;
PART I--ATMOSPHERIC AIR CLEANERS
a ragweed pollen grain of 20 microns in diameter would ap pear 16.5 ft in diameter, while the 50 micron particle (just
Conventional air filters and electronic air cleaners are in visible to the naked eye and able to pass through a 270 mesh
stalled in air handling systems-to remove dusts. These dusts screen) would appear to be 50 ft in diameter. Consideration
constitute a mixture of particle sizes within the classification of this range in particle size from a golf ball to a sphere 50 ft
of temporary and permanent impurities listed in Tig. 1, Chap in diameter will emphasize the difficulty of devising any single
ter 7, including bacteria, pollens, house dusts, and similar al test to measure adequately the performance of air cleaning
lergens which motivate attacks on persons of allergic sensi devices under all conditions of service.
tivityb *
The particles in the atmosphere can range in size from less
Since the purpose of the filter or cleaner is to free the air of than 0.01 micron up to things which are caught by an ordi
as much existing contamination as practicable, the degree of nary fly screen, such as lint, feathers, and insects. Almost all
air cleanliness required should influence the choice of appara conceivable shapes and sizes are represented. Tbe material
tus. Atmospheric dusts are mixtures of particles in all rises. is very commonly soot, ash, soil, lint, smoke, and fumes, but
The removal of these particles and fractions becomes pro may include particles of almost any inorganic or organic ma
gressively difficult as the particle rise decreases. Smoke parti terial and even such living organisms as virus, bacteria* and
cles are of major importance in many applications. Air clean fungus spores.
ers will justify their cost through a reduction in housekeeping
Thi3 wide variety makes it impossible to design one type of
expense in the ventilated space, by the protection of the cleaner which will be best for all applications. Mechanical
equipment in the ventilation system itself, and by providing filters of the low-pressure type can remove large particles
relatively dust-free air for critical manufacturing processes. effectively. Other mechanical filters can remove extremely
Cleaning devices for atmospheric air are classified by the fine particles, but may be handicapped somewhat by high-
principle employed to collect dirt particles such as impinge pressure drop and cost. Electronic air cleaners have the ability
ment on viscous coated media, filtration through porous me to give high effectiveness on normal atmospheric contamina
dia, or electronic air cleaning. In some cases a filter may dis tion, with a low operating-pressure drop.
play a combination of these principles. Fjuh type of air
As a general rule, the renjoval of the coarser dust particles
cleaner has certain advantages. There are applications where and lint from the ventilating air produces tangible results in
1
i