WRITTEN BY: PULL EM QAT APPROVED BY: DERIVATIVE'S AREA
SUPERVISOR'S DATE: 6/22/88 REVIEWED: 7/89 MJF
This SOP is written to develop a uniform procedure throughout Derivatives to ensure that the appropriate steps are taken prior to removing from service or bypassing an alarm, instrument, or shut down system automatic valve. This SOP will provide an effective way of communicating the status of these instruments to others and making sure that the necessary steps are taken to correct the problem. This procedure is intended to apply to all pressure, temperature, flow, level, analyzer, etc. instrumentation and the ,associated control valves.
This SOP has been modified for VCM-JI.
CHECK
ACTION STEPS (Capital letters) and Comments (Small letters)
0
CO LO CO
O Q C/3
1. IF AN ALARM, INSTRUMENT, OR SHUT DOWN SYSTEM MALFUNCTIONS, THE OPERATOR'S FIRST RESPONSE SHOULD BE AN ATTEMPT TO FIX IT.
In every circumstance, the first response should be a reasonable effort toward correcting the cause of the problem. Operating without alarms, instrumentation, or shut down system valves introduces a level of risk that is not desirable.
2. CHECK TO MAKE CERTAIN WHAT PRIORITY THE ALARM, INSTRUMENT, OR CONTROL VALVE FALLS INTO:
Check the list of alarms attached in the unit SOP manual to
determine what the priority of the alarm is.
The priority
system to be used is as follows:
w 3 C* 0 T1?4 'J o <!> -H W *4 m tv t. + **< -M
&G I r-4 ^
to.? o- c->
m n. o
1X c - 0 C' 'T St u
'o ; -'A
Priori tv 1_ - Critical instruments whose failure would either
cause or fail to inform of situations causing accidental
fire, explosion, uncontrolled release of dangerous
i
materials, reportable environmental releases, or major'
property or production loss. These alarms include those
which have been mandated by outside agencies (RCRA, EPr. ,
DEO, Consent Decree), also Operations Review Committee
(ORC) reliability alarms, and alarms deemed critleal.-
operations supervision. All of these alarms are op . the;'
prooftesting schedule.
* -- *
Pri ori t y
- Critical instruments whose failure could either
cause or fail to inform of serious conditions involvingi
recordable environmental releases, property or product if;)
losses, or other non-life threatening situations.- These
-r, ja * 2 -t(A
id]*-'are,^slfi ghtly lower priority
r> -
^ ,ppop^f eating schedule.
.'> $. 'Priorit v" 3'*-* Wil^n-other alarms,
prooftesting schedule. For
alarms which are
which are not on VCM-II, priority
also on fh--
the 3 includes
control valves which are not tied directlv into a PCS'.
PAGE 1 OF 4
rr LO ro tj-
o
o
CO
tj M3 0) 0
Tj o
Vj O -
y
-H y ta p 4i *n < *> X *r t* IDh y. 4-i w o *-! ^ a u *s ^ *- C. -H
If.. u *
KG 0 O C- K CJ 3
*j n
y
ui *r*. -> Xt -* 3 H
w
o
Note: Operations will treat priority 1 and 2 alarms in an
identical fashion. The only reason that these are
differentiated is for the sake of the proof testing"*
program.
IF THE ALARM. INSTRUMENT, OR CONTROL VALVE IS PRIORITY 1 :0R 2,
GO TO STEP 05. IF THE ALARM IS PRIORITY 3. GO TO STEP-03.
'X
3. RESPONSE TO PRIORITY 3 ALARMS AND BYPASSED CONTROL VALVES. THE LEAD OPERATOR SHOULD USE HIS KNOWLEDGE OF THE UNIT TO*.
EVALUATE EACH SITUATION AND MAKE A DECISION AS TO WHETHER .THE INSTRUMENT OR CONTROL VALVE CAN BE BYPASSED OR NOT. \ ['} *
If there is any doubt about this choice, supervision -sh&uld
be consulted. These alarms and instrumentation are hot'
considered critical under normal conditions.
.
4. THE LEAD OPERATOR SHOULD FILL OUT A YELLOW OUT-OF-SERVICE
TAG FOR BYPASSED CONTROL VALVES ONLY. A TAG DOES NOT HAVE TO
BE FILLED OUT FOR PRIORITY 3 ALARMS.
Immediate action is to be taken to initiate repairs on instrumentation. This means at least a note in the maint. logbook so that the problem will not be forgotten.
STOP HERE FOR PRIORITY 3 ITEMS.
5. RESPONSE TO PRIORITY 1 OR 2 ALARMS. RCRA, EPA, CONSENT DECREE. OR CRITICAL ALARMS, INSTRUMENTATION OR SHUT DOWN SYSTEM AUTOMATIC VALVES. NOTIFY YOUR LEAD OPERATOR OF THE SITUATION.
No one except the unit lead operator or supervisor has the authority to approve taking an alarm out of service.
6. THE LEAD OPERATOR WILL DECIDE IF IT IS SAFE TO TAKE THE INSTRUMENT OUT OF SERVICE. IF IT IS SAFE TO DO SO, THE LEAD OPERA TOR WILL COMPLETE AN OUT-OF-SERVICE" TAG AND MOUNT IT ON THE CONTROL PANEL. HE WILL ALSO MAKE NOTE IN THE OPERATIONS LOGBOOK TO EXPLAIN THE DETAILS OF WHAT HAS BEEN DONE AND WHY IT WAS NECESSARY. IF. IN THE LEAD OPERATOR'S OPINION, IT IS NOT SAFE TO DO SO. SUPERVISION SHOULD BE CONSULTED. \ ;
The out-of-service tag is intended to be a communications
tool for notifying other people that Priority 1 or 2 alarms
are out of service or a control valve is bypassed.. :These
tags should be affixed to the instrument on the dontirgl
panel or, if this is not possible, in another prominent
place on the control panel. These out-of-service tags will
remain on There are
the board until the situation is corrected
*-. " *
7 *i circumstances during routine operations when
some
of these alarms or valves need to be taken out of service
for short periods of time to perform, short term routine work
on the system. Some examples of this include the- fol low i (1). Pulling alarm cards at EDC I to look for a "myster^W
alarm".
(2) . Taking alarms out of service on the computer at VCM
II long enough to identify them on the CRT display.
PAGE 2 OF 4
M5 m a. CO t*
V
O
> **
H "t uol V( OSiV' WJ **
fOt
4.'
-e. tr*
ro
a
*- n
%A
-ft*. 4*
in
(3). When an operator and log book instrument man go outside to look at a shut down system valve that is sticking.
(4). When OHC analyzers are bypassed for preventive maintenance work.
Under these and other similar circumstances it would net normally be worth the effort to complete an out-of-service ~tag. For these short-term situations it will be acceptable practice for the alarm, instrument, or control valve to be taken out. of Service provided that both of the following criteria are met:
1) The lead operator is informed of the situation and gives approval.
2) The operator gives undivided attention to this problem.
If both of these cannot be met, then the out-of-service tag must be used regardless of the length of time required for the work to be done.
The out-of-service tags are not a substitute for performing maintenance. The out-of-service tags serve only to communicate the status of instruments in need of repair.
8. TAKE IMMEDIATE ACTION TO INITIATE REPAIRS ON THE OUT-OFSERVICE INSTRUMENT.
After a priority 1 or 2 alarm, instrument, or control valve has been properly taken out-of-service or bypassed, it should not be forgotten about. On day shift this may require redirecting the maintenance logbook priorities, or notifying supervision so an "Emergency" work order can be written. On the back shifts and during holidays, this may mean notifying the shift supervisor and getting shift mechanics or calling out mechanics so that the repairs can be made in a timely fashion. In either case it is strongly recommended that repairs be started as soon as practical.
Ordering "Out-of-Service " ta as. These tags are set up m our reproduction department with a form number (S9A-6) so that day shift operators can reorder these by telephone.
9. WHEN THE REPAIRS ARE SUCCESSFULLY COMPLETED AND THE ALARM, INSTRUMENT, OR CONTROL VALVE IS PUT BACK INTO SERVICE, THE LEAD OPERATOR WILL REMOVE THE OUT-OF-SERVICE TAG FROM THE BOARD, TAPE IT INTO THE LOGBOOK, AND COMPLETE THE BOTTOM SECTION OF THE OUT-OF-SERVICE TAG.
1 0. A "WEEKLY OUT-OF-SERVICE TAGGING CHECKLIST" WILL BE COMPLETED
BY EACH UNIT ON MONDAY MORNING GRAVEYARD SHIFT TO CONFIRM .
THAT.THE PANEL ALARMS AND LIGHTS ARE IN WORKING ORDER AND \ V
in THAT ALL OF THE OUT-OF-SERVICE ALARMS, INSTRUMENTATIONy ANDf
in co
CONTROL VALVES HAVE. BEEN PROPERLY TAGGED ACCORDING TO THIS"
*3- SOP. THESE CHECKLISTS WILL BE MAILED TO THE DERIVATIVES '* v
O
ENVIRONMENTAL FOREMAN EACH WEEK FOR RECORDKEEPING AND K
\
AUDITING.
as
co The objective of the weekly checklist is to routinely ake
an inventory of the out-of-service tagging which has been
done and to correct all tagging deficiencies on the sp&t.
PAGE 3 OF 4
Each individual unit will make up a detailed checklist which will be entitled "Weekly Out-of-Service Tagging Checklist",
During this weekly inventory, the audible and visual alarms should be proven to be in working order. A check of all the out-of-service tags on the panel will be made to insunj
that they all have been done correctly. Also a cross-check
in the field will be made to insure that no bypassed SDS
-automatic valve has been overlooked. All tagging
discrepancies which are found should be corrected on-'the:
spot by following step #11 below.
"i
11. IF A PROBLEM IS IDENTIFIED DURING THE WEEKLY CHECKLIST WHICH
HAS NOT BEEN PROPERLY -OUT-OF-SERVICE* TAGGED, THE v :
DEFICIENCY MUST BE CORRECTED IMMEDIATELY. RETURN f6 STEP #1
ABOVE AND FOLLOW THIS SOP TO INSURE THAT EACH ITEM IS :
PROPERLY OUT-OF-SERVICE TAGGED.
v '*
12. THESE CHECKLISTS WILL BE REVIEWED BY THE UNIT SUPERVISORS AND
AREA SUPERVISOR, INITIALLED, AND MAILED WEEKLY TO THE
DERIVATIVES ENVIRONMENTAL FOREMAN.
SL 004356
ojsrioEirriAL: