Document e1zXKw7VJagEQ2QeR5YdbK1ZM
460
CHAPTER 25
1965 Guide And Data Book
poorly fitted window. All of the figures for double-hung
Table 3 .... infiltration Through Walts'
wood windows are for the unlocked condition. Just bow a
Frprmnarl jn ecfcte fact par (jqoar* foot) (baud
window is closed, or fits when it is closed, has considerable
influence on the leakage. The leakage will be high if the
Wind YetoaSr, M3* per Hoar
are short, if die meeting rail members are warped, or
Type of Waff
if the frame and sash are not fitted squarely to each other.
5 10 15 20 25 30
It is possible to have a window with approximately the
average - crack and clearance that will have a leakage at Brick Wall*
least double that of the figures shown. Values for the average
8H io- Plain
2 4 8 12 19 23
double-hung wood window in Table 2 are considered to be easily obtainable figures, provided the workmanship
Plastered*
0.02 0.04 0.07 0.11 0.16 0.24
on the window is good. Should it be known that the windows
Plain
1 4 7 12 16 21
under consideration are poorly fitted, the larger leakage
13 in. Plastered*
0.01 0.01 0.03 0.04 0.07 0.10
values should be used. Locking a window generally decreases its leakage, but in some cases may push the meeting rail
Plastered4
0.03 0.10 0.21 0.36 0.63 0.72
members apart nH increase the leakage. On windows with Frame Wall, lath and plas 0.03 0.07 0.13 0.18 0.23 0.26
large clearances, locking will usually reduce the leakage.
ter*
Wood casement windows may be assumed to have the same unit leakage as for the average double-hung wood window when properly fitted. Locking, a normal operation In the rinsing of this type of window, maintains the crack
at a low value. For a metal pivoted sash, the length of crack is the total
perimeter of the movable or ventilating sections. Frame
* Tbe nlm fires in this table an 30 pemeut 1cm then teat rmlae* to aUo* tor hnilrfing up c4 perwnrs in rooms, and era baaed on test data reported in tto papers listed in chapter footnotes.
* Constructed at poious brick and 1TM* inintri wnrVininiTiip poor.
* Two coats prepared (jpsuro H--on brick.
4 Furring, lath, and two coats prepared gypmm piaster on bride.
* Wall ecinstt uctfaa: beeel
or eedar
ins paper, wood lath, and three coats gypsum ptwter.
, sheathing, build-
leakage on steel windows may be neglected when they are
properly grouted with cement mortar into brick work or concrete. When they are not properly sealed, the linear feet of sash section in contact with steel work at mulhons should be figured at 25 percent of the values given in Table
2 for industrial pivoted windows. When storm ash are applied to well fitted windows, some
reduction in infiltration is secured; the application of the sash provides an air space which reduces the heat trans^ mission and helps prevent the frosting of the windows.0 By applying storm sash to poorly fitted windows, a reduction in leakage of 50 percent may be obtained, the effect, so far. as air leakage is concerned, being roughly equivalent to that obtained by the installation of weatherstrips.
with an air space between them. The infiltration indicated in Fig. 4 is that determined in the laboratory, and should be multiplied by the factor 0.80 to give values consistent with .-Table 3. In order to find air leakage rates from Table 3 re sulting from pressure due to stack action the procedure out lined under Air Leakage Through Windows can be followed.
Published data are not available for air leakage rates through modem curtain wall constructions. These no doubt vary considerably in initial tightness as well as in tightness in years following construction. Maximum air leakage rates may. be specified by architects in the design of large commercial buildings.
Air Leakage Through Doors
Air Leakage Through Walls
Infiltration through doors must be considered in relation
Data on infiltration through brick and frame walls are given in Table 3.u The brick walls listed in this table are walls that show poor workmanship, and which are con structed of porous brick and lime mortar. For good work manship, the leakage through hard brick walls with cementlime mortar does not exceed one-third the values given. These tests indicate that plastering reduces the leakage by
to the type of door and room or building involved. For residences and small buildings where doors are used infre quently, infiltration can be based on the air leakage through cracks between door and frame. Such doors vary greatly in * fit because of their tendency to warp. For a well fitted door, the leakage values for a poorly fitted double-hung wood win dow may be used. If poorly fitted, twice this figureshouid be
about 96 percent; a heavy coat of cold water paint, 50 per
cent; and three coats of oil paint .carefully applied, 28 per
cent. The infiltration through walls ranges from 6 to 25
percent of that through windows and doors in a 10-story
office building, with imperfect sealing of plaster at the base
boards of the rooms. With perfect wiling the range is from
0.5 to 2.7 percent; or a practically negligible quantity, which
indicates the importance of good workmanship for proper
sealing at the baseboard. It will be noted from Table 3
that the infiltration through properly plastered walls can
be neglected.
The value of budding paper, when applied between
sheathing and shingles, is indicated by curve 3D-7D, Fig. 4,
which represents the effects on outside construction only,
without lath and plaster. The effectiveness of plaster prop
erly applied is no justification for the use of low grade
building paper, or of the poor construction of the wall con
taining it. Not only is it difficult to secure and maintain the full effectiveness of the plaster, but also it is highly de sirable to have two points of high resistance to air flow
Rg. 4 .,.. infiltration Through Various Types of Shingle Construction
Infiltration and Ventilation
461
Rg. 5 .... Design Chart for Evaluating Air Infiltration Rate Through Swinging Door Entrances' Under Winter Heating Conditions
used. If weatherstripped, the values may be reduced one-half. A,angle door that is frequently opened, as might be the case in a small store, should have a value applied three times that for a well fitted door. This extra allowance is for opening and dosing loeses, and is kept from being greater by the fact that doors are not used as much in the coldest and windiest
weather.- large.rates of leakage can occur with doors in use and this must.be taken into account in commercial establish-
ittentB where high traffic rates are expected. Information on
we infiltration characteristics of swinging and revolving doors has been quite limited14 and predictions for purposes of toad calculations generally have been a matter of engineering
judgment.14 A recent program of Society research has pro vided comprehensive data on the air leakage characteristics of swinging door entrances4 and similar data-on revolving
00r8;" Complementary data on pressure differences across entrances of tall buildings1 have also been provided..
Swinging Door Entrances
Air leakage through swinging door entrances is complicated by the opening and closing of doors and other variables re lated to the entrance. Based on a recent research* a simplified chart17 for design purpose is shown in Fig. 5 The infiltration can be evaluated by following the flow diagram if height of building, inside-outside temperature difference, net supply or exhaust air change, type of entrance and traffic rate' are known. Example 1 illustrates the use of the chart.'
Example t: A conventional .building 350 ft high'has :a"net cubage of 4,200,000 cu ft. Fresh air fans supply outside air.at the rate of 80,000 cfm and exhaust fans, discharge 50,000.cfm. The building a vestibule-type entrance having.four 3 X 7 ft doors and the indoor temperature is maintained at 75 F. Find the infil tration rate through the entrance at a time when:the traffic'rate 5a 2000 persons per hour. Outdoor temperature is 0;F.-rij,;ijifin;
Solution; From Fig. 5A; the theoretical draft, for.,a 350 ft