CHAPTER 41
1949 Guide
general, long radius elbows and gradual changes in shape tend to maintain
uniform velocities accompanied by decreased turbulence, lower resistance and a. minimum of noise.
Heavy canvas connections (asbestos cloth" if there is a fire hazard) are
recommended on both the inlet and outlet to all fans. The fan discharge
` U.tV
-
~ja)
Standing seam
Dlw"' s*8"*
Pittsburgh seam
S slip
sftp '
9. Doer- Fig.
Sheet Metal
and Abrangement Details
connections shown in Fig. 9 are marked good, fair, and poor in the order of the amount of turbulence produced. Ah inspection of the heater connections shown in Fig. 9 will readily show that uniform velocity through the heater cannot be expected in the diagram noted poof. When obstruc
tions cannot be avoided, the duct area should never be decreased mote than 10 per cent and then a streamlined collar should' be used. ' Larger obstructions require an increase in the^ duct size in order to maintain as nearly uniform velocity as possible. Branch take-offs should always be
Air Duct;Pesign
829
Table 8. Weights of Shbbt Metal Used for Duct Construction ' -
Black. Sheets
Galvanized Sheets
u.s. Cage
Approximate Thickness, In.
Weight Per Square Foot
Approximate Thickness. In.
Weight Per Square Foot
30 28 26 ' 24 22 20 ' 18 16 . 14 12 11
10
Steel
0.0123 0.0153 0.0184 0.0245 0.-0306 0.0368 0.0490 0.0613 0.0766 0.1072 0.1225 0.1379
Iron
Ounces
0.0125 0.0156 0.0188 0.0250 0.0313 0.0375 0.0500
0.0625 0.0781 . 0.1094
0.1250 0.1406
8 10 12 16 20 24 32
40 50 . 70
80 90
Pounds
0.500 0.625 0.750 1.000 1.250 1.500 2.000 2.500 3.125 4.375 5.000 5.625
Steel
0.0163 0.0193 0.0224 0.0285 0.0346 0.0408 0.0530 0.0653 0.0806 0.1112 0.1265 0.1419
Iron
0.0165 0.0196 0.0228 0.0290 0.0353 . 0.0415 0.0540 0.0665 0.0821 0.1134 0.1290 0.1446
Ounces
10.5 12.5 14.5 18.5 22.5 26.5 34.5 42.5 52.5 72.5 82.5 92.5
Pounds
G.656 ' 0.781 0.906 . 1.156 - 1.406-. 1.656 2.156 * 2.656. 3.281 : 4.531 5.156 5.781 :
Galvanized sheets are gaged before galvanizing and are therefore approximately 0.004 in. thicker.
arranged to cut or slice into the air stream in order to reduce as fax as possible the losses in velocity head.
-The recommended gages for sheet metal duct construction are given in Table 7. Weights of sheet metal per square foot of surface for different gages are given in Table 8. The. weights of various gages and the. areas for any length of run of rectangular sheet metal ducts may also-be deter-' 'mined from Fig.. 10. The bottom scale represents the sum of the two rides of the duct and the oblique lines give the length of run in feet. Proceeding horizontally to the right from the intersection of.'vertical'-and oblique lines on the chart, the area of the duct may be determined in.the first vertical scale.*1 The scales to the right give" the weights, of the .duct run for different gages of metal.. In calculating the weighfsi&f duct, it is considered good practice to allow 20 per cent additional for weights of. joints and bracings. Various weights and thicknesses of standard: copper sheets will be found in Table 9 and of 2 S aluminum in Table 10.." .
HEAT LOSSES FROM DUCTS
In designing duct systems, the heat gains or losses of ducts should not be neglected. Heat gains in large duct systems can be quite considerable,
Table 9. Weights and Thicknesses of Standard Copper Sheets*
Rolled to Weight
Weight per Square Foot
Thickness, Inches
Ounces
10 12 14 16 18 20 24 28 32 36 40 44 . 48 - 56 64
Pounds
0.625 0.750
. . 0.875 1.000 1.125 1.250 1.500 1.750 2.000 2.250 2.500 2.750 3.000 3.500 4.000
Decimal Equivalent
0.0135 0.0162 0.0189 0.0216 0.0243 0.0270 0.0324 0.0378 0.0432 0.0486 0.0540 0.0594 - 0.0648 0.0756 0.0864
Nearest Fraction
% % % V
% '4s % % %
u%l*,
%
Variations from these weights must be Expected in practice.
Nearest Gage No.
B. & S.
27 26 25 23 ' 22 21 20 19 17
16 15 15 14 13 11
Stubs
29 27 26 24 23 22 21 20 19 18 17 17 16 . 15 : 14
U. S. Std.
29 28 26 25 24 23 22 . 20 19 18 17 ` 17 16. 1413