Document e5n00BRzDYLGkvZJD15E8anDG
ANSI A31.50-1976 (AWWA C150-76)
Revision of A21.50-1971 (AWWA C150-71)
AMERICAN NATIONAL STANDARD
tor the
THICKNESS DESIGN OF DUCTILE-IRON PIPE
Secretariats
AMERICAN GAS ASSOCIATION AMERICAN WATER WORKS ASSOCIATION NEW ENGLAND WATER WORKS ASSOCIATION
Revised edition approved by American National Standards Institute, Inc. Aug. 4, 1976
PUBLISHED BY
AMERICAN WATER WORKS ASSOCIATION
6666 West Quincy Avenue, Denver, Colorado 80235
American National Standard
An American National Standard implies a consensus of those substantially concerned with its scope and provisions. An American National Standard is intended as a guide to aid the manufacturer, the consumer, and the general public. The existence of an American National Standard does not in any respect preclude anyone, whether he has approved the standard or not, from manufacturing, marketing, purchasing, or using products, processes, or procedures not conforming to the standard. American National Standards are subject to periodic review, and users are cautioned to obtain the latest editions. Producers of goods made in conformity with an American National Standard are encouraged to state on their own responsibility in advertising and promotion ma terial or on tags or labels that the goods are produced in conformity with particular American National Standards.
CAUTION NOTICE. This American National Standard may be revised or with drawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five (5) years from the date of publication. Purchasers of American National Stan dards may receive current information on all standards by calling or writing the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018, ' (212) 868-1220.
Copyright 1976 by the American Water Works Assn. Printed in US
ii
t
CTD014567
Committee Personnel
Subcommittee 1, Pipe, which reviewed this standard, had the following per sonnel at that time:
Edward C. Sears, Chairman Walter Amory, Vice-Chairman
User Members
Robert S. Bryant Frank E. Dolson George F. Keenan Leonard Orlando J r. John E. Perry
Producer Members
Alfred F. Case W. D. Goode Thomas D. Holmes Harold Kennedy Jr. W. Harry Smith Sidney P. Teague
Standards Committee A21, Cast-Iron Pipe and Fittings, which reviewed and approved this standard, had the following personnel at the time of approval:
Lloyd W. Weller, Chairman Edward C. Sears, Vice-Chairman James B. Ramsey, Secretary
Organization Represented
American Gas Association American Society of Civil Engineers American Society of Mechanical Engineers American Society for Testing and Materials American Water Works Association
Cast Iron Pipe Research Association
Individual Producer Manufacturers' Standardization Society of
the Valve and Fittings Industry New England Water Works Association Naval Facilities Engineering Command Underwriters' Laboratories, Inc. Canadian Standards Association
Name of Representative
Leonard Orlando Jr. Kenneth W. Henderson James S. Vanick H. M. Cobb* Arnold M. Tinkey Lloyd W. Weller Thomas D. Holmes Harold Kennedy Jr. Edward C. Sears W. Harry Smith Alfred F. Case
Abraham Fenster Walter Amory Stanley C. Baker John E. Perry W. F. SemenchukJ
t ALilateisronnaterepresentative without vote
m
CTD014568
Table of Contents
SEC.
PACE
Foreword.................................................... vi
Standard
50-1 50-2
50-3
50-4
Scope......................................... 1 Procedure for Calculating Thick
ness Design Example forCalculating
Thickness............................. 2 Design Method........................ 3
1
Tables
50.1 Earth Loads P,, Truck Loads Pt, and Trench Loads P,.........
50.2 Design Values for Standard Lay ing Conditions.................. 8 50.3 Allowances for Casting Tolerance 50.4 Reduction Factors R for TruckLoad Calculations............ 8 0.5 Standard Thickness Classes of Ductile-Iron Pipe............. 10
6 8
SEC.
PACE
50.6 50.7 50.8 50.9 50.10 50.11 50.12 50.13 50.14
Surface-Load Factors for Single Truck on Unpaved Road.........
Diameter-Thickness Ratios for Laying Condition Type 1........
Diameter-Thickness Ratios for Laying Condition Type 2........
Diameter-Thickness Ratios for Laying Condition Type 3........
Diameter-Thickness Ratios for Laying Condition Type 4........
Diameter-Thickness Ratios for Laying Condition Type 5........
Thickness for Earth Load Plus Truck Load.................................
Thickness for Internal Pressure Rated Working Pressure and
Maximum Depth of Cover. ...
11 12 14 16 19 22 26 31 32
Figures 1. Standard Pipe Laying Conditions..
9
0 CTD014569
Foreword
This foreword is for information only and is not a part of ANSI AZ1.50 (A WWA C150).
American National Standards Com mittee A21, Cast-Iron Pipe and Fit tings, was organized in 1926 under the sponsorship of the American Gas Association, the American Society for Testing and Materials, the American Water Works Association, and the New England Water Works Associ ation. Since 1972, the co-secretariats have been A.G.A., AWWA, and NEWWA, with AWWA serving as the administrative secretariat. The present scope of Committee A21 activity is
Standardization of specifications for cast-iron and ductile-iron pressure pipe for gas, water and other liquids, and fittings for use with such pipe. These specifications to include design, dimensions, materials, coatings, lin ings, joints, accessories and methods of in spection and test.
The work of Committee A21 is con ducted by subcommittees. The di rective to Subcommittee 1--Pipe is that
The scope of the subcommittee activity shall include the periodic review of all current A21 standards for pipe, the preparation of re visions and new standards when needed, as well as other matters pertaining to pipe standards.
The first edition of A21.50, the standard for thickness design of duc tile-iron pipe, was issued in 1965 and a revision was issued in 1971. Sub committee 1 reviewed the 1971 edition and submitted a proposed revision to American National Standards Com mittee A21 in 1975.
Major Revisions
The basic design procedures are unchanged from the 1965 and 1971
editions. Certain design parameters have been changed to the following.
1. Trench load, which includes earth load and truck load, is expressed as vertical pressure in pounds per square inch. Earth loads for all pipe sizes are based on the prism load concept. Truck load is based on a single AASHTO* H-20 truck with 16 000-lb wheel load and 1.5 impact factor. Truck load is included at all depths of cover. In addition to tabu lated truck loads, equations are in cluded for complete calculation of truck loads.
2. The design ring bending stress is 48 000 psi, which provides safety factors under trench loading of at least 1.5 based on ring yield strength, and at least 2.0 based on ultimate strength of the material.
3. The design pipe deflection is 3 per cent of the outside diameter. Tests have shown that 3 per cent deflection is permissible without caus ing any damage to cement linings of ductile-iron pipe.
4. The standard laying conditions have been expanded to include five types. Types 1, 2, and 5 replace A, B, and S, respectively, in A21.50-1971. Types 3 and 4 have been added to provide a wider selection of laying conditions.
5. The design for internal pressure is based on a 2.0 safety factor. The design pressure is obtained by adding 100-psi surge allowance to the working pressure and multiplying the sum by the 2.0 safety factor. (If anticipated surge pressures are greater than 100 . .
* American Association of State Highway and Transportation Officials.
VII
CTD014570
AMERICAN NATIONAL STANDARD
psi, the maximum anticipated pres sure must be used.) The resulting design pressure is then applied to the minimum yield strength in tension of 42 000 psi.
6. The standard thickness classes have been renumbered. Class 1 be comes Class 51, Class 2 becomes Class 52, and so on. Class 50 has been added for 6-54-in. pipe and Class 51
has been expanded to include 3-12-in. pipe.
7. The tables have been modified to reflect the preceding changes. Also, a table has been added to show rated working pressure and maximum depth of cover for all the standard laying conditions and standard thickness classes.
*
VIU
CTD014571
ANSI A21.50-1976 (AWWA Cl50-76)
Revision of A21.50-1971 (AWWA 050-71)
American National Standard
for the
Thickness Design of Ductile-Iron Pipe
Sec. 50-1--Scope
This standard covers the thickness design of ductile-iron pipe complying with the requirements of ANSI A21.51 (AWWA, C151), "Ductile-Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds for Water or Other Liquids."
Section 50-2 outlines the design procedure and Sec. 50-3 gives a design example.
Section 50-4 explains the bases of design.
As opposed to using procedures in Sec. 50--2 or 50-4, the designer may reference Tables 12-14 directly.
Table 12 lists thicknesses for stan dard laying conditions and depths of cover up to 32 ft.
Table 13 lists thicknesses for 150350 psi water working pressure.
The greater thickness from Table 12 or 13 for given trench load or internal pressure should be used.
Table 14 lists working pressures and maximum depths of cover for standard laying conditions and thick ness classes.
Sec. 50-2--Procedure for Calculating Thickness
The thickness of ductile-iron pipe is determined by considering trench load and internal pressure separately.
50-2.1 Step 1--Design for trench load.
a. Determine trench load P,, Table 1 gives trench load, including earth load, P,, plus truck load Pt, for 2.5-32 ft cover.
b. Determine the standard laying condition from the descriptions in Table 2 and select the appropriate table for diameter-thickness ratios from Tables 7-11. Each table lists diameter-thickness ratios calculated for both bending stress and deflection over a range of trench loads.
c. For bending stress design, enter the column headed "Bending Stress Design" in the appropriate table of Tables 7-11 and locate the tabu lated trench load, P,, nearest to the calculated P, from paragraph 502.1.a. (If the calculated P, is half way between two tabulated values,' use the larger P, value.)
CTD014572
2 AMERICAN NATIONAL STANDARD
D Select the corresponding -- value for
thisP,. Divide the pipe's outside diameter D
D (Table 5) by the -- value to obtain
the net thickness t. d. For deflection design, enter the
column headed "Deflection Design" in the appropriate table of Tables 7-11 and locate the tabulated trench load, P,, nearest to the calculated P, from paragraph 50-2.1.a. (If the calcu lated P, is less than the minimum P, listed in the table, design for trench load is not controlled by deflection and this determination need not be com pleted.) If the calculated P, is half way between two tabulated values, use the larger P, value.
D Select the corresponding -- value for
this P,. Divide the pipe's outside diameter D
D (Table 5) by the -- value to obtain
minimum manufacturing thickness t\. Deduct 0.08-in. service allowance to obtain net thickness t.
e. Compare the net thicknesses from steps c and d and select the larger of the two. This will be the net thickness required for trench load.
50-2.2 Step 2--Design for internal pressure. Calculate the net thickness required for internal pressure using the equation for hoop stress:
t = PiD
25
in which t is net thickness in inches; Pi is the design internal pressure, which is equal to the safety factor of 2.0 times the sum of working pressure (Pw) in pounds per square inch, plus 100 psi surge allowance (P.) for water pipe. That is, P, = 2.0 (P,, + P,).
If anticipated surge pressures are greater than 100 psi, then the maxi mum anticipated pressure must be used. D is outside diameter of pipe in inches, and 5 is minimum yield strength in tension (42 000 psi).
50-2.3 Step 3--Selection of net thickness and addition of allowances.
a. Select the net thickness t from step 1 or 2, whichever thickness is larger.
b. Add the service allowance of 0.08 in. to the net thickness t. The resulting thickness is the minimum manufacturing thickness ti.
c. Add the casting tolerance from Table 3 to the minimum manufactur ing thickness h. The resulting thick ness is the total calculated thickness.
50-2.4 Step 4--Selection of stan dard thickness and class. Use the total calculated thickness from Sec. 50-2.3.c to select a standard class thickness from Table 5. Select the standard thickness nearest to the calculated thickness. When the calculated thick ness is halfway between two standard thicknesses, select the larger of the two.
In specifying and ordering pipe, use the class number listed in Table 5 for this standard thickness.
Sec. 50-3--Design Example for Calculating Thickness
Problem : Calculate the thickness for 30-in. ductile-iron pipe laid on a flatbottom trench with backfill lightly consolidated to centerline of pipe, lay ing condition Type 2, under 10 ft of cover for a working pressure of 200 psi.
50-3.1 Step 1--Design for trench load.
a. Earth load (Table 1) P, = 8.3 psi Truck load (Table 1) Pi = 0.7 psi Trench load, P, = P, + Pi = 9.0 psi
1
>
t
CTDO14573
THICKNESS DESIGN OF DUCTILE-IRON PIPE
3
b. Select Table 8 for diameterthickness ratios for laying condition
Type 2. c. Entering P, of 9.0 psi in Table
8, the bending stress design requires
-- of 128. From Table 5, diameter D
of 30-in. pipe is 32.00 in. Net thickness t for bending stress D 32.00 D ~ 128 0.25 in.
t d. Also, from Table 8, the deflec-
D tion design requires -- of 108.
n
Minimum thickness <i for deflection design D 32.00 0.30 in. D 108
!i Deduct service allowance
--0.08 in.
Net thickness t for deflection control 0.22 in
e. The larger net thickness is 0.25 in., obtained by the design for bending stress.
50-3.2 Step 2--Design for internal
pressure.
P. = 2.0 (Working pressure + 100 psi surge allowance)
(If anticipated surge pressures are
greater than 100 psi, then the actual
anticipated pressures must be used.)
Pi = 2.0 (200 + 100) = 600 psi _ PiD 600 X 32.00
1 ~ IS = 2 X 42 000
0.23 in.
Net thickness t for internal pressure is 0.23 in.
50-3.3 Step 3--Selection of net thickness and addition of allowances. The larger of the thicknesses is given by the design for trench load, Step 1, and 0.25 in. is selected.
Net thickness Service allowance
= 0.25 in. = 0.08 in.
Minimum thickness Casting tolerance
= 0.33 in. = 0.07 in.
Total calculated thickness = 0.40 in.
50-3.4 Step 4--Selection of stan dard thickness and class. The total calculated thickness of 0.40 in. is nearest to 0.39, Class 50, in Table 5. Therefore, Class 50 is selected for specifying and ordering.
Sec. 50-4--Design Method
50-4.1 The thickness of ductileiron pipe is determined by considering trench load and internal pressure separately.
Calculations are made for the thick nesses required to resist the bending stress and the deflection caused by trench load. The larger of the two is selected as the thickness required to resist trench load. Calculations are then made for the thickness required to resist the hoop stress of internal pressure.
The larger of these is selected as the net design thickness. To this net thickness is added a service allowance to obtain the minimum manufacturing thickness and a casting tolerance to obtain the total calculated thickness.
The standard thickness and the thickness class for specifying and ordering are selected from a table of standard class thicknesses.
The reverse of the preceding pro cedure is used to determine the rated working pressure and maximum depth of cover for pipe of a given thickness class.
50-4.2 Trench load, PT. Trench load is expressed as vertical pressure in pounds per square inch, and is equal to the sum of earth load P, and truck load P,.
50-4.3 Earth load, P,, Earth load is computed by Eq 4 for the weight of the unit prism of soil with a height equal to the distance from the top of the pipe to the ground surface. The unit weight of backfill soil is taken to be 120 lb/cu ft. If the designer antici-
CTD014574
4 AMERICAN NATIONAL STANDARD
pates additional loads because of frost, the design load should be in creased accordingly.
50--4.4 Truck load, Pt. The truck loads shown in Table 1 were computed by Eq 5 using the surface load factors in Table 6 and the reduction factors R from Table 4 for a single AASHTO H-20 truck on unpaved road or flexible pavement, 16 000-lb wheel load, and 1.5 impact factor. The surface load factors in Table 6 were calculated by Eq 6 for a single concentrated wheel load centered over an effective pipe length of 3 ft.
50-4.5 Design for trench load. Tables 7-11, the tables of diameterthickness ratios used to design for trench load, were computed by Eq 2 and 3. Equation 2 is based on the bending stress at the bottom of the pipe. The design bending stress / is
48 000 psi, which provides at least a 1.5 safety factor based on minimum ring yield strength and a 2.0 safety factor based on ultimate strength. Equation 3 is based on the deflection of the pipe ring section. The design deflection AX is 3 per cent of the out side diameter of the pipe, which is well below the deflection that might dam age cement linings. Design values of the trench parameters E', Kb, and Kz are given in Table 2.
Tables similar to Tables 7-11 may be compiled for laying conditions other than those shown in this stan dard by calculating the trench loads P, for a series of diameter-thickness
DD ratios, --t and 1--1 , using Eq 2 and 3 with values of E', Kb, and Kx appro priate to the bedding and backfill conditions.
Design Equations
P,D IS (1)
P. =
*(?)(?-*) Kb
K:
8E + 0.732
ii-')'
(2)
AX 8E
(?-*)P. = D \IKX
+ 0.732'
wH _ \2M _ H_ P. = 144 144 1.2
P, C-R-P-F 12D
(3) (4) (5)
["Vc JrC = -1 -- --2 arcsin 3 3r
A2 +H` + 1.5* "I A2 + H2)(H2 + 1.5*)
AH =r --!-- + _!_____ i
t\!a2 + h2 + 1.5* L -4* +H2 H2 + l.52 J
(6)
I
CTD014575
THICKNESS DESIGN OF DUCTILE-IRON PIPE
Explanation oi Symbols lor Equations
5
A = Outside radius of pipe in feet =* -- 24
C = Surface load factor (Table 6)
D = Outside diameter in inches (Table 5)
E = Modulus of elasticity (24 X 10* psi)
E' = Modulus of soil reaction in pounds per square inch.(Table 2)
F = Impact factor--1.5 / = Design bending stress--48 000 psi H = Depth of cover in feet
= Bending moment coefficient (Table 2) = Deflection coefficient (Table 2) P - Wheel load--16 000 lb
P. = Earth load in pounds per square inch
Pi = Design internal pressure in pounds per square inch = 2.0 (working pressure + 100 psi surge allowance)
P. = Truck load in pounds per square inch
P. = Trench load in pounds per square inch = P, + P,
R = Reduction factor which takes account of the fact that the part of the pipe directly
below the wheels is aided in carrying the truck load by adjacent parts of the
pipe that receive little or no load from the wheels (Table 4)
5 = Minimum yield strength in tension--42 000 psi
t = Net thickness in inches = Minimum thickness in inches (l + 0.08)
to = Soil weight--120 pounds per cubic foot
AX = Design deflection in inches
)= 0.03
Note : In Eq 6, angles are in radians.
6
Depth of Cover ft
2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32
Depth of Cover ft
2.5 3. 4 5 6 7 8 9 10 12 14 16 20 24 28 32
AMERICAN NATIONAL STANDARD
TABLE 50.1
Earth Loads P,, Truck Loads Ptl and Trench Loads P,--psi
Pt
2.1 2.5 3.3 4.2 5.0 5.8 6.7 7.5 8.3 10.0 11.7 13.3 16.7 20.0 23.3 26.7
3-in. Pipe
p, P.
9.9 12.0 7.4 9.9 4.4 7.7 3.0 7.2 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.6 10.6 0.4 12.1 0.3 13.6 0.2 16.9 0.2 20.2 0.1 23.4 0.1 26.8
4-in. Pipe
Pi P,
9.9 12.0 7.4 9.9 4.5 7.8 3.0 7.2 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.6 10.6 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
6-in. Pipe
Pi P,
9.9 12.0 7.3 9.8 4.4 7.7 3.0 7.2 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.6 10.6 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
8-in. Pipe
P; P,
9.8 11.9 7.3 9.8 4.4 7.7 3.0 7.2 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.6 10.6 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
P#
2.1 2.5 3.3 4.2 5.0 5.8 6.7 7.5 8.3 10.0 11.7 13.3 16.7 20.0 23.3 26.7
10-in. Pipe
Pi P.
9.7 11.8 7.2 9.7 4.4 7.7 2.9 7.1 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
12-in. Pipe
pi P,
9.6 11.7 7.2 9.7 4.4 7.7 2.9 7.1 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
14-in. Pipe
Pi P.
8.7 10.8 6.6 9.1 44 7.7 2.9 7.1 2.1 7.1 1.6 7.4 1.2 7.9 1.0 8.5 0.8 9.1 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
16-in. Pipe
P P,
8.2 10.3 6.2 8.7 4.1 7.4 2.8 7.0 2.0 7.0 1.5 7.3 1.2 7.9 1.0 8.5 0.8 9.1 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
1
>
ctO0'4511
THICKNESS DESIGN OF DUCTILE-IRON PIPE
7
Depth of Cover ft
2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32
2.1 2.5 3.3 4.2 5.0 5.8 6.7 7.5 8.3 10.0 11.7 13.3 16.7 20.0 23.3 26.7
Depth of Cover ft
2.5 3 4' 5 6 7 8 9 10 12 14 16 20 24 28 32
2.1 2.5 3.3 4.2 5.0 5.8 6.7 7.5 8.3 10.0 11.7 13.3 16.7 20.0 23.3 26.7
TABLE 50.1--(cont.)
18-in. Pipe
20-in. Pipe
24-in. Pipe
Pi P. Pi P. Pi P.
7.8 9.9 7.5
9.6 7.1
9.2
5.9 8.4 5.7 8.2 5.4 7.9
3.9 7.2 3.9 7.2 3.6 6.9
2.6 6.8 2.6 6.8 2.4 6.6
1.9 6.9 1.9 6.9 1.7 6.7
1.4 7.2 1.4 7.2 1.3 7.1
1.2 7.9 1.1 7.8 1.1 7.8
1.0 8.5 0.9 8.4 0.9 8.4
0.8 9.1 0.7 9.0 0.7 9.0
0.5 10.5 0.5 10.5 0.5 10.5
0.4 12.1 0.4 12.1 0.4 12.1
0.3 13.6 0.3 13.6 0.3 13.6
0.2 16.9 0.2 16.9 0.2 16.9
0.1 20.1 0.1 20.1 0.1 20.1
0.1 23.4 0.1 23.4 0.1 23.4
0.1 26.8 0.1 26.8 0.1 26.8
36*in. Pipe
42-in. Pipe
48-in. Pipe
Pi P. Pi P. Pi P,
6.2 8.3 5.8 7.9 5.4 7.5
4.9 7.4 4.6 7.1 4.4 6.9
3.4 6.7 3.3 6.6 3.1 6.4
2.3 6.5 2.3 6.5 2.2 6.4
1.7 6.7 1.7 6.7 1.6 6.6
1.3 7.1 1.3 7.1 1.2 7.0
l.l 7.8 1.0 7.7 1.0 7.7
0.8 8.3 0.8 8.3 0.8 8.3
0.7 9.0 0.7 9.0 0.7 9.0
0.5 10.5 0.5 10.5 0.5 10.5
0.4 12.1 0.4 12.1 0.4 12.1
0.3
13.6
0.3
13.6
0.3
13.6
0.2 16.9 0.2 16.9 0.2 16.9
0.1 20.1 0.1 20.1 0.1 20.1
0.1
23.4
0.1
23.4
0.1
23.4
0.1
26.8
0.1
26.8
0.1
26.8
30-in. Pipe
Pi p.
6.7 8.8 5.2 7.7 3.5 6.8 2.4 6.6 1.7 6.7 1.3 7.1 1.1 7.8 0.9 8.4 0.7 9.0 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
54-in. Pipe
Pi P.
5.0 7.1 4.1 6.6 3.0 6.3 2.1 6.3 1.6 6.6 1.2 7.0 1.0 7.7 0.8 8.3 0.7 9.0 0.5 10.5 0.4 12.1 0.3 13.6 0.2 16.9 0.1 20.1 0.1 23.4 0.1 26.8
CTD0A457S
8 AMERICAN NATIONAL STANDARD
TABLE 50.2
Design Values for Standard Laying Conditions
Laying Condition*
Description
Type It Type 2 Type 3 Type 4
Type 5
Flat-bottom trench.{ Loose backfill. Flat-bottom trench. Backfill lightly con
solidated to centerline of pipe. Pipe bedded in 4-in.-minimum loose soil.}
Backfill lightly consolidated to top of pipe. Pipe bedded in sand, gravel, or crushed
stone to depth of } pipe diameter, 4-in. minimum. Backfill compacted to top of pipe. (Approx. 80 per cent Standard Proctor, AASHTO T-99) Pipe bedded to its centerline in compacted granular material, 4-in. minimum under pipe. Compacted granular or select material to top of pipe. (Approx. 90 per cent Standard Proctor, AASHTO T-99)**
Bedding Angle deg
Kt
K.
150 30 0.235 0.108 300 45 0.210 0.105
400 60 0.189 0.103
500 90 0.157 0.096
700 150 0.128 0.085
' oec r#. i. t For pipe 30 in. and larger, consideration should be given to the use of laying conditions other than Type 1.
t Flat-bottom is defined as "undisturbed earth.'' ( Loose soil or select material is defined as "native soil excavated from the trench, free of rocks, foreign material, and frozen earth." ** AASHTO T-99. "Moisture Density Relations of Soils Using a 5.5 lb (2.5 kg) Rammer 12-in. (305-mm) Drop."
TABLE 50.3
Allowances for Casting Tolerance
Size in.
3-8 10-12 14-42
48 54
Casting Tolerance in.
0.05 0.06 0.07 0.08 0.09
TABLE 50.4
Reduction Factors R for Truck Load Calculations
Depth of Cover--/*
Size in.
<4
4-7 8-10 >10
Reduction Factor
3-12 14 16 18 20 24-30 36-54
1.00 0.92 0.88 0.85 0.83 0.81 0.80
1.00 1.00 0.95 0.90 0.90 0.85 0.85
1.00 1.00 1.00 1.00 0.95 0.95 0.90
1.00 1.00 1.00 1.00 1.00 1.00 1.00
CTD014579
THICKNESS DESIGN OF DUCTILE-IRON PIPE
9
Figure 1. Standard Pipe Laying Conditions
See Table 2
CTD014580
10 AMERICAN NATIONAL STANDARD
TABLE 50.5
Standard Thickness Classes of Ductile-Iron Pipe
Size Outside in. Diameter--in.
SO
3 3.96 _
4
4.80
--
6
6.90
0.25
8
9.05
0.27
10
11.10
0.29
12
13.20
0.31
14
15.30
0.33
16 17.40 0.34
18
19.50
0.35
20
21.60
0.36
24
25.80
0.38
30 32.00 0.39
36
38.30
0.43
42
44.50
0.47
48
50.80
0.51
54
57.10
0.57
SI
0.25 0.26 0.28 0.30 0.32 0.34 0.36 0.37 0.38 0.39 0.41 0.43 0.48 0.53 0.58 0.65
Thickness Class
52 55 54
Thickness--in.
0.28 0.29 0.31 0.33 0.35 0.37 0.39 0.40 0.41 0.42 0.44 0.47 0.53 0.59 0.65 0.73
0.31 0.32 0.34 0.36 0.38 0.40 0.42 0.43 0.44 0.45 0.47 0.51 0.58 0.65 0.72 0.81
0.34 0.35 0.37 0.39 0.41 0.43 0.45 0.46 0.47 0.48 0.50 0.55 0.63 0.71 0.79 0.89
55
0.37 0.38 0.40 0.42 0.44 0.46 0.48 0.49 0.50 0.51 0.53 0.59 0.68 0.77 0.86 0.97
56
0.40 0.41 0.43 0.45 0.47 0.49 0.51 0.52 0.53 0.54 0.56 0.63 0.73 0.83 0.93 1.05
CTD014581
THICKNESS DESIGN OF DUCTILE-IRON PIPE
11
TABLE 50.6
Surface Load Factors for Single Truck on Unpaved Road
Pipe Size--
Depth of
Cover
3
4
6
8
10 12 14 16
n
Surface Load Factor--C
2.S 0.0196 0.0238 0.0340 0.0443 0.0538 0.0634 0.0726 0.0814 3 0.0146 0.0177 0.0253 0.0330 0.0402 0.0475 0.0546 0.0614 4 0.0088 0.0107 0.0153 0.0201 0.0245 0.0290 0.0335 0.0379
5 0.0059 0.0071 0.0102 0.0134 0.0163 0.0194 0.0224 0.0254 6 0.0042 0.0050 0.0072 0.0095 0.0116 0.0138 0.0159 0.0181 7 0.0031 0.0038 0.0054 0.0071 0.0087 0.0103 0.0119 0.0135 8 0.0024 0.0029 0.0042 0.0055 0.0067 0.0079 0.0092 0.0104 9 0.0019 0.0023 0.0033 0.0043 0.0053 0.0063 0.0073 0.0083 10 0.0015 0.0019 0.0027 0.0035 0.0043 0.0051 0.0060 0.0068 12 0.0011 0.0013 0.0019 0.0025 0.0030 0.0036 0.0042 0.0047 14 0.0008 0.0010 0.0014 0.0018 0.0022 0.0027 0.0031 0.0035 16 0.0006 0.0007 0.0011 0.0014 0.0017 0.0020 0.0024 0.0027 20 0.0004 0.0005 0.0007 0.0009 0.0011 0.0013 0.0015 0.0017
24 0.0003 0.0003 0.0005 0.0006 0.0008 0.0009 0.0011 0.0012 28 0.0002 0.0002 0.0003 0.0005 0.0006 0.0007 0.0008 0.0009 32 0.0002 0.0002 0.0003 0.0003 0.0004 0.0005 0.0006 0.0007
Pipe Size--in.
Depth of Cover 18 20 24 30 36 42 48 54 ft
Surface Load Factor--C
2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32
0.0899 0.0681 0.0422 0.0283 0.0202 0.0151 0.0117 0.0093 0.0076 0.0053 0.0039 0.0030 0.0019 0.0013 0.0010 0.0008
0.0980 0.0746 0.0464 0.0312 0.0223 0.0167 0.0129 0.0103 0.0084 0.0059 0.0043 0.0033 0.0021 0.0015 0.0011 0.0008
0.1130 0.0867 0.0545 0.0369 0.0264 0.0198 0.0154 0.0122 0.0100 0.0070 0.0052 0.0040 0.0025 0.0018 0.0013 0.0010
0.1321 0.1028 0.0657 0.0449 0.0323 0.0243 0.0189 0.0151 0.0123 0.0086 0.0064 0.0049 0.0032 0.0022 0.0016 0.0012
0.1479 0.1169 0.0761 0.0525 0.0381 0.0288 0.0224 0.0179 0.0147 0.0103 0.0076 0.0059 0.0038 0.0026 0.0019 0.0015
0.1604 0.1286 0.0853 0.0595 0.0435 0.0329 0.0258 0.0206 0.0169 0.0119 0.0088 0.0068 0.0044 0.0030 0.0022 0.0017
0.1705 0.1384 0.0936 0.0661 0.0486 0.0370 0.0290 0.0233 0.0191 0.0135 0.0100 0.0077 0.0050 0.0035 0.0026 0.0020
0.1784 0.1466 0.1008 0.0720 0.0534 0.0409 0.0322 0.0259 0.0213 0.0151 0.0112 0.0087 0.0056 0.0039 0.0029 0.0022
CTD0U582
12 AMERICAN NATIONAL STANDARD
TABLE 50.7
Diameter-Thickness Ratios for Laying Condition Type I*
Trench Load (P)--psi
Trench Load (P.)--Psi
Bending Stress Design
4.40 4.43 4.46 4.S0 4.54
4.57 4.61 4.64 4.68 4.72
4.76 4.80 4.84 4.88 4.92
4.96 5.00 5.04 5.08 5.13
5.17 5.21 5.26 5.30 ' 5.35
5.40 5.45 5.49 5.54 5.59
5.65 5.70 5.75 5.80 5.86
5.91 5.97 6.03 6.09 6.15
6.21 6.27
Deflection Design
3.46 3.48 3.50 3.51 3.53
3.55 3.57 3.59 3.61 3.63
3.65 3.67 3.69 3.71 3.74
3.76 3.78 3.81 3.83 3.86
3.89 3.91 3.94 3.97 4.00
4.03 4.06 4.09 4.13 4.16
4.20 4.23 4.27 4.31 4.35
4.39 4.43 4.47 4.52 4.56
4.61 4.66
Dt D ror 77
170 169 168 167 166
165 164 163 162 161
160 159 158 157 156
155 154 153 152 151
150 149 148 147 146
145 144 143 142 141
140 139 138 137 136
135 134 133 132 131
130 129
Bending Stress Design
6.33 6.40 6.46
6.53 6.60 6.67 6.74 6.82
6.89 6.97 7.05 7.13 7.21
7.29 7.38 7.47 7.56 7.65
7.75 7.85 7.95 8.05 8.16
8 27 8.38 8.49 8.61 8.74
8.86 8.99 9.13 9.27 9.41
9.56 9.71 9.87 10.03 10.20
10.37 10.55 10.74 10.93 11.13
Deflection Design
4.71 4.76 4.82
4 87 4.93 4.99 5.05 5.11
5.18 5.25 5.32 5.39 5.46
5.54 5.62 5.71 5.79 5.88
5 97 6.07 6.17 6.27 6.38
6.49 6.61 6.73 6.86 6.99
7.12 7.26 7.41 7.57 7.73
7.89 8.07 8.25 8.44 8.64
8.85 9.06 9.29 9.53 9.78
>
Dt 0 t or ti
128 127 126
125 124 123 122 121
120 119 118 117 116
115 114 113
*112
111
110 109 108 107 106
105
104 103 102 101
100 99 98 97 96
95 94 93 92 91
90 89 88
87 i
86
CTD014583
THICKNESS DESIGN OF DUCTILE-IRON PIPE
13
TABLE 50.7--(cont.)
Trench Load (f\)--psi
Trench Load (Pc)--psi
Bending Stress Design
11.34 11.55 11.78 12.01 12.25
12.50 12.76 13.03 13.31 13.60
13.91 14.23 14.56 14.91 15.27
15.65 16.05 16.46 16.89 17.35
17.83 18.33 18.85 19.40 19.98
20.59 21.23
Deflection Design
10.04 10.31 10.60 10.90 11.22
11.56 11.91 12.28 12.67 13.08
13.51 13.97 14.45 14.96 15.50
16.07 16.68 17.32 18.00 18.73
19.50 20.32 21.19 22.12 23.12
24.18 25.32
Df D i r /.
85 84 83 82 81
80 79 78 77 76
75 74 73 72 71
70 69 68 67 66
65 64 63 62 61
60 59
Bending Stress Design
21.91 22.63 23.38
24.18 25.02 25.92 26.86 27.87
28.94 30.07 31.28 32.57 33.95
35.42 37.00 38.69 40.50 42.46
44.56 46.84 49.30 51.96 54.86
58.02 61.46 65.23 69.36 73.92
Deflection Design
26.54 27.85 29.26
30.77 32.39 34.15 36.05 38.10
40.32 42.73 45.35 48.20 51.31
54.72 58.44 62.53 67.03 71.99
77.47 83.54 90.28 97.80 106.20
115.62 126.21 138.18 151.73 167.15
Df D ior h
58 57 56
55 54 53 52 51
50 49 48 47 46
45 44 43 42 41
40 39 38 37 36
35 34 33 32 31
E` = ISO; Ki = 0.235; K. - 0.108. t The -- for the tabulated P nearest to the calculated P, is selected; when the calculated P, is halfway between
two tabulated values, the smaller y should be used.
CTD014584
14 AMERICAN NATIONAL STANDARD
TABLE 50.8
Diameter-Thickness Ratios for Laying Condition Type 2*
Trench Load (P)--psi
Trench Load (P*)--psi
Bending Stress Design
6.29 6.34 6.39 6.44 6.50
6.55 6.60 6.66 6.71 6.77
6.82 6.88 6.94 6.99 7.05
7.11 7.17 7.23 7.29 7.35
7.42 7.48 7.54 7.61 7.67
7.74 7.80 7.87 7.94 8.01
8.08 8.15 8.22 8.29 8.37
8.44 8.52 8.59 8.67 8.75
8.83 8.91
Deflection Design
6.18 6.19 6.21 6.23 6.25
6.26 6.28 6.30 6.32 6.34
6.37 6.39 6.41 6.43 6.46
6.48 6.50 6.53 6.56 6.58
6.61 6.64 6,67 6.70 6.73
6.76 6.79 6.83 6.86 6.89
6.93 6.97 7.01 7.05 7.09
7.13 7.17 7.22 7.26 7.31
7.36 7.41
Dt D t or i,
170 169 168 167 166
165 164 163 162 161
160 159 . 158 157 156
155 154 153 152 151
150 149 148 147 146
145 144 143 142 141
140 139 138 137 136
135 134 133 132 131
130 129
Bending Stress Design
8.99 9.07 9.16
9.25 9.33 9.42 9.51 9.60
9.70 9.79 9.89 9.99 10.09
10.19 10.29 10.40 10.51 10.62
10.73 10.84 10.96 11.08 11.21
11.33 11.46 11.59 11.73 11.87
12.01 12.16 12.31 12.46 12.62
12.79 12.96 13.13 13.31 13.49
13.68 13.88 14.08 14.30 14.51
Deflection Design
7.46 7.51 7.57
7.63 7.69 7.75 7.81 7.87
7.94 8.01 8.08 8.16 8.23
8.31 8.40 8.48 8.57 8.66
8.76 8.86 8.96 9.07 9.18
9.29 9.41 9.54 9.67 9.80
9.94 10.09 10.24 10.40 10.56
10.73 10.91 11.10 11.29 11.50
11.71 11.94 12.17 12.42 12.67
t
I
Dt D t or7,
128 127 126
125 124 123 122 121
120 119 118 117 116
115 114 113 112
111 t
110 109 108 107 106
I105
104 103 102 101
100 99 98 97 96
95 94 93 92 91
90 89
188
87 86
CTD014585
THICKNESS DESIGN OF DUCTILE-IRON PIPE
15
TABLE 50.8-- (cont.)
Trench Load (P)--psi
Trench Load (P*)--
Bending Stress Design
14.74 14.97 15.21 15.46 15.72
15.99 16.28 16.57 16.87 17.19
17.52 17.86 18.22 18.59 18.98
19.39 19.82 20.27 20.73 21.23
21.74 22.28 22.85 23.45 24.97
24.74 25.43 26.17
Deflection Design
12.94 13.22 13.52 13.83 14.16
14.50 14.86 15.24 15.64 16.06
16.51 16.98 17.48 18.00 18.56
19.14 19.77 20.43 21.13 21.87
22.67 23.51 24.41 25.37 26.39
27.49 28.66 29.91
Dt D 1 r ii
85 84 83 82 81
80 79 78 77 76
75 74 73 72 71
70 69 68 67 66
65 64 63 62 61
60 59 58
Bending Stress Design
26.95 27.77
28.64 29.56 30.53 31.57 32.67
33.84 35.08 36.41 37.83 39.34
40.96 42.70 44.57 46.57 48.73
51.06 53.57 56.30 59.25 62.46
65.96 69.79 73.98 78.57 83.64
Deflection Design
31.26 32.71
34.26 35.93 37.74 39.69 41.80
44.09 46.56 49.26 52.19 55.40
58.89 62,73 66.93 71.56 76.66
82.29 88.54 95.48 103.21 111.85
121.54 132.44 144.74 158.68 174.54
Df D T or 7i
57 56
55 54 53 52 51
50 49 48 47 46
45 44 43 42 41
40 39 38 37 36
35 34 33 32 31
* ' 300; K6 - 0.210; Km - 0.105. t The for the tabulated P. nearest to the calculated P is selected; when the calculated P* is.halfway between two tabulated values, the smaller ^ should be used.
CTD014586
16 AMERICAN NATIONAL STANDARD
TABLE 50.9
Diameter-Thickness Ratios for Laying Condition Type 3*
Trench Load (P)--psi
Trench Load (P)--psi
Bending Stress Design
3.25 3.29 3.33 3.37 3.41
3.45 3.49 3.54 3.58 3.63
3.67 3.72 3.76 3.81 3.86
3.91 3.96 4.01 4.06 4.11
4.17 4.22 4.28 4.33 4.39
4.45 4.51 4.57 4.63 4.69
4.76 4.82 4.89 4.96 5.03
5.10 5.17 5.24 5.31 5.39
5.47 5.54
Deflection Design
7.26 7.27 7.27 7.27 7.28
7.28 7.28 7.29 7.29 7.30
7.30 7.30 7.31 7.31 7.32
7.32 7.33 7.33 7.34 7.34
7.35 7.35 7.36 7.36 7.37
7.38 7.38 7.39 7.39 7.40
7.41 7.42 7.42 7.43 7.44
7.45 7.46 7.47 7.48 7.48
7.49 7.51
Dt D < or7,
310 308 306 304 302
300 298 296 294 292
290 288 286 284 282
280 278 276 274 272
270 268 266 264 262
260 258 256 254 252
250 248 246 244 242
240 238 236 234 232
230 228
Bending Stress Design
5.62 5.70 5.79
5.87 5.96 6.04 6.13 6.22
6.32 6.41 6.51 6.60 6.70
6.80 6.91 7.01 7.12 7.22
7.33 7.45 7.56 7.68 7.80
7.92 8.04 8.16 8.29 8.42
8.55 8.62 8.69 8.75 8.82
8.89 8.96 9.03 9.10 9.17
9.25 9.32 9.39 9.47 9.54
Deflection Design
7.52 7.53 7.54
7.55 7.56 7.58 7.59 7.60
7.62 7.63 7.65 7.66 7.68
7.70 7.72 7.74 7.76 7.78
7.80 7.82 7.84 7.87 7.89
7.92 7.95 7.98 8.01 8.04
8.07 8.09 8.11 8.13 8.14
8.16 8.18 8.20 8.22 8.24
8.27 8.29 8.31 8.33 8.36
Dt D < or<.
226 224 222
220 218 216 214 212
210 208 206 204 202
200 198 196 194 192
190 188 186 184 182
180 178 176 174 172
170 169 168 167 166
165 164 163 162 161
160 159 158 157 156
r
t
CTD014587
THICKNESS DESIGN OF DUCTILE-IRON PIPE
TABLE 50.9--(cont.)
Trench Load (P)--psi
Trench Load (?)--psi
Bending Stress Design
9.62 9.69 9.77 9.85 9.92
10.00 10.08 10.16 10.24 10.33
10.41 10.49 10.58 10.66 10.75
10.83 10.92 11.01 11.10 11.19
11.28 11.37 11 46 11.56 , 11.65
11.75 11.84 11.94 12.04 12.14
12.25 12.35 12.45 12.56 12.67
12.78 12.89 13.00 13.11 13.23
13.34 13.46 13.58
Deflection Design
8.38 8.41 8.43 8.46 8.49
8.52 8.54 8.57 8,60 864
8.67 8.70 8.73 8.77 8.81
8.84 8.88 8.92 8.96 9.00
9.04 9.09 9.13 9.18 9.23
9.28 9.33 9.38 9.44 9.49
9.55 9.61 9.67 9.74 9.80
9.87 9.94 10.02 10.09 10.17
10.25 10,34 10.42
Df D T orT,
155 154 153 152 151
150 149 148 147 146
145 144 143 142 141
140 139 138 137 136
135 134 133 132 131
130 129 128 127 126
125 124 123 122 121
120 119 118 117 116
115 114 113
Bending Stress Design
13.71 13.83
13.96 14.09 14.22 14.36 14.50
14.64 14.78 14.93 15.08 15.23
15.39 15.55 15.71 15.88 16.06
16.23 16.42 16.61 16.80 17.00
17.21 17.42 17.64 17.86 18.10
18.34 18.59 18.85 19.12 19.40
19.68 19.99 20.30 20.62 20.96
21.31 21.68 22.07 22.47 22.88
Deflection Design
10.51 10.61
10.71 10.81 10.91 11.02 11.13
11.25 11.37 11.50 11.63 11.77
11.91 12.06 12.21 12.37 12.54
12.72 12.90 13.09 13.29 13.50
13.72 13.95 14.18 14.43 14.70
14.97 15.26 15.56 15.88 16.21
16.56 16.93 17.31 17.72 18.15
18.61 19.09 19.59 20.13 20.69
17
Df D ror 7,
112 111
110 109 108 107 106
105 104 103 102 101
100 99 98 97 96
95 94 93 92 91
90 89 88 87 86
85 84 83 82 81
80 79 78 77 76
75 74 73 72 71
CTD014588
18 AMERICAN NATIONAL STANDARD
TABLE 50.9--(cont.)
Trench Load (P*)--Pit
Trench Load (P.)--pit
Bending Stress Design
23.32 23.78 24.26 24.76 25.29
25.85 26.43 27.04 27.68 28.36
29.08 29.83 30.63 31.47 32.36
33.31 34.30 35.37 36.49 37.69
Deflection Design
21.29 21.93 22.60 23.32 24.08
24.88 25.74 26.66 27.64 28.68
29.80 30.99 32.27 33.64 35.12
36.70 38.41 40.25 42.24 44.39
Df D T or 7i
70 69 68 67 66
65 64 63 62 61
60 59 58 57 ' 56
55 54 53 52 51
Bending Stress Design
38.97 40.33 41.78 43.33 44.98
46.76 48.66 50.71 52.91 55.28
57.84 60.61 63.61 66.86 70.40
74.27 78.49 83.11 88.19 93.79
Deflection Design
46.72 49.25 51.99 54.98 58.25
61.81 65.72 70.01 74.72 79.92
85.67 92.04 99.11 106.99 115.80
125.67 136.78 149.32 163.54 179.71
Df D r orT,
50 49 48 47 46
45 44 43 42 41
40 39 38 37 36
35 34 33 32 31
* ' - 400; Kt - 0.189; Km - 0.103. t The j for the tabulated P nearest to the calculated P* is selected; when the calculated P* is halfway between
two tabulated values, the smaller y should be used.
CTD014589
THICKNESS DESIGN OF DUCTILE-IRON PIPE
TABLE 50.10
Diameter-Thickness Ratios for Laying Condition Type 4*
Trench Load (P*)--Psi
Trench Load (P*)--Psi
-IS O
Bending Stress Design
5.93 6.00 6.07 6.14 6.21
6.29 6.36 6.43 6.51 6.59
6.67 6.74 6. S3 6.91 6.99
7.08 7.16 7.25 7.34 7.43
7.52 7.61 7.71 7.80 7.90
8.00 8.10 8.20 8.31 8.41
8.52 8.63 8.74 8.85 8.97
9.08 9.20 9.32 9.44 9.57
9.69 9.82
Deflection Design
9.70 9.70 9.71 9.71 9.71
9.72 9.72 9.73 9.73 9.73
9.74 9.74 9.75 9.75 9.76
9.76 9.77 9.77 9.78 9.78
9.79 9.79 9.80 9.81 9.81
9.82 9.83 9.83 9.84 9.85
9.86 9.86 9.87 9.88 9.89
9.90 9.91 9.92 9.93 9.94
9.95 9.96
310 308 306 304 302
300 298 296 294 292
290 288286 284 282
280 278 276 274 272
270 268 266 264 262
260 258 256 254 252
250 248 246 244 242
240 238 236 234 232
230 228
Bending Stress Design
9.95 10.08 10.21
10.35 10.49 10.62 10.77 10.91
11.05 11.20 11.35 11.50 11.66
11.81 11.97 12.13 12.29 12.45
12.62 12.79 12.96 13.13 13.30
13.48 13.66 13.84 14.02 14.20
14.39 14.48 14.57 14.67 14.76
14.86 14.96 15.05 15.15 15.25
15.34 15.44 15.54 15.64 15.74
Deflection Design
9.97 9.98 9.99
10.01 10.02 10.03 10.05 10.06
10.08 10.09 10.11 10.13 10.15
10.17 10.19 10.21 10.23 10.25
10.27 10.30 10.32 10.35 10.37
10.40 10.43 10.46 10.50 10.53
10.57 10.59 10.60 10.62 10.64
10.66 10.69 10.71 10.73 10.75
10.78 10.80 10.82 10.85 10.87
19
Df D T0T 71
226 224 222
220 218 216 214 212
210 208 206 204 202
200 198 196 194 192
190 188 186 184 182
180 178 176 174 172
170 169 168 167 166
165 164 163 162 161
160 159 158 157 156
CTD014590
20 AMERICAN NATIONAL STANDARD
TABLE 50.10--(cont.)
Trench Load (f\)--Psi
Trench Load (.P)--psi
Bending Stress Design
15.84 15.94 16.04 16.14 16.24
16.34 16.45 16.55 16.65 16.76
16.86 16.96 17.07 17.18 17.28
17.39 17.50 17.60 17.71 17.82
17.93 18.04 18.15 18.26 18.37
18.49 18.60 18.72 18.83 18.95
19.06 19.18 19.30 19.42 19.54
19.66 19.78 19.91 20.04 20.16
20.29 20.42 20.55
Deflection Design
10.90 10.93 10.96 10.98 11.01
11.04 11.07 11.11 11.14 11.17
11.21 11.24 11.28 11.31 11.35
11.39 11.43 11.48 11.52 11.56
11.61 11.66 11.71 11.76 11.81
11.86 11.92 11.97 12.03 12.09
12.15 12.22 12.28 12.35 12.42
12.50 12.57 12.65 12.73 12.82
12.91 13.00 13.09
Df D t r h
155 154 153 152 151
150 149 148 147 146
145 144 143 142 141
' 140 139 138 137 136
135 134 133 132 131
130 129 128 127 126
125 124 123 122 121
120 119 118 117 116
115 114 113
Bending Stress Design
20.69 20.82
20.96 21.10 21.24 21.39 21.54
21.69 21.84 22.00 22.16 22.32
22.49 22.66 22.83 23.01 23.20
23.38 23.58 23.78 23.99 24.20
24.42 24.64 24.88 25.12 25.37
25.63 25.90 26.18 26.47 26.77
27.09 27.42 27.76 28.11 28.49
28.87 29.28 29.70 30.15 30.62
Deflection Design
13.19 13.29
13.39 13.50 13.61 13.73 13.85
13.98 14.11 14.24 14.38 14.53
14.68 14.84 15.01 15.18 15.36
15.55 15.75 15.95 16.17 16.39
16.62 16.87 17.12 17.39 17.67
17.97 18.28 18.60 18.94 19.30
19.67 20.07 20.48 20.92 21.38
21.87 22.38 22.93 23.50 24.11
Dt D t 0r ti
112 111
110 109 108 107 106
105 104 103 102 101
100 99 98 97 96
95 94 93 92 91
90 89 88 87 86
85 84 83 82 81
80 79 78 77 76
75 74 73 72 71
T
)
thickness design of ductile-iron pipe
21
TABLE 50.10-- (cont.)
Trench Load (P)--Psi
Trench Load (P*)--Psi
Design
31.11 31.62 32.16 32.72 33.32
33.95 34.61 35.30 36.04 36.81
37.63 38.50 39.42 40.39 41.42
42.51 43.67 44.91 46.22 47.62
Deflection Design
24.75 25.43 26.16 26.92 27.74
28.60 29.53 30.51 31.56 32.68
33.88 35.16 36.53 38.00 39.58
41.28 43.12 45.09 47.22 49.53
md t r /,
70 69 68 67 66
65 64 63 62 61
60 59 58 57 56
55 54 53 52 51
Bending Stress Design
49.11 50.70 52.41 54.23 56.18
58.27 60.52 62.93 65.54 68.35
71.39 74.67 78.24 82.11 86.33
90.93 95.97 101.49 107.56 114.25
Deflection Design
52.03 54.74 57.69 60.90 64.40
68.23 72.42 77.02 82.08 87.66
93.82 100.65 108.24 116.70 126.15
136.74 148.66 162.12 177.37 194.72
Df D < or(,
50 49 48 47 46
45 44 43 42 41
40 39 38 37 36
35 34 33 32 31
*' - 500; Kb 0.157; Km - 0.096. f The ^ for the tabulated P nearest to the calculated P, is selected; when the calculated P* is halfway between
two tabulated values, the smaller -- should be used.
QTD0U592
22 AMERICAN NATIONAL STANDARD
TABLE 50.11
Diameter-Thickness Ratios for Laying Condition Type 5*
Trench Load (/*)--Psi
Trench Load (Pt)--psi
Bending Stress Design
3.06 3.10 3.1S 3.20 3.25
3.30 3.35 3.40 3.46 3.51
3.57 3.63 3.68 3.75 3.81
3.87 3.94 4.00 4.07 4.14
4.21 4.29 4.36 4.44 4.52
4.60 4.69 4.77 4.86 4.95
5.05 5.14 5.24 5.35 5.45
5.56 5.67 5.78 5.90 6.02
6.15 6.28
Deflection Design
15.09 15.09 15.09 15.09 15.09
15.09 15.09 15.09 15.09 15.09
15.10 15.10 15.10 15.10 15.10
15.10 15.10 15.10 15.10 15.10
15.10 15.10 15.10 15.11 15.11
15.11 15.11 15.11 15.11 15.11
15.11 15.11 15.12 15.12 15.12
15.12 15.12 15.12 15.13 15.13
15.13 15.13
Dt D i 011.
660 655 650 645 640
635 630 625 620 615
610 605 600 595 590
585 580 575 570 565
560 555 550 545 540
535 530 525 520 515
510 505 500 495 490
485 480 475 470 465
460 455
Bending Stress Design
6.41 6.54 6.68
6.83 6.98 7.13 7.29 7.46
7.63 7.80 7.98 8.17 8.36
8.56 8.77 8.98 9.20 9.43
9.66 9.91 10.16 10.42 10.69
10.97 11.26 11.56 11.87 12.19
12.52 12.66 12.80 12.94 13.08
13.23 13.37 13.52 13.67 13.83
13.98 14.14 14.30 14.46 14.62
Deflection Design
15.13 15.14 15.14
15.14 15.14 15.14 15.15 15.15
15.15 15.16 15.16 15.16 15.17
15.17 15.17 15.18 15.18 15.19
15.19 15.20 15.20 15.21 15.22
15.22 15.23 15.24 15.24 15.25
15.26 15.27 15.27 15.27 15.28
15.28 15.29 15.29 15.30 15.30
15.30 15.31 15.31 15.32 15.33
1
>
Df D t 07 h
450 445 440
435 430 425 420 415
410 405 400 395 390
385 380 375 370 365
360 355 350 345 340
335 330 325 320 315
3iu 31)8 306 304 302
300 298 296 294 292
290 288 286 284 282
CTDO14593
THICKNESS DESIGN OF DUCTILE-IRON PIPE
TABLE 50.11--(cont.)
Trench Load (P)--psi
Bending Stress Design
14.79 14.96 15.13 15.30 15.48
15.65 15.83 16.02 16.20 16.39
16.58 16.77 16.97 17.16 17.36
17.57 17.77 17.98 18.19 18.40
18.62 18.84 19.06 19.28 19.51
19.73 19.97 20.20 20.43 20.67
20.91 21.16 21.40 21.65 21.90
22.15 22.40 22.66 22.92 23.18
23.44 23.70 23.97
Deflection Design
15.33 15.34 15.34 15.35 15.35
15.36 15.37 15.37 15.38 15.39
15.40 15.40 15.41 15.42 15.43
15.44 15.45 15.45 15.46 15.47
15.48 15.49 15.51 15.52 15.53
15.54 15.55 15.57 15.58 15.59
15.61 15.62 15.64 15.65 15.67
15.69 15.71 15.73 15.75 15.77
15.79 15.81 15.83
Di D t or /i
280 278 276 274 272
270 268 266 264 262
260 258 256 254 252
250 248 246 244 242
240 238 236 234 232
230 228 226 224 222
220 218 216 214 212
210 208 206 204 202
200 198 196
Trench Load (P)--psi
Bending Stress Design
24.24 24.50
24.77 25.04 25.31 25.59 25.86
Deflection Design
15.86 15.88
15.91 15.93 15.96 15.99 16.02
26.13 26.41 26.68 26.96 27.23
27.51 27.65 27.78 27.92 28.06
28.19 28.33 28.47 28.60 28.74
28.87 29.01 29.15 29.28 29.41
29.55 29.68 29.82 29.95 30.08
30.21 30.34 30.48 30.61 30.74
30.87 30.99 31.12 31.25 31.38
16.06 16.09 16.12 16.16 16.20
16.24 16.26 16.28 16.31 16.33
16.35 16.37 16.40 16.42 16.45
16.48 16.50 16.53 16.56 16.59
16.62 16.65 16.68 16.71 16.74
16.78 16.81 16.85 16.89 16.92
16.96 17.00 17.04 17.09 17.13
23
Df D Tot Z
194 192
190 188 186 184 182
180 178 176 174 172
170 169 168 167 166
165 164 163 162 161
160 159 158 157 156
155 154 153 152 151
150 149 148 147 146
145 144 143 142 141
CTD014594
24 AMERICAN NATIONAL STANDARD
TABLE 50.11--(cont.)
Trench Load (P*)--Psi
Trench Load (P*)--psi
Bending Stress Design
31.50 31.63 31.76 31.88 32.01
32.13 32.25 32.38 32.50 32.62
32.75 32.87 32.90 33.11 33.23
33.35 33.47 33.59 33.71 33.83
33.95 34.07 34.19 34.31 34.43
34.55 ' 34.68
34.80 34.92 35.05
35.17 35.30 35.43 35.56 35.69
35.83 35.96 36.10 36.25 36.39
36.54 36.69 36.85
Deflection Design
17.17 17.22 17.27 17.32 17.37
17.42 17.47 17.53 17.58 17.64
17.70 17.76 17.83 17.89 17.96
18.03 18.11 18.18 18.26 18.34
18.42 18.51 18.60 18.69 18.78
18.88 18.98 19.09 19.20 19.31
19.43 19.55 19.68 19.81 19.95
20.09 20.24 20.39 20.55 20.72
20.89 21.07 21.26
Dt D t 01 tt
140 139 138 137 136
135 134 133 132 131
130 129 128 127 126
125 124 123 122 121
120 119 118 117 116
115 114 113 112 111
110 109 108 107 106
105 104 103 102 101
100 99 98
Bending Stress Design
37.01 37.17
37.34 37.52 37.70 37.89 38.08
38.28 38.49 38.71 38.93 39.17
39.41 39.67 39.94 40.22 40.51
40.82 41.14 41.48 41.84 42.21
42.60 43.02 43.45 43.92 44.40
44.91 45.46 46.03 46.64 47.28
47.96 48.68 49.44 50.25 51.11
52.02 52.99 54.02 55.12 56.28
.
Deflection Design
21.45 21.66
21.87 22.09 22.32 22.56 22.82
23.08 23.36 23.65 23.95 24.27
24.60 24.95 25.31 25.70 26.10
26.52 26.97 27.44 27.93 28.46
29.01 29.59 30.20 30.85 31.53
32.26 33.03 33.85 34.71 35.63
36.61 37.65 38.77 39.95 41.21
42.57 44.01 45.56 47.23 49.01
Dt D i ur <i
97 96
95 94 93 92 91
90 89 88 87 86
85 84 83 82 81
980
79 78 77 76
75
74 %
73 72 71
70 69 68 67 66
65 64 63 62 61
60 59
958
57 56
CTD014595
THICKNESS DESIGN OF DUCTILE-IRON PIPE
25
TABLE 50.11--(coni.)
Trench Load (P.)--fsi
Trench Load (Pt)--psi
Bending Stress Design
57.53 58.86 60.28 61.79 63.41
65.14 67.00 68.99 71.12 73.41
75.88 78.54 81.40
Deflection Design
50.93 53.00 55.23 57.64 60.25
63.07 66.13 69.46 73.09 77.04
81.36 86.10 91.29
Dt D l r ti
55 54 S3 52 51
50 49 48 47 46
45 44 43
Bending Stress Design
84.50 87.85
91.47 95.40 99.67 104.32 109.40
114.94 121.02 127.69 135.03 143.14
Deflection Design
97.01 103.31
110.27 117.98 126.56 136.11 146.78
158.75 172.21 187.41 204.63 224.22
Dt D Tor7I
42 41
40 39 38 37 36
35 34 33 32 31
* E' - 700; Kh - 0.128; Km - 0.085. t The - for the tabulated P nearest to the calculated P is selected; when the calculated P* is halfway between
two tabulated values, the smaller - should be used.
CTD014596
AMERICAN NATIONAL STANDARD
TABLE 50.12
Thickness for Earth Load Plus Truck Load
Laying Condition
Type 1
Type 2
Type 3
Type 4
Type S
Thickness* Class in.
Total
Total
Total
Use Calculated Use Calculated Use Calculated Use
Thickness* Class Thickness* Class Thickness* Class Thickness* Class
in. tn. in. in.
0.18 51 0.17 51 0.16 51 0.15 51 0.14 51
3 0.17 51 0.16 51 0.16 51 0.15 51 0.14 51
4 0.17 51 0.16 51 0.15 51 0.14 51 0.14 51
5 0.16 51 0.16 51 0.15 51 0.14 51 0.14 51
6 0.16 51 0.16 51 0.15 51 0.14 51 0.14 51
7
0.16 51
0.16 51
0.15 51
0.14 51
0.14
51
8 0.17 51 0.16 51 0.15 51 0.15 51 0.14 51
9 0.17 51 0.16 51 0.15 51 0.15 51 0.14 51
10 0.17 51 0.16 51 0.15 51 0.15 51 0.14 51
12 0.17 51 0.17 51 0.16 51 0.15 51 0.14 51
14 0.18 51 0.17 51 0.16 51 0.15 51 0.14 51
16 0.18 51 0.17 51 0.17 51 0.15 51 0.14 51
20 0.19 51 0.18 51 0.17 51 0.16 51 0.15 51
24
0.19 51
0.19 51
0.18 51
0.16 51
0.15
51
28
0.20 51
0.19 51
0.19 51
0.17 51
0.15 51
32 0.21 51 0.20 51 0.19 51 0.18 51 0.15 51
2. 0.19 51 0.18 51 0.17 51 0.15 51 0.15 51
3.
0.18 51
0.17 51
0.16 51
0.15 51
0.14 51
4 0.17 51 0.16 51 0.16 51 0.15 51 0.14 51
5 0.17 51 0.16 51 0.15 51 0.15 51 0.14 51
6 0.17 51 0.16 51 0.15 51 0.15 51 0.14 51
7 0.17 51 0.16 51 0.16 51 0.15 51 0.14 51
8 0.17 51 0.16 51 0.16 51 0.15 51 0.14 51
9
0.18 51
0.17 51
0.16 51
0.15 51
0.14
51
10 0.18 51 0.17 51 0.16 51 0.15 51 0.14 51
12 0.18 51 0.17 51 0.16 51 0.15 51 0.14 51
14 0.19 51 0.18 51 0.17 51 0.15 51 0.15 51
16 0.19 51 0.18 51 0.17 51 0.16 51 0.15 51
20 0.20 51 0.19 51 0.18 51 0.16 51 0.15 51
24 0.21 51 0.20 51 0.19 51 0.17 51 0.15 51
28 0.22 51 0.21 51 0.20 51 0.18 51 0.15 51
32 0.22 51 0.21 51 0.21 51 0.19 51 0.16 51
2. 0.21 50 0.20 50 0.18 50 0.16 50 0.15 50 3 0.20 50 0.19 50 0.18 50 0.16 50 0.15 50 4 0.19 50 0.18 50 0.17 50 0.16 50 0.15 50
S 0.19 50 0.17 50 0.17 50 0.15 50 0 15 50 6 0.19 50 0.17 50 0.17 50 0.15 50 0.15 50
7 0.19 50 0.18 50 0.17 50- 0.16 50 0.15 50
8 0 19 50 0.18 50 0.17 50 0.16 50 0.15 50 9 0.20 50 0.18 50 0.17 50 0.16 50 0.15 50 10 0.20 50 0.18 50 0.17 50 0.16 50 0.15 50 12 0.21 50 0.19 50 0.18 so 0.16 50 0.15 50
14 0.21 50 0.20 50 0.18 50 0.17 50 0.15 50 16 0.22 50 0.21 50 0.19 50 0.17 50 0.15 50 20 0.23 50 0.22 50 0.21 50 0.18 50 0 16 50 24 0.24 ' 50 0.23 50 0.22 50 0.19 50 0.16 50 28 0.25 50 0.24 50 0.23 50 0.20 50 0.16 so 32 0.26 50 0.25 50 0.24 50 0.22 50 0.17 50
to net thickness.
CTD014597
THICKNESS DESIGN OF DUCTILE-IRON PIPE
TABLE 50.12--(coni.)
27
Laying Condition
Depth of
Cover
ft
Type l
Total Calculated Use Thickness* Class
*w.
Type 2
Type 3
Type 4
Type 5
Total
Total
Total
Total
Calculated Use Calculated Use Calculated Use Calculated Use
Thickness* Class Thickness* Class Thickness* Class Thickness* Clast
in. in. <n. in.
2.5 0.24 50 0.22 50 0.20 50 0.18 50 0.16 50 3 0.23 50 0.21 50 0.19 50 0.17 50 0.16 50 4 0.21 50 0.19 50 0.18 50 0.16 50 0.15 50 5 0.21 50 0.19 50 0.18 50 0.16 50 0.15 50
6 0.21 50 0.19 50 0.18 50 0.16 50 0.15 50 7 0.21 50 0.19 50 0.18 50 0.16 50 0.15 50 8 0.21 50 0.19 50 0.18 50 0.16 50 0.15 50 9 0.22 50 0.20 50 0.18 50 0.17 50 0.15 50 10 0.22 50 0.20 50 0.19 50 0.17 50 0.15 50 12 0.23 50 0.21 50 0.19 50 0.17 50 0.16 50 14 0.24 50 0.22 50 0.20 50 0.18 50 0.16 50 16 0.25 50 0.23 50 0.21 50 0.18 50 0.16 ' 50 20 0.27 50 0.25 50 0.23 50 0.19 50 0.17 50 24 0.28 50 0.26 50 0.24 50 0.21 50 0.17 50 28 0.29 51 0.28 50 0.26 50 0.23 50 0.18 50 32 0.30 51 0.29 51 0.27 50 0.24 50 0.18 50
2.5 0.27 50 0.25 50 0.23 50 0.20 50 0.17 50 3 0.26 50 0.23 50 0.21 50 0.19 50 0.17 50 4 0.24 50 0.22 50 0.20 50 0.18 50 0.17 50 5 0.23 50 0.21 50 0.20 50 0.18 50 0.17 50 6 0.23 50 0.21 50 0.20 50 0.18 50 0.17 50 7 0.24 50 0.21 50 0.20 50 0.18 50 0.17 50 8 0.24 50 0.22 50 0.20 50 0.18 50 0.17 50 9 0.25 50 0.22 50 0.20 50 0.18 50 0.17 50
10 0.25 50 0.23 50 0.21 50 0.19 50 0.17 50 12 0.26 50 0.24 50 0.22 50 0.19 50 0.17 50 14 0.28 50 0.25 50 0.23 50 0.20 50 0.18 50
16 . 0.29 50 0.26 50 0.24 50 0.20 50 0.18 50 20 0.31 51 0.28 50 0.26 50 0.22 50 0.18 50 24 0.32 51 0.30 50 0.28 50 0.24 50 0.19 50 28 0.34 52 0.32 51 0.30 50 0.26 50 0.20 50 32 0.35 52 0.33 51 0.32 51 0.28 50 0.20 50
2.5 0.30 50 0.27 50 0.24 50 0.21 50 0.18 3 0.28 50 0.25 50 0.23 50 0.20 50 0.18 4 0.26 50 0.23 50 0.21 50 0.19 50 0.17 5 0.25 50 0.23 50 0.21 50 0.19 50 0.17 6 0.25 50 0.23 50 0.21 50 0.19 50 0.17 7 0.26 50 0.23 50 0.21 50 0.19 50 0.17 8 0.26 50 0.23 50 0.21 50 0.19 50 0.17 9 0.27 50 0.24 50 0.22 50 0.19 50 0.17 10 0.27 50 0.24 50 0.22 50 0.20 50 0.18 12 0.29 50 0.26 50 0.23 50 0.20 50 0.18 14 0.30 50 0.27 50 0.24 50 0.21 50 0.18 16 0.31 50 0.29 50 0.26 50 0.21 50 0.18 20 0.34 51 0.31 50 0.28 50 0.23 50 0.19 24 0.36 52 0.33 51 0.31 50 0.25 50 0.20 28 0.38 52 0.35 51 0.33 51 0.28 50 0.21 32 0.39 53 0.37 52 0.35 51 0.30 50 0.23
* Total calculated thickness includes service allowance and casting tolerance added to net thickness.
50 50 50 50 50 50 50 50 so 50 50 50 50 50 50 50
CTD014598
28 AMERICAN NATIONAL STANDARD
TABLE 50.12-- (coni.)
Laying Condition
Depth of
Cover
ft
Type 1
Type 2
Type 3
Type 4
Type J
Total
Total
Total
Total
Total
Calculated Use Calculated Use Calculated Use Calculated Use Calculated Use
Thickness* Class Thickness* Class Thickness* Class Thickness* Class Thickness* Class in. in. in. in. in.
2.5
0.32
50
0.29
50
0.26
50
0.22
50
0.20
50
3
0.31
50
0.27
50
0.24
so
0.21
50
0.19
50
4 0.29 50 0.26 50 0.23 50 0.21 50 0.19 50
5 0.28 50 0.25 50 0.23 50 0.20 50 0.19 50
6
0.28
50
0.25
50
0.23
50
0.20
50
0.19
50
7 0.28 50 0.25 50 0.23 50 0.21 50 0.19 50
8 0.29 50 0.26 50 0.23 50 0.21 50 0.19 50
9 0.30 50 0.26 50 0.24 50 0.21 50 0.19 50
10 0.31 50 0.27 50 0.24 50 0.21 50 0.19 50
12 0.32 50 0.29 50 0.26 50 0.22 50 0.19 50
14 0.34 50 0.30 50 0.27 50 0.23 so 0.20 50
16
0.35
51
0.32
50
0.29
50
0.24
50
0.20
50
20
0.38
52
0.35
51
0.32
50
0.26
50
0.21
50
24 0.40 52 0.38 52 0.34 50 0.28 50 0.22 50
28 0.42 53 0.40 52 0.37 51 0.31 50 0.24 50
32 0.44 54 0.42 53 0.39 52 0.34 50 0.26 50
2.5 0.34 50 0.30 50 0.27 50 0.23 50 0.20 50
)3 0.32 50 0.28 50 0.25 50 0.22 50 0.20 50
4 0.30 50 0.27 50 0.24 50 0.21 50 0.19 50
5 0.30 50 0.26 50 0.24 50 0.21 50 0.19 50
6 0.30 50 0.26 50 0.24 50 0.21 50 0.19 50
7
0.30
50
0.26
50
0.24
50
0.21
50
0.19
50
8 0.31 50 0.27 50 0.25 50 0.22 50 0.19 50
9 0.32 50 0.28 50 0.25 50 0.22 50 0.20 50
10 0.33 so 0.29 50 0.26 50 0.22 50 0.20 50
12 0.35 50 0.31 50 0.27 50 0.23 50 0.20 50
14 0.36 51 0.33 50 0.29 50 0.24 50 0.20 50
16
0.38
51
0.34
50
0.30 50 0.25 50 0.21
50
20
0.41
52
0.38
51
0.34 50 0.27 50 0.22 50
24 0.44 53 0.41 52 0.37 51 0.30 50 0.24 50
28 0.46 54 0.43 53 0.40 52 0.33 50 0.27 50
32
0.48
55
0.46
54
0.43
53
0.36
51
0.29
50
2.5 0.36 50 0.32 50 0.28 50 0.24 50 0.20 50
3 0.34 50 0.29 50 0.26 50 0.23 50 0.20 50
4 0.32 50 0.28 so 0.25 50 0.22 50 0.20 50
5
0.31
50
0.27
50
0.25
50
0.22
50
0.19
50
6 0.31 50 0.27 50 0.25 50 0.22 50 0.19 50
7 0.32 50 0.28 50 0.25 50 0.22 50 0.20 50
8 0.33 50 0.29 50 0.26 50 0.22 50 0.20 50
9 0.34 50 0.30 50 0.26 50 0.23 50 0.20 50
10 0.35 50 0.30 50 0.27 50 0.23 50 0.20 50
12
0.37
51
0.32
50
0.29
50
0.24
50 0.21
50
14 0.39 51 0.35 50 0.30 50 0.25 50 0.21 SO
16 0.41 52 0.37 51 0.32 50 0.26 50 0.22 50
J20 0.44 53 0.40 52 0.36 50 0.29 50 0.23 50
24 0.47 54 0.44 53 0.40 52 0.32 50 0.26 50
28 0.50 55 0.46 54 0.43 53 0.36 50 0.29 50
32
0.53
56
0.49
55
0.46
54
0.39
51
0.32
50
* Total calculated thickness includes service allowance and casting tolerance added to net thickness.
CTD014599
THICKNESS DESIGN OF DUCTILE-IRON PIPE
29
TABLE 50.12--(coni.)
Laying Condition
Depth Sue of IK. Cover
Type 1
Type 2
Type 3
Type 4
Types
ft Total
Total
Total
Total
Total
Calculated Use Calculated Use Calculated Use Calculated Use Calculated Use
Thickness* Class Thickness* Class Thickness* Class Thickness* Class Thickness* Class
in. in. in. in. in.
20 2.S 0.38 51 0.33 50 0.29 50 0.24 50 0.21 50 3 0.35 50 0.31 50 0.27 50 0.23 50 0.20 so 4 0.34 50 0.29 50 0.26 50 0.23 50 0.20 50 5 0.33 50 0.28 50 0.26 50 0.23 50 0.20 50 6 0.33 50 0.29 50 0.26 50 0.23 50 0.20 50 7 0.34 50 0.29 50 0.26 50 0.23 50 0.20 50 8 0.35 50 0.30 50 0.27 50 0.23 50 0.20 50 9 0.36 50 0.31 50 0.28 50 0.24 50 0.21 50
10 0.37 50 0.32 50 0.28 50 0.24 50 0.21 50 12 0.39 51 0.34 50 0.30 50 0.25 50 0.21 50 14 0.41 52 0.37 50 0.32 50 0.26 50 0.22 50 16 0.43 52 0.39 51 0.34 50 0.27 50 0.22 50 20 0.47 54 0.43 52 0.39 51 0.31 50 0.23 50 24 0.50 55 0.47 ' 54 0.42 52 0.34 50 0.28 50 28 0.54 56 0.50 55 0.46 53 0.38 51 0.31 50 32 0.57 -- 0.53 56 0.49 54 0.42 52 0.34 50
24 2.5 0.42 51 0.35 50 0.31 50 0.26 50 0.22 50 3 0.39 50 0.33 50 0.29 50 0.25 50 0.21 50 4 0.37 50 0.31 50 0.28 50 0.24 50 0.21 50 5 0.36 50 0.31 50 0.28 50 0.24 50 0.21 50 6 0.36 50 0.31 50 0.28 50 0.24 50 0.21 50 7 0.37 50 0.32 50 0.28 50 0.24 50 0.21 50
8 0.39 50 0.33 50 0.29 50 0.25 50 0.21 50
9 0.40 51 0.34 50 0.30 50 0.25 50 0.22 50 10 0.41 51 0.35 50 0.31 50 0.26 50 0.22 50
12- 0.44 52 0.38 50 0.33 50 0.27 50 0.23 50
14 0.46 53 0.41 51 0.35 50 0.28 50 0.23 50 16 0.49 54 0.44 52 0.38 50 0.31 50 0.24 50 20 0.54 55 0.49 54 0.43 52 0.36 so 0.25 50 24 0.57 56 0.53 55 0.48 53 0.40 51 0.32 50 28 0.61 -- 0.57 56 0.52 55 0.43 52 0.36 50 32 0.65 -- 0.60 -- 0.56 56 0.47 53 0.40 51
30 2.5
3
4 5 6 7 8
9
10
12
14
16
20
24 28 32
t
t 0.40 50 0.34 50 0.28 50 0.23 50
0.37 50 0.32 50 0.27 50 0.23 50
0.35 50 0.31 50 0.26 50 0.22 50
0.35 50 0.31 50 0.26 so 0.22 50
0.35 50 0.31 50 0.26 50 0.22 50
0.36 50 0.31 50 0.26 50 0.23 50
0.37 50 0.33 50 0.27 50 0.23 50
0.39 50 0.34 50 0.28 50 0.23 50
0.40 50 0.35 50 0.28 50 0.24 50
0.44 51
0.37
50 0.30 50
0.24
50
0.47 52 0.40 50 0.32 50 0.25 50
0.51 53 0.43 51 0.37 50 0.26 50
0.57 55 0.50 53 0.43 51 0.29 50
0.62 56 0.56 54 0.48 52 0.37 50
0.67 -- 0.61 56 0.51 53 0.43 51 0.71 -- 0.66 -- 0.55 54 0.47 52
* Total calculated thickness includes service allowance and casting tolerance added to net thickness, t For pipe 30 in. and larger, consideration should be given to laying conditions other than Type 1.
CTD014600
30 AMERICAN NATIONAL STANDARD
TABLE 50.12--(coni.)
Laying Condition
Depth of
Cover
ft
Type 1
Total Calculated Use Thickness* Class
tn.
Type 2
Total Calculated Use Thickness* Class
in.
Type 3
Total Calculated Use Thickness* Class
in.
Type 4
Total Calculated Use Thickness* Class
in.
Type 5
Total Calculated Use Thickness* Class
in.
9 9
2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32
2.5 3 4 5 6 7 8 9 10 12 14 16 20 24 28 32
2.5 3 4 5 6 7
8 9 10 12 14 16 20 24 28 32
t t t
t 0.43 50 0.37 50 0.30 50 0.25 50
0.40 50 0.35 50 0.29 50 0.24 50
0.39 50 0.34 50 0.28 50 0.24 50
0.38 50 0.34 50 0.28 50 0.24 50
0.39 50 0.34 50 0.28 50 0.24 50
0.40 50 0.35 50 0.29 50 0.24 50
0.42 50 0.36 50 0.30 50 0.24 50
0.43 50 0.37 50 0.30 50 0.25 50
0.45 50 0.38 50 0.31 50 0.25 50
0.49 51
0.42 50
0.33 50
0.26 50
0.54 52 0.46 51 0.37 50 0.27 50
0.58 53 0.49 51 0.42 50 0.28 50
0.65 54 0.57 53 0.50 51 0.33 50
0.71 56 0.63 54 0.55 52 0.43 50
0.77 -- 0.70 55 0.60 53 0.50 51
0.82 -- 0.76 -- 0.64 54 0.55 52
t 0.46 50 0.40 50 0.32 50 0.26 50 0.44 50 0.38 50 0.31 50 0.25 50
0.42 50 0.37 50 0.30 50 0.25 50
0.42 50 0.37 50 0.30 50 0.25 50
0.42 50 0.37 50 0.30 50 0.25 50
0.44 50 0.38 50 0.31 50 0.25 50
0.46 50 0.39 50 0.32 50 0.26 50
0.48 50 0.41 50 0.33 50 0.26 50
0.50 51
0.42 50 0.33 50 0.27 50
0.55 51
0.47
50 0.35 50 0.28 50
0.60 52 0.52 51 0.42 50 0.29 50
0.64 53 0.56 52 0.48 50 0.30 50
0.73 54 0.64 53 0.57 52 0.37 50
0.80 56 0.71 54 0.63 53 0.49 50
0.87 -- 0.79 55 0.69 54 0.57 52
0.93 -- 0.86 -- 0.73 54 0.63 53
t 0.50 50 0.43 50 0.35 50 0.28 50 0.48 50 0.42 50 0.34 50 0.28 50
0.46 50 0.40 50 0.33 50 0.27 50
0.46 50 0.40 50 0.33 50 0.27 50
0.47 50 0.41 50 0.33 50 0.27 50
0.48 50 0.42 50 0.34 50 0.28 50
0.51 50 0.44 50 0.35 50 0.28 50
0.53 50 0.45 50 0.36 50 0.29 50
0.56- 51 0.47 50 0.37 50 0.30 50
0.61 51 0.53 50 0.39 50 0.31 50
0.67 52
0.59 51
0.48 50 0.32
50
0.72 53 0.64 52 0.55 51 0.33 50
0.82 54 0.72 53 0.65 52 0.43 50
0.91 56 0.80 54 0.72 53 0.56 51 0.98 -- 0.89 55 0.79 54 0.65 52
1.05 0.97 -- 0.84 55 0.72 S3
* Total calculated thickness includes service allowance and casting tolerance added to net thickness, t For pipe 30 in. and larger, consideration should be given to laying conditions other than Type i.
CTD014601
thickness design of ductile--ikon pipe
31
TABLE 50.12-- (coni.)
Laying Condition
Depth
Type 1
Type 2
Types
Type 4
Types
Size of
in. Cover
n Total
Total
Total
Total
Total
Calculated Use Calculated Use Calculated Use Calculated Use Calculated Use
Thickneaa* Class Thickness* Class Thickness* Class Thickness* Class Thickness* Class
in. in. in. in. in.
54 2.5 3 4 5 6 7 8 9 10 12 14 16
20 24 28 32
t
t 0.54 50 0.46 50 0.37 50 0.30 50 0.52 50 0.45 50 0.37 50 0.30 50 0.51 50 0.44 50 0.36 50 0.30 50 0.51 50 0.44 50 0.36 50 0.30 50 0.52 50 0.45 50 0.37 50 0.30 50 0.53 50 0.46 50 0.37 50 0.30 50 0.56 SO 0.48 50 0.38 50 0.31 50
0.59 50 0.50 50 0.39 50 0.32 50 0.62 51 0.52 50 0.41 50 0.32 50 0.68 51 0.60 50 0.43 50 0.34 50 0.74 52 0.67 51 0.54 50 0.35 50 0.80 53 0.72 52 0.62 51 0.36 50
0.91 54 0.81 53 0.73 52 0.48 50 1.01 56 0.89 54 0.81 53 0.63 51 1.09 -- 0.99 55 0.88 54 0.73 52
1.17 -- 1.08 -- 0.94 55 0.81 S3
* Total calculated thickness includes service allowance and casting tolerance added to net thickness, t For pipe 30 in. and larger, consideration should be given to laying condit ons other than Type 1.
TABLE 50.13
Thickness for Internal Pressure
Rated Water Working' Pressure*--tsi
Pipe Size
is.
150 200 250 300 350
Total Calculated Thickness
iff.t
Use Class
Total Calculated Thickness
iii.t
Use Class
Total Calculated Thickness
*t
Use Class
Total Calculated Thickness
in.t
Use Class
Total Calculated
Thickness in.t
Use Class
3
0.15
51
0.16
51
0.16
51
0.17
51
0.17
51
4
0.16
51
0.16
51
0.17 51
0.18
51
0.18
51
6 0.17 50 0.18 50 0.19 50 0.20 50 0.20 50
8 0.18 50 0.19 50 0.21 50 0.22 50 0.23 50
10
0.21
50
0.22
so
0.23
50
0.25
so
0.26
50
12 0.22 50 0.23 50 0.25 50 0.27 50 0.28 50
14 0.24 50 0.26 50 0.28 50 0.30 50 0.31 50
16 0.25 50 0.27 50 0.30 50 0.32 50 0.34 50
18 0.27 50 0.29 50 0.31 50 0.34 50 0.36 50
20 0.28 50 0.30 50 0.33 50 0.36 50 0.38 51
24
0.30
50
0.33
50
0.37
50
0.40
51
0.43
52
30
0.34 50 0.38 50 0.42 51
0.45
52
0.49
53
36
0.38 50 0.42 50
0.47
51
0.51
52
0.56
53
42 0.41 50 0.47 50 0.52 51 0.57 52 0.63 53
48
0.46 50 0.52 50 0.58 51
0.64
52
0.70
53
54
0.51
50
0.58
50
0.65
51
0.71
52
0.78
53
These pipe are adequate for the rated working pressure plus a surge allowance of 100 psi. t Total calculated thickness includes service allowance and casting tolerance added to net thickness.
CTD014602
32 AMERICAN NATIONAL STANDARD
TABLE 50.14
Rated Working Pressure and Maximum Depth of Cover
Pipe Size in.
Thickness Class
Nominal Thickness
in.
Rated Water Working Pressure
psi*
Type 1
Laying Condition
Type 2
Type 3
Type 4
Maximum Depth of Cover--/ft
Type 5
3 51
0.25
350
98 loot toot loot loot
52 0.28 350 loot loot toot toot loot
53 0.31 350 loot toot loot loot loot
54 0.34 350 loot loot loot loot loot
55 0.37 350 toot loot loot loot loot
56 0.40 350 loot loot loot loot loot
4 51
0.26
350
76 86 96 loot loot
52 0.29 350 loot loot loot loot loot
53 0.32 350 loot loot 100t loot loot
54 0.35 350 loot loot loot loot loot
55 0.38 350 loot loot loot loot loot
56 0.41 350 loot loot loot loot loot
6 50
0.25
350
32 38 44 56 75
51 0.28
350
49 57 64 80 loot
52 0.31
350
67
77
86
loot
loot
53 0.34
350
91 loot loot loot loot
54 0.37 350 toot loot loot loot loot
55 0.40 350 loot loot loot loot loot
56 0.43 350 loot loot loot loot loot
S 50
0.27
350
25 30 36 46 64
51 0.30
350
36 42 49 61 81
52 0.33
350
47 54 62 77 99
?3 0.36
350
64 73 82 loot loot
54 0.39
350
80
91
loot
loot
loot
55 0.42
350
98
loot
loot
loot
loot
56 0.45 350 loot loot toot loot loot
10 50 51 52 53 54
55
56
12 50
51
52
53 54
55
56
0.29 0.32 0.35 0.38 0.41 0.44 0.47
0.31 0.34 0.37
0.40
0.43 0.46 0.49
350 350 350 350 350 350 350
350 350 350 350 350 350 350
19 24 29 38 55 27 32 38 49 66 35 41 47 59 79 45 52 59 74 95 57 65 74 91 loot 67 77 86 loot loot 81 92 loot loot loot
17 22 27 36 52 23 28 33 43 60 30 35 41 53 71 36 42 49 61 81 45 52 59 74 95 54 62 71 87 loot 64 73 83 loot loot
* These pipe are adequate for the rated working pressure plus a surge allowance of 100 pai. Ductile-iron pipe for working pressures higher than 350 psr is available,
t An allowance for a single H-20 truck with 1.5 impact factor is included for all depths of cover, t Calculated maximum depth of cover exceeds 100 ft.
3 3
3
CTD014603
THICKNESS DESIGN OF DUCTILE-IRON PIPE
33
TABLE 50.14--(coni.)
Pipe Size ,
Thickness Class
Nominal Thickness
Rated Water Working Pressure
Psi*
Type 1
Laying Condition
Type 2
Type 3
Type 4
Maximum Depth of Cover--, ft
Type S
14 so 51 52 53 54 55 56
16 50 51 52 53 54 55 56
18 50 51 52 .53 54 55 56
20 so 51 52
, 53 54 55 56
24 50 51 52 53 54 55 56
30 50 51 52 53 54 55 56
0.33 0.36 0.39 0.42 0.45 0.48 0.51
0.34 0.37 0.40 0.43 0.46 0.49 0.52
0.35 0.38 0.41 0.44 0.47 0.50 0.53
0.36 0.39 0.42 0.45 0.48 0.51 0.54
0.38 0.41 0.44 0.47 0.50 0.53 0.56
0.39 0.43 0.47 0.51 0.55 0.59 0.63
350 350 350 350 350 350 350
350 350 350 350 350 350 350
350 350 350 350 350 350 350
300 350 350 350 350 350 350
250 300 350 350 350 350 350
200 250 300 350 350 350 350
15 19 24 33 49
19 23 28 38 55
24 29 34 44 62
30 35 41
53 71
36 42 49 61 81
43 50 57 71 92
52 59 67 83 loot
13 17 21 30 47 16 21 25 34 51 20 25 30 40 57 25 30 36 46 64 30 35 41 53 71 35 41 47 59 79 41 48 55 68 89
11 15 20 29 42 14 19 23 32 49 18 22 27 36 53 22 26 31 41 58 25 30 36 46 64 30 35 41 53 71 35 41 47 59 79
10 14 18 27 38 13 17 21 30 44 16 20 25 34 50 19 23 28 38 54 22 27 32 42 59 26 31 37 47 65 30 35 41 53 71
8 12 17 23 31 10 15 19 27 36 13 17 21 30 41 15 19 24 33 47 18 22 27 36 53 20 25 30 40 57 24 29 34 44 61
5 10 14 18 25
12 16 21 29 14 19 24 33 17 21 29 38 19 24 33 44 22 27 36 51 26 31 41 57
* These pipe are adequate for the rated working pressure plus a surge allowance of 100 pai. Ductile-iron pipe or working pressures higher than 350 psi is available.
t An allowance for a single H-20 truck with 1.5 impact factor is included for all depths of cover. Calculated maximum depth of cover exceeds 100 ft.
For pipe 30 in. and larger, consideration should be given to laying conditions other than Type 1.
CTD014604
rr
34 AMERICAN NATIONAL STANDARD
TABLE 50.14--(cont.)
Pipe Sise in.
Thickness Class
Nominal Thickness
M.
Rated Water Working Pressure
fist*
Type 1
Laying Condition
Type 2
Type 3
Type*
Maximum Depth of Cover--fit
Type S
36 50 51 52 53 54 55 56
42 50 51 52 S3 54 55 56
48 50 51 52 S3 54 55 56
54 '50 51 52 53 54 55 56
0.43 0.48 0.53 0.58 0.63 0.68 0.73
0.47 0.53 0.59 0.65 0.71 0.77 0.83
0.51 0.58 0.65 0.72 0.79 0.86 0.93
0.57 0.65 0.73 0.81 0.89 0.97 1.05
200 250 300 350 350 350 350
200 250 300 350 350 350 350
200 250 300 350 350 350 350
200 250 300 350 350 350 350
i 10 13 17 25
12 16 20 28 15 19 24 32 17 21 28 37 20 25 33 43 23 28 37 so 26 31 41 59
i 9 13 16 24
12 15 19 27 14 18 22 30 17 22 27 35 20 24 32 42 23 28 38 48 26 31 41 57
! 9 12 15 23
12 14 18 26 14 18 21 30
917 21 25 34
20 24 30 40 23 28 37 47 26 31 41 55
i 9 12 15 23
12 14 18 25 14 17 21 29
317 21 25 34
20 25 30 40 23 28 37 47 27 32 42 55
* These pipe are adequate for the rated working pressure plus a surge allowance of 100 pai. Ductile-iron pipe for working pressures higher than 350 psi is available,
t An allowance for a single H-20 truck with 1.5 impact factor is included for all depths of cover.
t Calculated maximum depth of cover exceeds 100 ft. i For pipe 30 in. and larger, consideration should be given to laying conditions other than Type 1.
CTD014605
3r--5M--4/78--43150
CTD014606