830
CHAPTER 75
1962 Guide And Data Boq^S
pump installation, or may be a self-contained domestic-water heat pump.
Various designs of self-contained domestic water heat pumps are available, and one particular arrangement is shown in Fig. 17.
Hot water heating by means of a heat pump is not yet ad visable where high water temperatures are desired. This is due to the fact that higher water outlet temperatures result in lower coefficients of performance.
For coefficients of performance of 4 or higher, the heatpump water heater may be more economical to operate than a conventional water beater.'
Although the first cost of domestic hot water heat pumps is somewhat high, they have the advantages of operating with out products of combustion, odors, soot, or chimney. A further advantage is that they may be used for cooling pur poses. With a coefficient of performance of 2Vt to 3, water temperatures of 140 to 150 F may be obtained *
REFERENCES
1R. B. Hunter: Water Distributing Systems for Buildings (National Bureau of Standards Report BMS79, p. 6). (Charts extended to flow of 030 gpm.)
* Private communication from H. E. Degler.' * T, Z. Dunn, R. N. Spear, B. E. Twin, and Don Williams (Members of Water Heating and Steam Operation Committee of A.GA.): Water heating for commercial kitchens (Air Condi tioning, Beating and Ventilating, May 1959, p. 70). Alan pub lished as a bulletin entitled Enough Hot Water--Hot Enough (American.Gas Association, 1959). * E. F. Hebrank: Investigation of the performance of auto matic storage-type gas and electric domestic water heaters (Uni versity of Illinois, Engineering Experiment Station Bulletin No. 438, 1956).
*Svend Plum: Plumbing Practice and Design (John Wiley and Sons, New York, 1943).
*P. 8pom and E. R. Ambrose: Progress report on a beat pump water heater (Healing and Ventilating, Vol. 46. February 1949, p. 78).
BIBLIOGRAPHY
H, C. Russell: Laundry, kitchen Rnt^ hospital equipment (ABHYE Transactions, Vol. 35, 1929, p. 45).
G. C. St. Laurent: Water consumption, cost and ---3 (Hotel Engineering, Vol. 1, American Hotel Association, 19n?
F. M. Dawson and A. A. Kalinske: Water-Supply the Plumbing System (National Association of Master Technical Bulletin No. 3).
F. A. Brooks: Use of Solar Energy for Heatma (Smithsonian Institution, Washington, D.C.).
1
R. B. Hunter: Methods of Estimating Loads in Phcmbun. Systems (National Bureau of Standards Report BMS65, 194^
Plumbing Manual, Report of the Subcommittee oh Phimbau, Central Housing Committee on Research, Design andCmL slruction (National Bureau of Standards Report BMS66, I94Q)
R. B. Hunter: Water-Distributing Systems for BuOda^, (National Bureau of Standards Report BMS79, 1941).
M. B. Mackay: Hot water requirements (Modem Samteuinm
Vol. 1. August 1949, p. 30).
"><u>ou,
M. A. Pond: Urban domestic water consumption (Journal of the American Water Works Association, VoL 31, No 12. iom P- 2003). .
J. C. Church: Hot water for hospitals (Heating and Venti. latmg, October 1952, p. 97).
R. Murray: How to'size and install gas water heaters cor
rectly (Air Conditioning, Heating and Ventilating, FebraarJ
1955, p. 86).
,
J. C. Church: Water supply for tall buildings (Air Conditioning, Heating and Ventilating, February 1955, p. 99).
F. M. Reiter: Service hot water design for multi-story build- ings (Air Conditioning, Heating and Ventilating, Decemter 1955, p. 79).
F. M. Reiter: Service hot water for commercial and industrial
use (Air Conditioning, Heating and Ventilating, February 1956.
n flo*
'
F. M. Reiter: Design data for service hot water (Atr Condi tioning, Heeding and Ventilating, April 1956, p. 81).
G. R. Jerus: Design of swimming pools (Air Conddiotma, Heating and Ventilating, February 1957, p. 113).
J. Nachbar: Water supply for industrial plants (Air Condi tioning, Heating and Ventilating, December 1957, p. 53).
National Plumbing Code (American Standards Association. ASA A403-1955).
Spray Type Dishwashing Machines (Standard No. '3, Na tional Sanitation Foundation, 1953).
Commercial Gas and Electrically Heated Hot Water Generat ing Equipment for Pood Service Establishments Using Disk washing Machines (Standard No. 5, National Sanitation Foun dation, 1959).
CHAPTER 76
SNOW MELTING
Design Hoofing Requirement, Hydraulic Requirement, Installation: Safety, Internal Corrosion, Slab Construction, Thermal Stresses, Control, Testing, Draining, Drifting Snow, Design Example
THE practicability of melting snow by means of heated the convection and radiation losses vary with changes in air coils has been demonstrated in a large number of instal temperature and wind speed. lations in sidewalks, roadways, ramps, and runways. In ad To determine evaporation and heat transfer from the
dition to eliminating tiie need for snow removal, other ad melted snow to the air it is necessary to know three of the
vantages gained are greater safety to pedestrians and vehicles, four climatic factors: (1) wind speed, (2) air temperature, and
and reduction of labor in removal of slush from floors.
(3) relative humidity, and (4) rate of snowfall. The fourth
Hie design of a snow-melting system must determine and factor, rate of snowfall, is necessary to determine the heat
satisfy two primary requirements: (1) the heating require-- required to warm the snow to 32 F, and to melt it
Dent, and (2) the hydraulic requirement. Each of these is
Before deriving equations to give quantitative values for
treated in this chapter. Several points regarding installation the effects of these four factors, it is necessary to consider the
practices are also discussed.
insulating effect of the snow before it is melted. As stated
DESIGN
previously, the first
fall on a dry, warm surface, and
are then wanned to 32 F
melted. During the time that
Heating Requirement
the flakes are being warmed, and before they are completely melted, they can be considered as tiny blankets or insulators.
The heating requirement for snow melting is affected by four atmospheric factors: (1) rate of snowfall, (2) air temper
The effect of this insulation been measured1 and can be of crmsidt-fahln magnitude. Since the snowflakes cover a frac
ature, (3) wind velocity, and (4) humidity. The effects of these tion of the surface area, it has been convenient to think of
factors can be evaluated by consideration of the action of the insulating effect as an area ratio. The area covered by the
snow failing on a wannedsurface.
snowflakes is the insulated area, and the uncovered area is the
The first flakes fall on a dry, warm surface, and are then uninsulated area. The term free area ratio Ar has been adopted
wanned to 32 F and melted. Tire water from the melted snow to represent the ratio of the uncovered, or free, area to the
soon forms a film over the entire area and starts to evapo total area or,
rate. The evaporation of the film is a mass transfer from the
surface to the atmosphere. In addition, there is a heat transfer
from the film to the ambient air and surfaoes.
Mass transfer due to evaporation. The rate of evaporation of the melted snow from the snow-melting slab is affected by
where
the wind speed and the vapor-pressure difference between the
At * Free area ratio.
air and the melted snow. The vapor pressure of air, however, is fixed by the relative humidity and the temperature of the air. If the slab surface temperature is fixed, then the evapora
A/ -- Free area, sq ft. A% -- Total' area, sq ft.
tion loss varies with changes in air temperature, relative humidity; and wind speed.
Heal transfer by convection and radiation from the melted
hence
0 < At <1
*now to the ambient air and surfaces. A combined film coefficient Iras been used with sufficient accuracy to determine the com
For At m 1) tiie system would have to melt the snow so
bined convection and radiation loss. This coefficient is based rapidly that the snow accumulation would be absolutely zero.
on a heat transfer from a toetted surface, such as the film of molted snow, to air. The coefficient is a function of wind BPced alone. The heat transfer, of course, is dependent upon
This is impossible from a theoretical standpoint, but for all practical purposes it is permissible to have Ar 1 as a max imum. For At K 0, the surface would be completely covered
the film coefficient and the temperature difference between with snow to a depth sufficient to completely prevent evapo
the surface and the air. Since the surface temperature is fixed,
ration and beat transfer losses. Research on the insulating