Document g20BQZ9Nzyw54qvRDVRyyyE5G
794
CHAPTER 50
1965 Guide And'Data-Book
Lubricants in Refrigerant Systems
795
fig. -19 .... Viscosity, of Mixture, of -150 SUV Paraffin Base Oil and-Refrigerant 13B114 -
fig. 21 .... Viscosity of Mixture of 300 SUV Paraffin Base Oil.and Refrigerant 13Bt14
ate point where much of the refrigerant has escaped from the
oiL1 In the case of the highly miscible oil-Refrigerant 12
solutions, the maximum viscosity is quite lowj` and oil.return
problems have seldom occurred with this refrigerant On the
other hand, such problems have occurred'with Refrigerant 22
in 80me low temperature installations, and it is possible to'
picture'a posable example from the data in Fig. 39. If ab-
evaporator on a Refrigerant 22 system is operating at about
-- 40 F, which corresponds to 1 prig suction pressure, any oik
Refrigerant 22 solution that separates should be quite low in
viscosity at that temperature. However, when this solution
moves into a region where.the temperature is -- 20 F, possibly
in the suction line, its viscosity would be expected to increase
many tim***, perhaps to such an extent as to interfere with
gas flow.
.w
Fluidity of Oil at Low Temperatures
As implied in the preceding paragraph, any oil intended for
low temperature service, whether in refrigeration equipment
or in other,types of machinery, should be able to flow at the
lowest temperature likely to be encountered. This require
ment is usually met by specifying a suitably low! pour point' fhepour point of an oil is defined as the lowest temperature
at which.it is still fluid, and can be poured, when tested ac
cording to the standard method prescribed in ASTM D-97.
Nominal pour points of typical refrigeration oils are listed in
Table 1.
-
.The loss of fluidity by cooling to the pour point temperature
may manifest itself in two different ways. With some oils a
gradual increase in viscosity occurs; the flow Becomes more
and more sluggish as the temperature is lowered and, finally,
becomes so slow that iio perceptible motion is seen within the
time C5.sec) specified in the test procedure. This.type of be
havior'is most frequently seen in testing "naphthene base oils.
CotnbtnxJ date from Reference* 9, 13, and IS. Include* naphthene and paraffin bate o3t la viscoafy grades from I SO SUV to 300 SUV.
Fig. 23 .... Solubility of Refrigerant 22 in Refrigeration Oils
crystals which:occupy the entire volume of the sample. .This
network prevents flow but may still retain unfrozenliquid in
its interstices. The wax crystals have relatively high freezing
points in comparison with other hydrocarbon types; hence,
when equivalent viscosity grades are tested, pour points.of
paraffin, base oils are generally , higher than pour points of
naphthene base oils.
,
Oils intended for refrigeration use, whether paraffin or
naphthene base, are normally refined and dewaxed to obtain
low pour points. Although not recommended for refrigeration
oils, for some applications pour points can-be lowered by
adding chemicals known as pour^point depressors: These
chemicals do not actually prevent wax separation but merely
change the crystal structures from needle-like shapes which
trap tile unfrozen oil to ball-like shapes which will pour with
the oik* .
-
v!
liquids other than mineral oils, such as polybutyl silicates^
and alkyl benzenes?1 which do not contain waxy constituents,
have also been suggested for lubricating systems in which
wax separation (or oil-rich phase separation) may be aprob-
fem.-
,i
Standard pour tests are pjerformed on oils alone,-in-room
air. But in a refrigerant system, oil is always-mured with
refrigerant which, - if soluble, greatly increases the' fluidity
even at low. temperatures. For this reason, the significance of
the standard pour tests when used to qualify refrigeration oils
has been questioned.. :> ...
..
..Standard pour test values are.significant in the selection of
oils for ftmmonift and carbon dioxide systems, or for any other system in which refrigerant and oil are almost totally immisci ble. In such a system, any oil which-gets into the low'side is essentially1 refrigerant-free, and hence the pour point of the oil itself--in other words, the standard pour point--will de-
fig.,24,.... Viscosity-Temperature -Chart for.Solutions.of Refrigerant 22 in 150 SUV Naphthene and-Paraffin Base Otis