Document em9ZYd6VOR3nRGanJQDJwnN8q

572 Chapter 31 1945 Guide -usuaLto keep-the sum of the duct losses-one-third-to one-half and the loss through the other units at less than one-half of the static pressure. The remainder is then available for producing velocity. In the design of an ideal duct system, all factors should be taken into consideration and the air velocities proportioned so that the resistance will be practically equal in all ducts regardless of length. DUCT SIZES Ducts and flues for gravity circulation must be sized so that the friction loss will not exceed 50 per cent of the available aspirating effect due to the temperature and height of the column of heated air. Duct systems for mechanical circulation may be sized so as to have much higher pressure lpsses than gravity systems. .The to'tal pressure of these systems is limited to the available pressure from the fan used. The general rules to be followed in the design of a duct system are enumerated herewith: 1. The air should be conveyed as directly as possible at reasonable velocities to obtain the results desired with greatest economy of power, material and space. 2. Sharp elbows and bends should be avoided unless turning vanes are used. 3. Transformation pieces should be made as long as possible. The angle between the sides and axis of the duct should never exceed 30 deg and, where possible, 15 deg should be made the maximum. 4. Especial'care should be taken to maintain a true cross-section and not to restrict the air flow either in transformation pieces or in elbows. 5. Rectangular ducts or flues should be made as nearly square as possible. Good practice limits the ratio between the long side and the short side to 3 to 1. In no case should this ratio exceed 10 to l. 6. Wherever possible, ducts should be constructed of smooth materia) such as sheet metal. Where masonry ducts are used, proper allowance for the surface coefficient should be made. 7. The use of furred spaces, spaces between joists, etc., should be avoided unless lined with sheet metal. , Procedure for Duct Design The general procedure for designing a duct system is outlined in the several items listed herewith: 1. Study the plan of the building and draw in roughly the most convenient system of ducts, taking cognizance of the building construction, avoiding all obstructions in steel work and equipment, and at the same time maintaining a simple design. 2. Arrange the positions of duct outlets to insure the proper distribution of air. 3. Divide the.building into zones and proportion the volume of air necessary for each zone. 4. Determine the size of each outlet, based on the volume as obtained in the preceding paragraph, for the proper outlet velocity and throw. 5. Calculate the sizes of all main and branch ducts by either of the following two methods : a. Velocity Method. Arbitrarily fix the velocity in the various sections, reducing the velocity from the point of leaving the fan to the point of discharge to the room. In this case the pressure loss of each section of the duct is calculated separately and the total loss found by adding together the losses of the various sections of the continuous run. b. Friction Pressure Loss Method. Proportion the duct for equal friction pressure loss per foot of length. 6. Calculate the friction for the duct offering the greatest resistance to the flow of air, which resistance represents the static pressure which must be maintained in the fan outlet or in the plenum space to insure distribution of air in the duct system. The duct having the greatest resistance will usually be that having the.longest run, although not necessarily so. Air Duct Design 573 "Air Velocities ' The air velocities giyen in Table 3 have been found to give satisfactory results in engineering practice. Where the higher velocities are used, the ducts should be cross-braced to prevent breathing, buckling or vibration. High velocities at one point in the system offset the effect of proper design in all other parts of the system; hence the importance pf air velocities, elbow design, location of dampers, fan connections, grille and register approach connections, and similar attention to details. For industrial buildings, noise is seldom given much consideration, and niain duct velocities as high as 2800 or 3000 fpm are sometimes used but, when these velocities are used, due consideration should be given to duct design, resistance pressure, fan efficiencies and motor, horsepower. For; department stores and similar buildings, 2000 to 2200 fpm are sometimes Table 3. Recommended and Maximum Duct Velocities Designation Recommended Velocities, fpm Maximum Velocities, fpm Residences Schools. Theaters, Public Buildings Industrial Buildings Residences Schools, Theaters, Public Buildings Industrial Buildings Outside Air Intakes3 700 800 1000 ' 800 900 1200 Filters* 250 300 350 300 350 350 Heating Coils* 450 500 600 500 600 700. Air Washers Suction Connections Fan Outlets 5<fo 500 500 700 . 800 1000 1000-1600 1300-2000 1600-2400 500 900 1700 500 500 1000 1400. 1500-2200 1700-2800 Main Ducts Branch Ducts Branch Risers 700-900 1000-1300 1200-1800 800-1000 1100-1400 1300-2000 600 600-900 800-1000 700 800-1000 1000-1200 500 600-700 800 . 650 800-900 1000' "These velocities are for total face area, not the net free area. used in main ducts where noise is not objectionable and space conditions warrant it. Wherever velocities higher than those shown in Table 3 are used, it is essential that the ducts should be of heavier gages, have addi tional bracing and be carefully constructed for a minimum resistance. Where the high velocity diffusing outlets are used, the duct velocity should not be less than the throat velocity of the diffusers, as dynamic losses occur wherever velocities are stepped up or down. One recent trend in grille design is toward the use of much higher grille and branch duct velocities. Some installations have been made with velocities as higft as 1600 fpm in branches and through the net area of grilles, but many of these have proven unsatisfactory because of noise and drafts. Grille manufacturers publish selection tables which size the grilles for volume of air, temperature.differential, and distance of throw. In following these tables, maximums should be avoided and the manner in which the duct connects to the grille should be given careful consideration. Most of the selection tables are based on straight approach 'to the grille. Elbow connections to supply grilles should be provided with turning vanes to equalize the face velocity. See Chapter 30 for a discussion of grilles.