Document e1mwN86OzLrVOM87V0aa1baNG
HEATING VENTILATING AIR CONDITIONING CUIDE 1944
through the building materials in proportion to the vapor pressure dif ference on the two sides of the material. The total amount of water vapor transmitted is dependent on the permeability which is usually expressed in grains of moisture per square foot per hour per inch of mercury vapor pressure difference. The values for permeability in Table 11 are quoted from a publication of the National Bureau of Standards1J. The water vapor entering the conditioned space must be added to the latent cooling load.
Table 11. Permeability of Various Materials to Water Vapor
Material
Permeability
SGrains per q Ft
per Hr
per Inch Hg
Group 1*
14.7 2.9 49.1 4.9 3.4 12.5 1.1
. Group 2b V
0.08 to 0.13 0.13 to 0.17 1.37 to 2.58
11.00 3.68 to 3.84 .
1.15 ,19.73 to 20.57
2.67 to 2.74 25.68 to 34.27
3.03 to 4.36 6.19 29.07
Calculating Vapor and Heat Transfer Through Walls, by L. G. Miller (.Beating and Ventilating 35,
No. 11, 56 November, 1938).
' . '
**How to Overcome Condensation in Building Walls and Attics, by L. V. Teesdale (Heating and Venti lating 36, No. 4, 36 April. 1939).
Vapor barriers, to be effective in reducing entrance of moisture, must seal completely the walls, ceilings, and floors that are exposed to space having excessive vapor pressure and all doors must have gaskets applied to them to make the barrier effective.
ILLUSTRATION
From the foregoing discussion it is obvious that the determination of the maximum cooling load is rather complicated by reason of the variable nature of contributing load components. An illustrative example will explain the method.
^Moisture Condensation in Building Walls, by Harold W. Woolley (U. S. Department of Commerce', National Bureau of Standards, Building Materials and Structures Report BMS63).
160
CHAPTER 7. COOLING LOAD
____________________
.E
it
Store room ^
w
Ceiling height, \2-XT
e/vrr
!?
cp1 u.
8'xK
14'x6*
14'x6'
Fig. 4. Plan Diagram of Clothing Store
14'x6*
Example 1. Determine cooling load requirements for a clothing store illustrated in Fig. 4 and located in Pittsburgh, Pa., Latitude 40 deg. This is a one-story building located on a corner and it faces south and west. Assume building on east and north sides conditioned.
Wall construction, 8 in. concrete block, 4 in. brick veneer, plaster on walls, XJ = 0.33 (Table 7, Chapter 4, No. 93 B).
Roof construction, 2 in. concrete, H in. insulating board, metal lath and plaster ceiling, U = 0.26 (Table 14, Chapter 4, No. 14 B).
Floor, maple flooring on yellow pine, no ceiling below, U = 0.34 (Table 10, Chapter 4, No. l-O).
Partition, wood lath and plaster on both sides of studding, U = 0.34 (Table 8, Chapter 4, No. 3 B).
Windows, provided with awnings.
Front doors, 2 ft 6 in. x 7 ft (glass paneled).
Side door, 3 ft x 7 ft (glass paneled), XJ = 1.13 (Table 17 A, Chapter 4).
Occupancy, 10 clerks, 40 patrons.
Lights, 4200 w.
Outside design conditions, dry-bulb 95 F; wet-bulb 75 F;
Inside design conditions, dry-bulb 80 F; wet-bulb 67 F.
Basement temperature, 85 F.
Store room temperature, 88 F.
Solution. It is obvious from the shape and exposure of this store and the large glass area on the west side that the maximum cooling load will occur during the afternoon when the sun is shining on the west wall. From Fig. 1, the peak load may be expected at 4:00 p.m.
The combined normal transmission and solar radiation transmission through the roof at 4:00 p. m. is obtained from Fig. 2. While none of the roofs in Fig. 2 is exactly like this one, roof C is similar. A heat flow of 11 Btu per square foot per hour was assumed, slightly less than for roof C. The combined normal transmission and solar radiation
161