Document e1eOL1qpeexY8dVKzB8ZY49Mq
Monsanto
MONSANTO COMPANY
CENTRAL ENGINEERING DEPARTMENT
TRANSMITTAL
11
CEA NO. 24tl LOCATION
LU Cb
Q^i^KnPir. M
TRANSMITTAL NO. _
PROJECT TITLE
MC-S__ / q i <<=,~~X)c s,~T. C-C.'sCT * ors------------------------------------------------------------------
DISTRIBUTION:
MoRin________Caj <o
PROJECT MANAGER
p A (J FL
T
/K]cCoTCLK^^
U3 & (C_
1
ATTACHED ARE
Prints
.
Reproducibles
REMARKS:
THESE ARE Prel iminary For Approval
THESE ARE TO BE USED FOR
--------- Design Construction
PLEASE Review & Comment
Acknowledge
DRAWING NUMBER (OR EQUIPMENT NO.) REV. NO. .
/ AJ.S.T- /E?_o /~y~) a^J ~r
F-'u AJ C -T' / 0 A J
Fo FL,
L-OOP
AJo'b
P DT - do/-<?
piCLA. - So l-S~
Fic - So?-1
Xd-V - 6o3' / k. 2-
L-RC - 3 ov5- 3'
TS A - ,3s7-/
Fic - 3oi-|
C/ A - 3 / JL -"i
Zl l
- 3 t C=> - /
/ 1 - 3Ao-/
Tic ' 3iS' 5
Ci /X - 3 -2-S'
Cl ^ - 3 "2-4-1
F I c. -- ?> 4 4-1
_____________ K. ( <3 -
________
DESCRIPTION 4) uT (-/ aJ <?-.
CLoP<-/ ^
FlCL-^oC-/
f t cl- 4 t4-r
ft - ^ / s1-/
I'lC- ,44/-/
^ FfCA-T ^ F/ca-Si--
Signature ______ C? r\ / /4f/?AJ S
CE-29 REV. 12-69
PCB-ARCH-EXT0372703
Monsanto
DIVISION
Organic
\ INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
PDI-301-4
ISSUED BY
DATE
C. J. Hans 7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
1 OF
COLUMN AP INDICATOR
1.0 NEED FOR LOOP
Overall column AP is used to verify that the desired vapor rate is being generated in the reboiler furnace. It is also a desirable operating aid to manufacturing people.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to measure and indicate the pressure difference between the top and bottom of the distillation column.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
A differential pressure transmitter senses pressures at the top and bottom of the column and sends a proportional 3-15 psig signal to an indicator mounted on the panel.
ES 141 (8/69)
PCB-ARCH-EXT0372704
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
W. G. Krummrich
PLANT
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
PDI-301-4
ISSUED BY
DATE
C. J. Hans 7/29/71
REV. BY
DATE .
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION
3.1 NORMAL OPERATION
Typical loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
.
3.3.1 Air Failure
Loss of air will cause indication to drop.-to zero.
3.3.2 Power Failure
Not affected.
ES 141 (8/69)
PCB-ARCH-EXT0372705
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
PLANT W* G* KrUrtmriCh
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
ISSUED BY
C. J. Hans
REV. BY
PICA 301- 5 7/l9/71 PLANT LOOP NO.
DATE
REV
SHEET
1 OF
1.0 COLUMN PRESSURE: CONTROLLER
The column head pressure needs to be controlled (40 mm for 1016; 360 mm for "mono") to limit the still pot liquid temperature to a maximum of 300C at 140 mm. The still pressure is set by the
approximate 100 mm overall column AP for both operation.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to indicate and control the column's absolute pressure and active an alarm in the control room on high pressure.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The column pressure is sensed at the top of the column by an absolute pressure type pneumatic transmitter. The transmitter sends a 3-15 psig signal to a local indication, a pressure switch in the field cabinet for the alarm function, and to an indicating controller mounted on the panel in the control room. The controller compares the signal with the set point and sends a compensating signal to the control valve. The control valve bleeds air into the vacuum system.
The pressure switch activates an alarm when it senses an abnormally high input signal.
ES 141 (8/69)
PCB-ARCH-EXT0372706
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w- Gm Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO. .
___ PICA 301-5
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/19/71
REV. BY
DATE
REV
SHEET
OF
3.0 OPERATION OF LOOP
3.1 NORMAL OPERATION
Same as for a typical pressure loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Upon instrument air failure to controller, the valve will close, preventing air from being bled into the vacuum system. This would take all control of the vacuum system away from the controller. The vacuum system would' lower the column down to its inherent limits.
3.3.2 Power Failure
Upon electrical power failure only the alarm would be inoperative.
ES 141 (8/69)
PCB-ARCH-EXT0372707
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
ISSUED BY
C. J.
REV. BY
FIC-303-1
DATE
PLANT LOOP NO.
Hans 7/19/71
DATE
REV
SHEET l OF
1.0 COLUMN DISTILLATE CONTROLLER
The column distillate draw-off rate serves indirectly to control the column reflux ratio. This reflux ratio is automatically reset via this controller from 3:1 to 5:1 for 1016 and from 4:1 to 8:1 for "mono".
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to control the flow of product to storage and thereby set the reflux ratio.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The distillate flow rate is controlled by measuring the rate of flow in the line using an armored tube rotameter transmitter. This transmitter sends a pneumatic signal to the panel mounted indicating controller. The indicating controller compares this signal with a set point signal and sends a varying 3-15 psig signal to the control valve which adjusts the valve to compensate for variation of the set point.
The same rotameter transmitter signal is also sent to an analogue computing station which squares the signal (to be compatible with the integration on the panel). This analogue computing station sends its output to the integrator on the new panel which totalizes the amount of distillate to storage. Upon a preset number of counts, a contact in"the integrator closes causing a solenoid to energize and switch an air signal to the set point of the flow controller. This air signal comes from one of two manual loading stations which are preset to give a., 3:1 and a 5:1 reflux ratio. At the predetermined count, the solenoid switches air from the 3:1 signal to the 5:1 signal.
On the "mono" operation these signals will be set for a 4:1 and 8:1 reflux ratio. Settings for these points or any intermediate reflux ratio may be found with the attached table D-10.
ES 141 (8/69)
PCB-ARCH-EXT0372708
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
W. G. Krummrich
PLANT
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
FIC-303-1
ISSUED BY
C. J. Hans
DATE
7/19/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION
3.1 NORMAL
a. At the start of batch the controller manual output should be at with the controller in manual position (for total reflux). Set the integration total to read 0 counts. Set the predetermining counter to read 7842 counts. (7842 x 2.44 factor = 19,135 gallons
. @3:1 ratio). Check setpoint regulator outputs so that reflux ratios will be 3:1 and 5:1 for 1016 operation and 4:1 and 8:1 for "mono" operation.
After column has lined out switch controller to automatic red pointer should move up to correct reflux ratio immediately.
If a forecut is taken it will be necessary to observe the integration reading to know where to switch XCV-303-1 open to divert product to the receiver.
When the predetermining counter reaches the number of counts previously set, the reflux ratio will automatically move to the correct reflux ratio for the last half of the distillation step.
3.1.1 Startup Instructions
a. Set controller manual output on 0, with switch in manual position.
b. Set PCV-303.1 and PCV-303.2 in field cabinet.
c. Set counter to zero
d. Set predetermining register to correct setting.
3.1.2 Shut-Down Instructions
a. Switch "auto manual" switch to "manual" on FIC-303-1 with output at 0 to go on total reflux.
3.1.3 Manual Operating Instructions
a. Switch "auto manual" switch to "manual" to control flow through FV-303-1 to receiver.
3.2 INTERLOCKS
None.
ES 141 (8/69)
PCB-ARCH-EXT0372709
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Organic
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
246
2417
1.0 COLUMN TOP-PRODUCT DIVERTOR
CED LOOP NO.
XCV 303-1 & XCV 303- 2
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans___7/19/71
REV. BY
DATE
REV
SHEET
1 1 OF
These valves are needed to divert top product from the column (Item 301) to various locations depending on the product specifications.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
These valves enable the operator, at his discretion, to divert all product flow either to the MCS 1016 product receiver (Item 542, #4 product tank), to the light ends receiver (Item 328) or back to the column (Item 301).
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
Placing panel switch SS-5 in the "light ends" position opens valve XCV 303-2 and closes XCV 303-1.
All column top product then flows to the light ends receiver (item 328). Placing the switch in the "closed" position closes XCV 303-1 and XCV 303-2 and diverts all top product, as reflux, back to the column (Item 301). Placing the switch in the "product" position opens XCV 303-1 and closes XCV 303-2. This diverts all product to the #4 product tank (Item 542).
ES 141 (8/69)
PCB-ARCH-EXT0372711
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
246
2417
CED LOOP NO.
XCV 303-1 & XCV 303-2
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans
REV. BY
7/19/71
DATE
REV
SHEET
1
2 OF
3.0 OPERATION OF LOOP
3.1 NORMAL OPERATION
Typical.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATION
3.3.1 Air Failure
Air failure to the valves will cause both valves to close which puts column on total reflux.
3.3.2 Power Failure
Same as air failure.
ES 141 (8/69)
PCB-ARCH-EXT0372712
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Organic
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
1.0 STILL POT LEVEL CONTROLLER
CED LOOP NO.
LRC-305-3
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans
7/19/71
REV. BY
DATE
REV
SHEET
1 OF
This instrument serves two needs: a) level recording for 1016A and "mono"; and b) level control of still pot feed during 1016 semi-continuous operation and the chain feed part of the "mono" operation. This instrument allows a volume of crude feed to enter the still equal to the distillate volume drawn off via FIC 303-1.
1.1 DESCRIPTION
1.1.1 Function
a. To indicate, record the level of liquid in the still pot.
b. To control the level of liquid during semi-continuous operation.
c. To activate and alarm on high or low liquid level.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
A displacer type level transmitter senses the level and senses a 3-15 psig signal to the level indicating controller and also to the recorder. The controller compares this signal with a set point and send a 3-15 psig signal to control valve FV-305-3 to compensate for variations from the -set point.
Two pressure switches mounted in the field cabinet also receive this signal and sound an alarm in the control room upon high or low level.
Note: This level transmitter has been calibrated to give a 100% output for a 100% level on MCS-1016 operation. (Sp. gr. 1.178.) For mono operation the output would be about 76% assuming a gravity of .885, therefore a Foxboro computer has been added which will multiply the signal by a factor of 1.31 to bring the output to the panel indicator and the pressure switches up to 100% for 100% level during mono operation. A 3-way switch in the field cabinet must be placed in "mono" position during "mono" operation to accomplish this.
ES 141 (8/69)
PCB-ARCH-EXT0372713
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LRC-305-3
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/19/71
REV. BY
DATE
REV
SHEET
OF
3.0 OPERATION
Typical
.1 loop.
3.2 INTERLOCKS
^
- -
None.
' .
3.3 ABNORMAL OPERATIONS
.
3.3.1 Air Failure
Upon air failure to the loop the valve will close and the alarm will
sound.
.
.
.
3.3.2 Power Failure
- Upon power failure the alarm will be inoperative.-
....................... -
ES 141 (8/69)
PCB-ARCH-EXT0372714
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w* G*
BLDG/DEPT
811.00
Krummrich
AUTH NO.
2471
CED LOOP NO.
BA307-1
ISSUED BY
DATE
C. J. Hans 7/23/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET 1 OF
ES 141 l 8/69)
FURNACE - 307 - SHUTDOWN SYSTEM
1.0 NEED FOR LOOP
The purpose of this description is to define the furnace shutdown system. The purpose of the system is to protect the plant and personnel against abnormal operating conditions.
1.1 DESCRIPTION OF LOOP
The shutdown loop is composed of several components as follows:
1.1.1 BE 307-1
The furnace is provided with three (one for each burner) ultra-violet flame scanners. A failure of any burner flame will shutdown that furnace burner and signal a "furnace shutdown" alarm.
1.1.2 TIA 307-4
High stack temperature monitor (located in the field cabinet). High furnace stack temperature can be caused by excess fuel feed, abnormal firing conditions or a deficiency of circulating aroclor. Actuation of this alarm will signal a "furnace stack high temperature" alarm and a subsequent "furnace shutdown" alarm.
1.1.3 TJRIA-300-5 ,
Aroclor from furnace high temperature alarm... This alarm is actuated by an alarm contact, associated with point 5',' in multipoint recorder TJRI-300. High aroclor temperature can be caused by excess furnace fuel .feed, or low aroclor flow. Actuation of this alarm will signal a "aroclor from furnace high temperature" alarm and a subsequent "furnace shutdown" alarm.
1.1.4 FIA 307-5
This is a low flow alarm for aroclor flow through the furnace. Low aroclor flow can be caused by a blockage in the furnace, an aroclor leak in the furnace or a failure of circulating pump 306. The alarm contact is located in FIA 307-5. Actuation of this alarm will signal a "aroclor through furnace low flow" alarm and a subsequent "furnace shutdown" alarm.
1.1.5 TJRIA - 300 - 16
Non-condensables from vent cooler - 324 high temperature furnace shutdown. This shutdown is actuated by an alarm contact associated with point 16, in multipoint recorder TJRI-300. High temperature at this point could result in aroclor pollution of the atmosphere. An actuation of this alarm will signal a "furnace shutdown" alarm. In this case, however, the "furnace shutdown" alarm will be preceded by a "vent cooler exit high temperature" alarm.
PCB-ARCH-EXT0372715
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w* G* Krummrich
BLDG/DEPT
811.00
AUTH NO.
2471
CED LOOP NO.
BA-307-1
ISSUED BY .
C. J. Hans
DATE
PLANT LOOP NO.
7/23/1 1
REV. BY
DATE
REV
SHEET
OF
1.1 DESCRIPTION OF LOOP (Cont'd.)
1.1.6 Fuel Pressure Switches
Each burner has four pressure switches, high gas pressure, low gas pressure, low fuel oil pressure and low atomizing steam pressure. When operating on gas the gas pressure switches must be satisfied or the individual burner will shutdown. When operating on fuel oil the gas pressure switches are by passed, and the low fuel pressure and low atomizing steam pressure switches must be satisfied. Pressure switches on one burner do not effect the operation of the other burners. The "furnace shutdown" alarm will sound when the first burner is shutdown. Addition burner failures' -failures will not alarm in the control building but will alarm at the field cabinet.
ES 141 (8/69)
PCB-ARCH-EXT0372716
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
FIC-307-1
ISSUED BY
DATE
C. J. Hans 7/19/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
1
OF
1.0 FURNACE FUEL FLOW CONTROLLER
The fuel flow and thus the furnace firing level serves as the basis of the column vapor through-put. This is the primary instrument concerned with column capacity.
1.1.1 Function
The function of this loop is to control the flow of fuel: gas or fuel oil to the reboiler furnace.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The fuel gas flow is controlled by measuring the rate of flow in the line via an orifice plate and differential pressure transmitter. The' D/P transmitter sends a 3-15 psig signal to the indicating controller. The controller compares this signal with a set point and sends a carying 3-15 psig signal to the fuel' gas control valves to compensate for variation from the set point.
When using fuel oil the measurement is made using an integral orifice.
D/P transmitter, a switch on the field panel, selects either fuel
gas or fuel /'oil operation and at the same time selects the D/P
transmitter for that service, and either the fuel.`gas or fuel oil
control valves. One, two or three burners can be used. Each one
.
having its on control valve which can be selected from the field
panel.
ES 141 (8/69)
PCB-ARCH-EXT0372717
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Oraanic
plant w. O. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
3.0 OPERATION
CED LOOP NO.
PIC-307-1
ISSUED BY
C. ,T.
REV. BY
Hans
DATE
PLANT LOOP NO.
7/19/71
DATE
REV
SHEET
OF
3.1 NORMAL OPERATION
Typical flow control loop.
3.1.1 Startup
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATION
3.3.1 Air Failures
Air failure to the loop will cause the furnace to shutdown.
3.3.2 Power Failure
Power failure to the loop will cause the control valves to close shutting down the furnace.
ES 141 (8/69)
PCB-ARCH-EXT0372718
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w- G- Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LIA-312-3
ISSUED BY
DATE
C. J. Hans 7/29/71
REV, BY
DATE
PLANT LOOP NO.
REV
SHEET 1 OF
RESIDUE SURGE TANK LEVEL
1.0 NEED FOR LOOP
Residue from 1-312 is fed to the existing No. 2 still for distillation. Surge tank level must be known prior to pumping residue from the still pot after a column run.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to provide an indication of the residue surge tank level at both the control panel and in the field. Also to give an alarm on high or low level and to shutdown the still circulating pump on high level.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The level in the tank is sensed by a displacer type level transmitter which sends a 3-15 psig air signal to a 0-100% indicator on the control panel as well as a field mounted 0-100% indicator. This signal also sends an air signal to two pressure switches in the field panel. One switch is for low alarm and the other operates a relay which shuts down pump 1-306 and gives an alarm on high level.
ES 141 18/69)
PCB-ARCH-EXT0372719
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
ISSUED BY
LIA-312-3
DATE
C. J. Hans
REV. BY
7/29/71
DATE
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION
3.1 NORMAL OPERATION `
Typical level indicator loop.
3.2 INTERLOCKS
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
.
Air failure to this loop will cause loss of indication and an alarm indicating low level.
3.3.2 Power Failure
Power failure to the loop will cause the annunciator to be inoperative and pump 1-306 will shut down.
ES 141 <8/69)
PCB-ARCH-EXT0372720
L /A -3 ^ -3 .. fe io u e S y a .& f TXM. K . U v s L
PCB-ARCH-EXT0372721
Monsanto
DIVISION
Oraanic
INSTRUMENT FUNCTION OUTLINE
plant w* G* Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LI-316-1
ISSUED BY
DATE
C. J. Hans 7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
LL
O i--:
FUEL OIL STORAGE LEVEL
1.0 NEED FOR LOOP
A level gauge is needed for proper oil inventory control.
.
Fuel oil is needed as back-up fuel for the reboiler operation.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to provide an indication of the level of oil in the fuel oil storage tank and to actuate an alarm upon high or low level.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The level in the fuel oil tank is sensed by a diaphragm type level transmitter which sends a 3-15 psig proportional signal to a 0-100% indicator mounted near the tank. This signal is also sent to two pressure switches mounted in the field panel which actuate an alarm on high or low level.
ES 141 (8/69)
PCB-ARCH-EXT0372722
Monsanto
DIVISION
Orcranic
INSTRUMENT FUNCTION OUTLINE
plant
BLDG/DEPT
G- Krummrich
AUTH NO.
811.00
2417
CED LOOP NO.
LI-316-1
ISSUED BY
C. J. Hans
DATE
7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION 3.1 NORMAL OPERATION
Typical level loop. 3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS 3.3.1 Air Failure Air failure to the loop will cause loss of indication and low level alarm. 3.3.2 Power Failure Power failure will cause alarm to be inoperative.
ES 141 (8/69)
PCB-ARCH-EXT0372723
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LI-320-1
ISSUED BY
DATE
C. J. Hans
REV. BY
7/23/71
DATE
PLANT LOOP NO.
REV
SHEET
1 OF
lime slurry level indicator
1.0 NEED FOR LOOP
Slurry level indication is important in this tank as required lime concentrations will be made up according to this gauge. The lime will be added and mixed with the crude Aroclor by concentration.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to measure and indicate the level of slurry in the lime slurry tank.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
A displacer ~ :type level transmitter serves the level and sends a 3-15 PSIG signal to a receiver gauge, mounted near the vessel, which needs 0-100% level.
ES 141 (8/69)
PCB-ARCH-EXT0372724
Monsanto
DIVISION
Orqanic
INSTRUMENT FUNCTION OUTLINE
PLANT BLDG/DEPT
811.00
G* KrUIllIrlrich AUTH NO.
2417
CED LOOP NO.
LI-320-1
ISSUED BY
C. J. Hans
DATE
7/23/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
Typical level indicator loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
3.1.1 Air Failure
Upon air failure there will be no indication of level.
ES 141 (8/69)
PCB-ARCH-EXT0372725
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant
G* Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
TIC -325-3
ISSUED BY
C. J. Hans
DATE
7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
u. O -- i 1
TEMPERED WATER CONTROLLER
1.0 NEED FOR LOOP
Condenser cooling water must be heated and maintained at elevated temperatures for both the 1016 and "mono" operations to prevent freeze-ups in the condenser. Water must be controlled at the proper temperature to minimize "PCB" emissions to the atmosphere.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to maintain a constant temperature of the cooling water to the column condensor and to actuate an aiarm on high temperature @ 70C.
1.1.2 System Performance Required
The temperature should be maintained _+ 5C of set point (65C).
1.1.3 Accomplishment of Function
The temperature in the water line is sensed by a temperature indicating controller using a capillary bulb sensing element. The controller compares this temperature with a set point and sends a 3-51 psig air signal to a control valve to compensate for variations from the set point. As hot water leaves via the control valve, cold city make-up water enters the system in a equal volume.
ES 141 (8/69)
PCB-ARCH-EXT0372726
Monsanto
DIVISION
Oraanic
INSTRUMENT FUNCTION OUTLINE
m,,1T W. G. Krummrich
PLANT
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
TIC--325-3
ISSUED BY
DATE
C. J. Hans 7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION
3.1 NORMAL OPERATION
Typical local temperature control loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Air failure to the loop will cause the control valve to open.
3.3.2 Power Failure
Loss of power will cause the alarm to be inoperative.
ES 141 (8/69)
PCB-ARCH-EXT0372727
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
ISSUED BY
LIA-328
DATE
C. J. Hans
REV. BY
7/29/71
DATE
PLANT LOOP NO.
REV
SHEET
1 OF
LIGHT ENDS RECEIVER LEVEL
1.0 NEED FOR LOOP
Reliable level measurement is essential in this receiver for proper balance of light ends received from the column and LE1s feed to the chlorinators.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this instrument is to measure and indicate the level of material in the light ends receiver and to provide an alarm on high or low level.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
A diaphragm type level transmitter senses the liquid level in the tank and sends a proportional 3-15 psig air signal to a 0-100% indicator mounted near the transmitter. This signal is also sent to two pressure switches in the field cabinet which are set to provide an alarm at the panel on high or low level.
ES 141 (8/69)
PCB-ARCH-EXT0372728
Monsanto
DIVISION
Orcranic
INSTRUMENT FUNCTION OUTLINE
plant w* G* Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LIA-328
ISSUED BY
C. J. Hans
DATE
7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET OF
3.0 OPERATION
3.1 NORMAL OPERATION
Typical level loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Air failure to the loop will cause loss of indication and the low level alarm will actuate.
3.3.2 Power Failure
Power failure will cause alarms to be inoperative.
ES 141 (8/69)
PCB-ARCH-EXT0372729
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G* Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LIA-329-1
ISSUED BY
DATE
C. J. Hans 7/29/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET 1 OF
NO. 2 INTERMEDIATE STORAGE LEVEL
1.0 NEED FOR LOOP
The still pot is both batch charged and "chain" fed with Aroclors in this tank. Accurate level measurement is essential for this very active in-process tank for smooth refining operations.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to measure and indicate the level of material and to alarm on high level.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
A diaphragm type level transmitter senses the liquid level in the tank and sends a proportional 3-15 psig air signal to a 0-100% indicator on the panel and also one near the transmitter. This signal is also sent to a pressure switch which actuates an alarm on high level.
ES 141 ( 8/69)
PCB-ARCH-EXT0372730
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
CED LOOP NO.
LIA-329-1
ISSUED BY
C. J. Hans
7/29771 PLANT LOOP NO.
REV. BY
DATE
REV
SHEET OF
3.0 OPERATION 3.1 NORMAL OPERATION
Typical level loop. 3.2 INTERLOCKS
None. 3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure Air failure to the loop will cause loss of indication. 3.3.2 Power Failure Loss of power will cause alarm to be inoperative.
NOTE:
The zero of level transmitter should be set after N2 blanketing system is in operation. N2 enters and is regulated > 4" W.C. and relieves at 7" W.C. Since the low side is not compensated, it will be necessary to run the zero elevated () almost 5" W.C.
ES 141 (8/69)
PCB-ARCH-EXT0372731
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
...
PLAAN,,,TT W. G. Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
ISSUED BY
C. J.
REV. BY
ET C -- 349-1
DATE
Hans 7/19/71
DATE
PLANT LOOP NO.
REV
SHEET
1
OF
1.0 NO. 5 ABSORBER FEED FLOW CONTROLLER
This controller regulates the feed rate through and thus the AP across No. 5 absorber to allow the (exist) 538 feed pump to operate within its head-volume capability.
1.1 DESCRIPTION
1.1.1 Function
The function of this loop is to measure and control the flow by feed to No. 5 absorber and to provide an alarm on low flow.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The feed flow is controlled by measuring the rate of flow with an integral orifice differential pressure transmitter. The d/p transmitter sends a 3-15 psig signal to the indicating controller. This signal is compared to a set point and the controller sends a varying 3-15 psig signal to the control valve FV-349-1 to compen sate for variation from the setpoint.
A pressure switch activates an alarm on low flow.
ES ui (8/69)
PCB-ARCH-EXT0372732
Monsanto
INSTRUMENT FUNCTION OUTLINE
DIVISION
Orcranic
plant w. O. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2417
3.0 OPERATION
CED LOOP NO.
ISSUED BY
C. J. Hans
REV. BY
FIC-349-1
DATE
7/19/71
DATE
PLANT LOOP NO.
REV
SHEET OF
3.1 MANUAL OPERATION
Typical flow loop.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATION
3.3.1 Air Failures
Upon air failure to the loop the valve will close and the alarm will sound.
3.3.2 Power Failure
Upon power failure the alarm will be inoperative.
ES 141 (8/69)
PCB-ARCH-EXT0372733
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2471
CED LOOP NO.
KIC-352-1
ISSUED BY
DATE
C. J. Hans 7/23/71
REV. BY
DATE
PLANT LOOP NO.
REV
SHEET
1 OF
SLURRY CONTROL VALVE TIMER
1.0 NEED FOR LOOP
Allow lime slurry to be mixed on a semi-continuous basis with the crude Aroclors on the way to intermediate storage. Lime mixing on this basis is necessary to neutralize essentially all the HCL dissolved in the Aroclors prior to charging the Aroclors to the still pot. This in turn is required to minimize the potential of chloride stress corrosion cracking in the 316 SS column.
1.1, DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to control the flow rate by lime slurry addition to the product going to intermediate storage.
1.1.2 System Performance Required
1.1.3 Accomplishment of Function
The flow rate is adjusted by two timers mounted on the panel which control the amount of time a pneumatic actuated ball valve is open and how long it is closed each cycle. The valve is continuously cycled open and closed after the open-close selector switche is turned to "open".
ES 141 (8/69)
PCB-ARCH-EXT0372734
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2471
CED LOOP NO.
KIC-352-1
ISSUED BY
DATE
C. J. Hans
REV. BY
7/23/71
DATE
PLANT LOOP NO.
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
The slurry timer is turned on during the time material is going to intermediate storage from the chlorinators.
3.1.1 Startup Instructions
Set "open" timer for number of seconds valve is to be open (0-6 sec.) Set"cycle"timer for number of minutes valve is to be closed (0-6 min.) Turn selector switch to "open" position.
3.1.2 Shut-Down Instructions
Turn selector switch to close position.
3.2 INTERLOCKS
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Upon air failure valve will fail closed.
3.3.2 Power Failure
Upon power failure valve will fail closed.
ES 141 (8/69)
PCB-ARCH-EXT0372735
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w- G- Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
FIC-406-1 & Existing FICA-7
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/23/71
REV. BY
DATE
REV
SHEET
1 OF
#6 CHLORINATOR' BIPHENYL FEED CONTROLLER
1.0 NEED FOR LOOP
This loop is needed to assure that the proper amount of Biphenyl is added to the chlorinator. The parallel feed controller is needed to maximize the production of "mono" in the column system. The flow through-put of the existing FT-7 was too small to perform this function.
1.1 FUNCTION
1.1.1 Function
The function of this loop is to control the rate of flow of Biphenyl into the chlorinator and sound an alarm on low flow.
1.1.2 System Performance Required
The flow rate should be maintained + 1/8 GPM of set point.
1.1.3 Accomplishment of Function
The Biphenyl flow rate is controlled by measuring the rate of flow in the line and transmitting an air signal proportional to this rate to an indicating controller; the measuring and transmitting is done by one of two differential pressure transmitters. One measures the flow across an orifice plate in the line for the "mono" operation and the other has an integral orifice for measuring the smaller flow in the 1016 operation. The indicating controller compares the air signal with a set point flow rate and sends a varying 3-15 psig signal to the Biphenyl control valve to compensate for variations from the set point. The transmitter also eeds an air signal to a pressure switch which activates an alarm on low flow. The flow is also field indicated at #6 chlorimator and at the Biphenyl feed pump pushbutton.
ES 141 (8/69)
PCB-ARCH-EXT0372736
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
.
FIC-406-1 & Existing FICA-7
ISSUED BY
C. J. Hans
DATE
PLANT LOOP NO.
7/23/71
REV. BY
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
a. 1016 Operation
1. Set selector switch in field to " 1016' ' portion 2. Close valve to FT-406-1 3. Open valve to FT-7 4. Set controller set point to flow rate desired and place
controller in "auto"position. 5. Open block valves in feed line
b. "Mono" Operation
1. Set selector switch in field to "Mono" position 2. Close valve to FT-7 3. Open valve to FT-406-1 4. Set controller set point to desired flow rate and place
controller in "auto" position. 5. Open block valves in feed line.
3.1.1 Start-up
Same as above plus alarms should be checked.
3.1.2 Shutdown
a. Set FIC-7 set point to 0.
b. Close block valves in Biphenyl feed line
3.1.3 Manual Operating Instructions
a. Set FIC-7 on manual and control flow through FV-7 to #6 chlorinator by adjusting air output to valve.
3.2 INTERLOCKS
None.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Air failure to the loop will cause control valve FV-7 to close.
3.3.2 Power
Power failure will cause the annunciator to be inoperative. The control valve will continue to operate.
ES 141 (8/69)
PCB-ARCH-EXT0372737
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2471
CED LOOP NO.
FIC-414-1
ISSUED BY
C. J. Hans
REV. BY
DATE
PLANT LOOP NO.
7/23/71
DATE
REV
SHEET
1 OF
#8 CHLORINATOR CHLORINE FEED
1.0 NEED FOR LOOP
This new controller is required to accept the pneumatic output from the existing densitrol so as to make the required gravity Aroclor material in No. 8 unit for "mono" operation only. The Aroclor 1105 feed (for "mono") gravity is finished off in No^ 8 chlorinator so that No. 9 chlorinator can be used for blowing (de-gassing).
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to control the flow rate of chlorine to #8 chlorinator by using the density measurement to reset the set point when on "mono" operation.
For operation on "1016" refer to IFO FIC-10.
1.1.2 System Performance Required
The flow rate schould be + 1% of set point.
1.1,3. Accomplishment of Function
The chlorine flow is controlled by measuring the rate of flow in the line using an orifice plate and a differential pressure transmitter. The D/P transmitter sends an air signal (3-15 PSIG) proportional to the flow rate to the indicating controller. The controller compares this signal with a set point flow rate which is determined by a density indicating controller (DIC-39). The controller sends a varying 3-15 PSIG signal to the chlorine control valve to compensate for variation from the set point.
ES 141 (8/69)
PCB-ARCH-EXT0372738
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
AUTH NO.
811.00
2471
CED LOOP NO.
FIC-414-1
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans
REV. BY
7/23/71
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
Set the specific gravity controller for #8 chlorinator in "auto". The set point will be determined by supervision. The densitrol will adjust the chlorine feed automatically to #8 to maintain the indicated specific gravity. Note: The range of the densitrol for "mono" operation is /, o/Q to I > pLo .
3.1.1 Startup instructions
a. Open manual valves in chlorine feed line. b. Bring specific gravity up to desired level with controller
"local-remote" in "local" position and on "auto. c. When desired level is reached switch to "remote" to allow DIC-39
to adjust set point. d. Check specific gravity manually every 2 hours.
3.1.2 Shut-Down Instructions
a. Close chlorine valves to distributor. b. Switch controller to local and move set point to "0".
3.1.3 Manual Operating Instructions
Place controller in "local" and "manual". Adjust air to regulate control valve opening.
3.2 INTERLOCKS
There are two interlocks on this system. (1) Cln valve will not operate if circ. pump is down, (2) on high temperature the Cl2 valve will not operate (Hi temp, is 205C). The reset button on panel board must be pushed after interlock has come in.
3.3 ABNORMAL OPERATIONS
3.3.1 Air Failure
Air failure to the loop will cause the feed valve to close and instru ment will indicate no flow.
3.3.2 Power Failure
Power failure to the loop will cause the feed valve to close due to the interlock with chlorine pump. The instrument will indicate zero flow.
ES 141 (8/69)
PCB-ARCH-EXT0372739
Monsanto
DIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant w- G* Krummrich
BLDG/DEPT
AUTH NO.
811.00
2471
CED LOOP NO.
ISSUED BY
FT--418 --1 ____________________________
DATE
PLANT LOOP NO.
C. J. Hans 7/23/71
REV. BY
DATE
REV
SHEET
OF
3.0 OPERATION
3.1 NORMAL OPERATION
a. Close chlorine block valve ahead of control valve. b. Open N2 block valve ahead of control valve. c. Set selector switch in field to "Ng"d. Set controller "local remote" switch to "local". e. Adjust setpoint as required for "mono" operation. f. Open N2 feed valve.
3.1.1 Startup Instructions
Same as above.
3.1.2 Shut-Down Instructions
Close N2 valves to distributor and set controller set point to "0".
3.1.3 Manual Operating Instructions
Set controller to "manual" and adjust air to FV-11.
3.2 INTERLOCKS
'.
/
Same as FIC-11
3.3 ABNORMAL OPERATIONS
Same as FIC-11.
ES 141 (8/69)
PCB-ARCH-EXT0372741
Monsanto
OIVISION
Organic
INSTRUMENT FUNCTION OUTLINE
plant W. G. Krummrich
BLDG/DEPT
811.00
AUTH NO.
2417
CED LOOP NO.
.
FICA-541-1 & FICA-32
ISSUED BY
DATE
PLANT LOOP NO.
C. J. Hans 7/29/71
REV. BY
DATE
REV
SHEET 1 OF
#2 AND #3 ABSORBERS INLET FLOW CONTROL & ALARM
1.0 NEED FOR LOOP .
This loop is needed to insure proper flow of aroclor to the absorber.
1.1 DESCRIPTION OF LOOP
1.1.1 Function
The function of this loop is to control the flow of material into the absorbers and to sound an alarm if flow is too low.
1.1.2 System Performance Required
The flow rate should be maintained +. ^ GPM of set point.
1.1.3 Accomplishment of Function
The flow rate is sensed by a differential pressure transmitter across an orifice plate in the line. The transmitter sends a 3-15 psig air signal to a flow indicating controller. The controller compares this signal to a set point and sends a 3-15 psig air signal to a control valve to compensate for variation from set point. The transmitter also sends an air signal to a pressure switch which activates an alarm on low flow.
ES 141 (8/69)
PCB-ARCH-EXT0372742