A GUIDE TO
THE APPLICATION AND INSTALLATION OF
LARGE BOILERS IN
HYDRONIC HEATING SYSTEMS
Sales Personnel Development Unit American-Standard. Plumbing and Heating Division
40 West Uoth Street New York l8, New York
Form No. SPD-6313 July 1, 1963
Copyright 1963 American Radiator & Standard Sanitary Corporation
17566
FOREWORD
To the Field Sales Personnel
"No salesmen ever lost an order because he knew too much about his product."
This Guide has been prepared to aid field sales personnel in the application, installation and sale of American-Standard cast iron boilerB, especially the &-4o, G-6o, A-5 and A-7-
Fundamentals of heat, pressure, combustion and electricity have been covered for background.
In a few instances complete technical and scientific accuracy have been sacrificed in the interest of simplicity and brevity. Such omissions have no practical effect upon the understanding of funda mentals in the ranges of temperature and pressure applicable to large boilers.
The technical and practical information on steam systems, hot water systems, manifolding and breeching sizing, to name a few subjects, should be helpful in guiding the contractor, the architect and the consulting engineer on boiler replacement as well as new in stallations .
Certain special applications are discussed, the theory explained and tables prepared to simplify the arithmetic required for an accurate engineering approach to the problem.
It is suggested that you study the Guide and use it in its pres ent tentative form. During the next year additional Chapters may be required. Perhaps some of its present Chapters will need expanding. Whatever the action taken will depend on the Guide's usefulness to you.
17567
TABLE OF CONTENTS
Chapter 1 Fundamentals of Heat " 2 Fundamentals of Pressure " 3 Fundamentals of Combustion
v' ! Fundamentals of Electricity Control Circuits " 6 Basic Control Systems " 7 Heating Control Systems -- Large Buildings " 8 Cast Iron vs Steel Boilers " 9 Stoker-Fired Boilers " 10 Oil Fired Boilers " 11 Indirect Domestic Hot Water Heaters " 12 How the Steam System Works " 13 Steam Accessories 14 Steam Piping Details and Terminology 15 Sizing the Piping " 16 Pressure Steam Systems " IT Steam Systems -- Pressure Below Atmosphere " 18 Steam Boiler Manifold Sizing " 19 Hot Water -- Forced Circulation 20 Hot Water -- Sizing and Location of Pump 21 Hot 'Water -- Sizing the Expansion Tank 22 Hot Water -- Boiler Manifold Sizing 23 Converters 24 Sizing the Boiler 25 Sizing -- Chimney and Breeching
17568
TABLE OF CONTENTS (Cont'd)
Chapter 26 II 27 *1 28 II 29 II 30 II 31 M 32 U 33
Locating the Boiler Blast Coils and Unit Heaters Domestic Hot Water Greenhouse Heating Heating Swimming Pools Maintenance Competitive Comparisons Getting the Order
17569
CHAPTER 1
FUNDAMENTALS OF HEAT
17570
CHAPTER 1
FUNDAMENTALS OF HEAT
Including several ways of looking at heat... how it is measured...and how it is trans ferred.
We measure the intensity of heat with a thermometer. The thermometer tells "how hot" a substance is. It does not tell us how much heat the sub stance contains.
Obviously two quarts of boiling water hold more heat than a cupful... but the thermometer in each case reads 212F.
We measure the quantity of heat in btu's (British Thermal Units). This measurement is based on two factors:
1) The temperature (Fahrenheit) or intensity of the heat in a substance.
2) The weight of the substance in pounds.
We can then use the btu to measure the heating power of fuels, heat losses and gains in buildings, the heat-carrying capacity of pipes, the capacity of boilers, etc.
One btu is the quantity of heat needed to raise one pound of water one degree fahrenheit. Two btu's will raise two pounds of water one degree or one pound of water two degrees.
How many btu's are required to heat 12 pounds of water at 32F to
18oF?
Y equals 12 (pounds of water) x 1 x (180-32) Y equals 12 x 1 x 148 Y equals 1776 btu's
So far we have discussed btu's as a measurement of the quantity of heat needed to raise temperatures. Actually it is a measurement of the quantity of heat exchanged.
If we take one pound of water at 70F, put it on the stove and heat it to the boiling point, we will have used 14-2 btu's (212-70). If we then set the one pound of boiling water on a counter, it will liberate or give off 142 btu's, a6 it cools back to 70F.
This experiment demonstrates two things:
1) The law of heat exchange; heat lost : heat gained.
2) The fact that heat flows when there is a difference in temperature... from the warmer to the cooler substance.
Page 1-1
17571
Specific Heat
Different substances have different capacities for absorbing (and giving off) heat. This capacity depends upon the specific heat. Specific heat is the number of btu's required to raise one pound of the substance 1F.
Water, in the temperature ranges encountered in low temperature hot water heating, has a specific heat of one.
A cubic foot of water at atmospheric pressure and 70F weighs 62.27 lbs. This water heated to 170F absorbs 6227 btu or approximately 3460 times the heat absorption of air.
This explains in part why warm air systems need large ducts as com pared with the small pipes needed in hot water systems.
The State of a Substance
Practically all substances can exist in more than one state. Metals are solid, or, when they are melted, liquid. If heated to a high enough temperature, they will vaporize. Water, our main interest, also exists in three states; at a pressure of 29*92 inches of mercury it is solid, as ice, at 32F and below...liquid, as water, from 32F and through 2120F...and in a gaseous state, steam, at 212F and above. These temperature limits will change under pressure. We'll get to that in the next chapter.
Sensible Heat (or Enthalpy) and Latent Heat
First; the new word, "enthalpy". The dictionary defines it as, "the sum of the internal and the external energies of a fluid system; thermodynamic potential at constant pressure."
Because we are more interested in the heat potential or the ability to heat than we are in the inherent heat of the liquid, enthalpy is a more exact definition. However, some engineers (usually the older ones) will use the word "heat" usually in the phrase "heat content" while some (usually the younger ones) will use the word "enthalpy". Despite the difference in dictionary definition, they are both talking about the same thing.
Sensible heat is the heat required to change the temperature of sub stance. It gets its name from the fact that this form of heat can be sensed or felt. In measuring the sensible heat of a substance, this measurement must be made from some base temperature. With water a base temperature of 32F is used, since this temperature is the lowest at which water can exist in the liquid state under standard atmospheric pressure. The sensible heat or enthalpy of one pound of water at l80F is approximately 148 btu. Two pounds of water at l80F would contain twice 148 btu, or approximately 296 btu cf sensible heat or enthalpy.
Latent heat...or enthalpy...is heat that cannot be sensed, or felt. It is heat used to change a substance from one state to another.
17572
Page 1-2
Boiling water must be kept boiling by the application of heat to change it into steam. But because the temperature of both the water and. the 6team remain the same during boiling, this heat cannot be sensed, or felt. It is hidden or latent heat.
Thi6 latent heat put into boiling the water jLs then recovered, in a steam system, as the steam in the radiators condenses back into the liquid state.
The quantity of heat required to change one pound of boiling water into steam (970.3 btu at atmospheric pressure) is called the "latent enthalpy of vaporization" or just "enthalpy of vaporization". Again, some older engineers may substitute the word "heat"I
Steam; Saturated and Superheated
During boiling, steam rises from the surface of the water at the same temperature as the water and Is called saturated steam. Its enthalpy con tent is equal to the sensible enthalpy of the water plus the latent enthalpy of evaporation.
Superheated steam is steam that has been removed from the presence of the boiling water by the steam main and then put through a series of tubes called a superheater. The tubes are then heated...the steam absorbs the additional heat and becomes superheated.
Additional heat cannot be applied to the steam in the presence of the water because the added heat would result only in the boiling of more water.
To see the effect of heat on water, let's apply heat to one pound of water at 32F, at atmospheric pressure.
Page 1-3
17573
Raising one pound, of water from 32F to 212F requires 180 btu of sensible heat. To boil the water completely into steam requires 970.3 btu of latent heat. Because the specific heat of superheated 6team under these conditions is 0.48 only 8.64 btu of sensible heat is required. (230-212 x 1 x 0.48 8.64)
Thus, the total enthalpy of the saturated steam equals:
The enthalpy of the liquid -- 180.0 btu plus the enthalpy of vaporization -- 970.3
OR 1,150.3 btu
And the total enthalpy of the superheated steam equals;
The enthalpy of the liquid -- 180.0 btu
plus the enthalpy of vaporization -- 970-3
plus the enthalpy of superheat --
8.64
OR 1,158.94 btu
These figures are true at atmospheric pressure only. Variations in pressure will vary the temperature at which water boil6 and so, also vary the sensible, latent and total enthalpies.
Equivalent Direct Radiation (EDR) Steam
Steam heating boilers and radiation are rated in square feet of equivalent direct radiation (EDR). One EDR of steam equals 240 btu per hour.
In the early days of steam heating, the old large column radiators gave off 240 btu per hour per square foot of surface, when tested with steam at 215F.
Modern radiation, being much more efficient, has changed the numbers but the theory remains the same.
Today's radiation i6 tested with steam under carefully maintained code conditions to determine its capacity in btu/hr. This figure is then divided by the old standard of 240 btu/hr. per square foot. The resultant figure is a rating in "square feet of radiation" (or EDR).
Though it has no relation to the actual square feet of surface under test, it does provide a standard to measure the capacity of various kinds and types of radiation and boilers.
Page 1-4
17574
UBlng EDR to Compute Relationship Between Radiation and Boiler
To convert one pound of boiling water to one pound of steam at 215F requires a latent enthalpy of 968.4 btu.
The steam, as it condenses in the radiator, will of course deliver 968.4 btu through the radiation to the space to be heated.
Since one square foot of EDR equals 24-0 btu hr...4 square feet of EDR equals 960 btu/hr...or 4 square feet of EDR approximates the heat delivered by one pound of steam at 215F.
EXAMPLE
How many pounds of steam must a boiler make to carry the load of 1600 square feet of radiation'
1600 sq. ft._______ 4 sq. ft./lb. of steam
Equals 400 lbs. of steam/hr.
EXAMPLE
Specifications for a boiler state that it has the capacity to deliver 500 lbs. of steam per hour. What is the boiler's capacity in square feet of radiation?
500 lbs. steam/hr. x 4 sq. ft./lb. equals 2,000 sq. ft.
Page 1-5
17575
CHAPTER 2
FUNDAMENTALS OF PRESSURE
17576
CHAPTER 2
FUNDAMENTALS OF PRESSURE
"Pressure", like many words in the English language, has many variations. For instance, "moral pressure", "pressure group", "pressing", "squeezing", "weight or burden", etc.
However, in this text, we are interested in the "mechanical" definition; "a force in the nature of a thrust, distributed over a surface".
In discussions of boilers, piping, radiation, etc., we can precisely measure pressure by measuring both the force and the area against which it is exerted.
Probably the most common expression of pressure is in "pounds per square inch"...or p.s.i.
Other ways to measure and state the force of a pressure are based on the weight of water and mercury.
Water; 62F
Mercury; 32F
FIGURE 2-1
Assume two tanks 12" x 12" x 12"...one filled with water, one with mercury. Figure 2-1. We also assume water temperature of 62F and mer cury temperature of 32F. These are arbitrarily chosen standards to es tablish a definite relationship between weight and volume. Heated above 32F, for instance, the mercury would expand and run over the sides of the tank. We would still have the same volume but less weight.
Page 2-1
17577
Water: 62F
Mercury; 32F
62.37 lbs.
848.2 lbs.
62.37 lbs. per sq. ft. Total Pressure at Bottom 848.2 lbs. per sq. ft.
62.37
iwr~
=
.433
Pressure lb6. per sq. in. 848 . 2 155--
5.89
We now 6ee that 12 inches, or one foot column of water, exerts a pressure of .433 p.s.i. while one foot of mercury equals 5.89 p.s.i.
By computation, then, we can set up other standards:
If 1 foot of water equals .433 p.s.i., then 1 -f .433 or 2.31 feet
(27.72") of water = 1 p.s.i.
If 1 foot of mercury equals 5*89 p.s.i., then 1 -1 5.89 or .17 feet (or 2.036") of mercury = 1 p.s.i.
Also 589 p.s.i. .491 p.s.i.
12 will give the pressure 1 inch of mercury,
We now have four different methods of expressing or defining "pressure";
1. Pounds per square inch
2. Inches of water
3- Feet of water 4. Inches of mercury
Why four? Basically, for the same reasons that 6pace engineers discuss the dimensions of electronic components in "tenths of an inch"...the speed of supersonic aircraft in terms of "mach"...the distance between stars in terms of "light years"...to give them more practical and manageable figures to work with.
The selection of any of the four expressions for pressure is determined by the size of the force being defined.
For instance, boiler pressure, when greater than the atmosphere, is a large pressure and is expressed in "pounds per square inch", while the draft in a boiler is such an extremely small pressure, it is expressed in "inches of water", which, even then, usually turns out to be only a fraction.
The expressions "greater than atmosphere" and "less than atmosphere" are quite common. They point to the importance of the atmosphere in pressure measurements.
Page 2-2
17578
Atmospheric pressure is all around us. We live at the bottom of an ocean of air, which most time goes unnoticed. It seems to be a relatively light pressure, because we've grown used to it, and because it exert6 equal pressure on all sides.
Atmospheric pressure is often referred to as barometric pressure, be cause it is measured with a barometer. The simplest barometer is a mercury barometer -- Figure 2-2
Take a glass tube, fill it with mercury...heat it to drive off air bubbles created in the filling process...put jour finger over the open end to keep the mercury from running out...bury the open end in a pool of mercury open to the atmosphere...bring the tube to a vertical position... arrsinge a scale 60 you can read the height of the mercury in the tube above the mercury in the pool ...and you have a mercury barometer.
Some of the mercury will run out of the tube into the pool, leav ing a vacuum at the top of the tube.
How much will run out? Ju6t enough so as to leave the mercury in the column with weight enough to ex ert the same pressure as the pressure of the atmosphere on the surface of the pool surrounding the base of the tube.
FIGURE 2-2
Because stormy weather i6 pre ceded by a drop in atmospheric pres sure which causes "a falling glass" and clearing weather with a rise in atmospheric pressure causing "a ris ing glass"...the barometer is a basic instrument in weather forcasting.
In Figure 2-3 we show 29.92 inches because that is the height of the mercury column under average conditions at sea level...and represents the equivalent pressure of 14.696 p.s.i. which is the pressure of a "standard atmosphere".
Page 2-3
17579
Standard Pressure Sea Level r~
Pressure 5,000 ft Elevation
25" Hg
29.92" Hg
Absolute Zero Pressure FIGURE 2-3
At higher altitudes, because the amount of air above you is less, the atmospheric pressure is less. In Denver, Colorado, for instance, under average conditions the mercury column is approximately 25 inches high.
The readings in p.s.i. are ob tained by multiplying the height of the column in inches by the density of mercury (.4-91 Its. per cubic inch). This chart shows an atmospheric pres sure of 14.696 p.s.i. at sea level and 12.279 at Denver.
Hg is the chemical symbol for Mercury.
Both of these pressures are measurements from an absolute zero pressure line and so they are ( as are all barometric readings) abso lute pressures.
Gage and Vacuum Pressure
The pressures inside a heating system are limited by the design of the equipment and the temperature at which it works. They are called gage pres sures because they are measured by a gage.
The most common gage is the Bourdon Tube, usually made of 6teel, and oval in its cross section.
Pressure from the boiler, fill ing the tube, tends to straighten it out, while atmospheric pressure, pushing on the outside, tends to make it curl up.
Actually, then, the tube takes a position determined by the differ ence between the boiler pressure and the atmospheric pressure.
FIGURE 2-4
Page 2-4
17580
By connecting the end of the Bourdon Tube in Figure 2-5 via link age (A) to quadrant (B), which meshes with a small pinion gear (C) mounted on a shaft which carries pointer (D), we can calibrate a scale (E) to read the gage pressure.
FIGURE 2-5
In Figure 2-6 we show the indicator at zero, which means that boiler pres sure is exactly compensating for the atmospheric pressure and precisely can celling it out.
We can now finish calibrating our scale both up (when boiler pressure ex ceeds atmospheric pressure) and down (when boiler pressure falls below at mospheric pressure, creating a negative pressure or vacuum).
Arbitrarily, pressures above at mosphere are expressed in "pounds per square inch"...pressures below atmos phere are expressed in "inches of mer cury. "
FIGURE 2-6
Boiler pressure 16 then added to (in the case of gage pressure) or subtracted from (in the case of vacuum pressure) the existing atmospheric pressure, to arrive at the total or "absolute pressure" affecting the system.
Page 2-5
17581
Atmospheric Pressure
Approx. 30" Hg
or 14.7 psi
Starting at sea level. Figure 2-7, with no pressure added or subtracted by the functioning of the system, it is subject only to atmospheric pres sure of 14.7 p.s.i. (rounding off 14.696), or 30 inches of mercury (rounding off 29.92).
To denote gage pressure we add the letter "g" to our abbreviation "p.s.i.".
Absolute Zero Pressure
FIGURE 2-7
Boiler Pressure
Atmospheric Pressure
.Vacuum
5" Hg
i
1
Gage Pressure
5 psig
.
Approx. 30" Hg
14.7 psi
Absolute Pressure
25" Hg
Absolute Pressure 19-7 psi
__ ___
Absolute Zero Pressure
If the system then develops 5 p.s.i.g. of internal pressure, Figure 2-8, thi6 gage pressure must be added to the atmospheric pressure to get the absolute pressure (19-7 p.s.i.) etc.
If the system builds up a vacuum, or negative pressure equal to the weight of 5 inches of mercury, we will have a drop in absolute pressure from 30 inches Hg to 25 inches Hg and so on.
FIGURE 8-8
Page 2-6
17582
Importance of Pressure The knowledge of these pressures and how they are determined is important
since the absolute pressure on a liquid determines its boiling temperature. This phenomenon holds true whether the liquid be water, Freon or a metallic liquid such as mercury.
For practical purposes particularly at elevations near sea level, boiling temperatures can be related to gage pressure. However, the atmos pheric pressure diminishes about 4$ for each 1,000 feet above sea level. Consequently, to get a reasonably accurate estimate of boiling temperatures, pressures must be corrected to absolute.
Page 2-7
17583
CHAPTER 3
FUNDAMENTALS OF COMBUSTION
17584
CHAPTER 3
FUNDAMENTALS OF COMBUSTTOW
Combustion... or burning...i6 the rapid oxidation of a substance and characteristically the result is the production of heat and light.
The word "oxidation" here means the combining of oxygen with another substance to form a third substance.
The combustion process, when methane gas iB used as a fuel, can be expressed as:
CH4 + 2 02 -->
C02 + 2 H20
These symbols mean; CH4 equals 1 cu. ft. of Methane (CH^) 2 02 equals 2 cu. ft. of Oxygen (02) CO2 equals 1 cu. ft. of Carbon Dioxide (COg) 2 HgO equals 2 cu. ft. of water (E^O)
So the equation now reads, "Combine one cubic foot of methane with 2 cubic feet of oxygen and the resultant combustion will leave one cubic foot of carbon dioxide and 2 cubic feet of water (in the form of steam) as flue gases.
Because the only practical way to get the oxygen is from the air around us, and because oxygen is only 21$ of air by volume, we must, in theory, introduce 4-3/4 cubic feet of air into the system for every cubic foot of oxygen required, or 9-l/2 cubic feet of air to supply the 2 cubic feet of oxygen called for in our equation. The other 79$ of the air is assumed to be nitrogen.
The left hand side of the equation now reads;
CH4 + 9-5 Air
But because we are primarily interested in the 2 cubic feet of oxygen, we separate it and the 7.5 cubic feet of nitrogen and write the equation this way;
CHj^ + 2 Og + 7-5 N2 --) C02 + 2 HgO + 7-^ N2
Page 3-1
17585
Nov the formula says that when 1 cubic foot of methane (CH^) is burned with 9-5 cubic feet of air the resultant flue gases are 1 cubic foot of CCg, 2 cubic feet of steam and 7-5 cubic feet of nitrogen. The nitrogen does not join in the combustion process, but is heated along with the CO^ and the HpO. The heat that these products carry off is called stack loss.
The above formula represents perfect or theoretical combustion.
As a practical matter, theoretical perfection i6 impossible to attain. Therefore, in order to insure that every molecule of Methane is furnished the proper number of molecules of oxygen, excess air is introduced into the system to furnish additional oxygen.
W'i+h natural draft gas burners, approximately 50$ excess air is added.
Since the excess air, representing a safety factor, is not used up in the combustion process, it is added to the flue gases...and increases the stack losses.
That's why 50$ excess air is used, not more. Obviously 70$ excess air would contain even more oxygen and represent an even greater safety factor.
But it would also represent extra gases to absorb more heat and create a higher chimney loss.
Adding surplus gases of any kind to the combustion products loses heat two ways;
1. In just heating more flue gases 2. All boilers have flues to hold the hot gases in the boiler so that
the water jacket can absorb more of their heat before they are vented. As the quantity of flue gases increase the velocityof the gases through the flues increases. The gases moving through the flues faster have less time to give uptheir heat to the boiler surface and consequently go up the chimney at higher tem peratures, thus increasing the stack loss. Stack temperatures from a given boiler have a direct relationship with the amount of flue gases going through it.
Nov, let's look at cur foimuia for perfect turning again, CH, + 2 02 + A) II? --> C02 + 2 H20 + 7-3 II
and add the 50$ air for complete practical burning. C.\ + 3 Op + 11.2? :i2 --) co2 + 2 h2o + 11.23 u2 +
o2
If;-.; v/e nave 15.25 cubic feet cf flue gas.
Page 5-2
17586
If a COg analysis was made on the products of combustion for perfect combustion conditions, this analysis would show 11.8$ COg by volume. See the following tabulation;
Perfect Combustion
C02 1.0 cu. ft.
$ by
Volume
11. a*
(Steam) H20
2.0 cu. ft.
n2 7-5 cu. ft.
2 0.0 cu. ft.
TOTAL 10.5 cu. ft. Less H20 2.0
88.2$
Total Dry products of Combustion. . .
LPv
GO
cu. ft.
100.056
NOTE; When flue gas analyses are made, the steam condenses making it impossible to obtain its volume.
Similarly the percentage of CO2 by volume analysis for practical or complete combustion of this gas becomes 7*5^ as shown in the following tabulation;
Practical or Complete Combustion
co2 1.0 cu. ft.
f> by
Volume
7.55*
(Steam) H20
2.0 cu. ft.
11.25 cu. ft
84.90
2 1.0 cu. ft.
TOTAL 15.25 *Less H20 2.0
7-55
Total Dry products of Combustion............. 13*25 cu. ft
100.0
NOTE; When flue gas analyses are made, the steam condenses making it impossible to obtain its volume.
It is evident that as the percentage of C02 in the flue gases diminishes when burning a given fuel, the amount of' excess air is in creasing. Hence, the C02 percentage becomes a measure of the amount of excess air and, when combined in a formula or with curves of 6tack tem perature gives a basis for determining the boiler efficiency.
Page 3-3
17587
When analyzing flue gases the percentage of CO2 which is obtainable under practical or complete combustion conditions varies with the kind of fuel due to the different percentages of carbon in these fuels. As the carbon content becomes larger so does the per cent of 009. The type of fuel burning equipment plays a part.
For natural gas, C02 readings for practical combustion conditions may range from 8$ to 10$, for oil 9$ to 11$ and for coal (stoker fired) 12$ to 13$.
It has been pointed out earlier in this chapter that complete com bustion of all the oxidizable elements in the fuel is desirable. To accomplish thi6 complete combustion excess air must be added.
'When fuel is not burned completely, heat is lost. Should insufficient air cause the carbon in the fuel to burn to carbon monoxide (CO) not only is a poisonous gas formed but only 5;500 btu per pound of carbon are released. One pound of carbon burning to COg releases 14,600 btu.
A similar result occurs with the hydrogen in the fuel. If sufficient oxygen is present to burn one pound of hydrogen to water vapor, 62,000 btu are released. When insufficient air is present to burn all the hydrogen, the unburned percentage escapes up the chimney and a proportionate amount of heat is lost.
The burning of oil efficiently presents a greater problem than burning the other two fuels. First the oil must be atomized into very small droplets. This is done by the nozzle. Secondly, the oil droplets must be vaporized. This action is accomplished by the combustion chamber walls. The air which is mixed with the vaporized oil now is able to burn it.
Materials used in combustion chambers vary from stainless steel and light-weight refractory materials to fire brick. Dense fire brick is usually employed where oil is being burned continuously.
Intermittent firing such as practiced with American-Standard boilers requires light-weight materials for combustion chambers. The quicker the combustion chamber walls become incandescent, following the starting of the burner, the quicker the combustion conditions reach maximum efficiency.
Page S*4
17588
chapter a
fundamentals of electricity
17589
CHAPTER 4
FPSPAMEMTALfi OF EUiCTRICITY
An electric current is formed, by the movement of electrons.
Because electrons move easily in metals; silver, copper, aluminum, etc., they are used to "conduct" electricity from source to load.
Because electrons do not move easily in such materials as glass, porcelain, cotton and rubber, they are used as insulation.
The flow of electric current in a circuit is analagous to the flow of water in a piping system.
The pressure or force making the current flow is supplied by a gen erator or a battery.
Wire size and length of the circuit determine the quantity of electri city flowing.
Large wires have less resistance to current flow than small ones.
The terminology in electricity is as follows;
1. The pressure or electromotive force (EMF) is measured in volt6. 2. The quantity of electricity flowing is measured in amperes. 3. A rate of flow can be expressed as ampere hours. 4. Power equals volts X ampere hours divided by hours or watts.
A German physicist, George Simon Ohm, first studied electricity flow in a circuit in 1822. He found that in every circuit the amount of current is dirctly proportional to the pressure, or EMF, applied, and inversely proportional to the resistance in the circuit...of I =-E-
R
The formula, I
E , is called Ohm's law. K
Resistance varies from circuit to circuit for three reasons.
1. Various conductors have different resistances. Silver is the best conductor and copper is almost as good (and a lot cheaper). Aluminum offers greater resistance, but because of its weight, is often used for large overhead cables.
2. The length of the circuit. The longer the wire, the greater the resistance.
3- The thickness of the conductor. The thinner the wire the greater the resistance.
Page 4-1
17590
A convenient way to remember Ohm's law. Cover what you're look ing for and the rest of the diagram will tell you the formula. To find
amps...cover amps in^the diagram and the formula then is -2-. Similarly R is Covering volt! leaves I x R.
FIGURE 4-1
One other important formula for measuring electricity and its effects is the relationship between E (volts), current (amperes) and power de livered (watts);
Watts equals Amperes X Volts
A 60-watt bulb connected to a 110-volt supply uses:
60 1 A X 110
or 60 : -55 amps
110
A toaster using 11.5 amps in a 110-volt supply uses:
W = 11-5 x 110
or 12o5 watts
Electricity is either DC (direct current) or AC (alternating current). In direct current the electrons move around the circuit always in the same direction. In the alternating current circuit, they move in one direction for a time, then reverse themselves and move in the opposite direction. This is similar .to the action of a piston in a cylinder of your automobile engine.
And, as with the piston in a cylinder, one move in both directions is called a cycle. The standard in this country is oO cycles per second, though there are some variations. Before installing any piece of electrical equip ment it is very important to know the AC cycle time as well as the voltage and amperage available.
The generation of electric current is a relatively simple principle. If a wire in a circuit is moved through a magnetic field an electric current will oe produced in the wire.
Pae
17591
FIGURE 4-2 FIGURE 4-3 FIGURE 4-4
With the north and south pole6 of a magnet facing each other, a mag netic field is set up between them. A wire connected to a circuit at posi tion "A" would have no voltage generated and no current flowing through it.
As the wire is moved through the magnetic field, however, voltage is created and the current starts to flow and reaches its maximum value in toth volts and amperes at point "B" wh; re the magnetic field reaches it maximum density.
As the wire continues to move toward "C" the voltage and current will lessen again, until at "C", it once aeain reaches zero.
Page 4-3
17592
When the wire is then moved back through the magnetic field, voltage and current will again reach maximum value at point "B". Only, this time, because of the reversed movement, the voltage and current will be in the opposite direction.
Continuing back toward "A", the voltage and current will, again, lessen and, again reach zero at "A"...com pleting one cycle in the generation of AC current.
The amount of current depends on the strength of the magnetic field, and the size of the wire.
Obviously, if the circuit included a bulb, and the frequency of cycling was very low, the bulb would flicker. At 60 cycles per second the alternate build-up and fall-off of current have no apparent effects on the continuity of light given off by an electric bulb, since it does not have time to cool down.
Motors are roughly similar to generators. The difference is that with a generator, mechanical energy is used to turn the coil which makes it turn and deliver mechanical energy.
The same effect of alternating current can be accomplished by holding the wire stationary and moving the magnet.
Page 4-4
17593
s^aT0R cO,t
To generate large amounts of power, huge electromagnets are rotated In the center of a series of colls.
As the poles of the magnet spin, their magnetic fields rotate and In duce current In the colls.
FIGURE 4-7
The frequency is determined by the number of magnets and the speed with which the magnets turn...the amount of current generated is determined by the power of the magnet and the dimensions of the wire in the coil6.
To obtain the sixty cycle current commonly in use in this country generators operate as follows;
with 2 pole magnet 4 pole magnet 6 pole magnet
-- 3600 r.p.m. ----- 1800 r.p.m. -- 1200 r.p.m.
The above listed r.p.m.'s are known as synchronous speeds.
Induction motors try to attain the same synchronous speeds depending on the number of poles they have. For example an induction motor rated at 1750 r.p.m. is designed with 4 poles. The motor load slows it down to the rated speed. Similarly a 3450 r.p.m. induction motor is of two pole design.
Another use of the electromagnet is to keep the magnet stationary and move the magnetic flux inside the magnet. Thi6 is the principle used in the transformer.
Page 4-5
17594
FIGURE 4-8 FIGURE 4-9
When a coil around, a magnet is connected to an AC source, magnetic flux is built up in, and travels around, the magnet. Thi6 flux movement corresponds to the AC cur rent building up and then falling off .. first in one direction and then the other
If we then wrap another, secon dary coil around the magnet, the magnetic flux moving in the magnet will "induce" a current in this secondary coil.
The important features of this transformer are based on the fact that the relationship of voltage between the primary coil "A" and secondary coil "B" are determined by the number of turn6 in each coil. The cycles in the secondary coil will be the same as in the primary.
Page 4-5
17595
If the primary coil had double the turns of the secondary, we would have a step-down transformer and the result would be reversed; Voltaste would be cut in half, and the amperage doubled.
Example;
In a 115/24 volt step-down transformer the primary coil has 230 turns. How many turns in the secondary coil?
No. of turns = 230 X 24 115
or 48 turns
The transformer allows us to alter available voltage to suit the needs of various pieces of equipment.
The first and most important use of transformers, however, is to make it possible to transmit large amounts of electrical power over long distances, economically.
Large amperages need large diameter wires. But, because with a trans former with many turns on the secondary and relatively few on the primary we can build up the voltage, and at the same time reduce the amperage by very large amounts, power can be transmitted by relatively light, inexpensive cable. Long-Distance transmission voltages often exceed 300>000 volts.
Sub-stations may transform this voltage to something like 12,000 volts for short transmission systems with secondary sub-stations stepping it down even further to 2400 volts.
The 2400 volts, then, on its way to the consume.' (residential, com mercial or industrial) is finally reduced by the transformer on the utility pole to 440, 230, 208, or 115 volts depending on need.
J Phu - 21*00 felt DlJtrlbutlon Serrlc*
S)ct-tVImlr*to- Sa lrn**al*l^apehM
If your home has a 3-wire elec tric service offering you both 115 volts and 230 volts, this diagram shows the circuits from utility pole to the house.
FIGURE 4-10
Page 4-7
17596
The two wires at either end of the secondary coil are brought into the house. These are both hot wires and may carry a 23 volt current between them.
A third wire tapped into the center of the coil is brought into the house, but is also brought down the pole and grounded. This third wire, then, is neutral and carries 115 volts between it and either hot wire.
This gives us 230 volts across the two hot wires for 230 volt ap pliances like stoves and hot water heaters, for instance.
Also there are 115 volts for lighting and 115 volt appliances like toasters, radios, etc., between the ground wire and either hot wire.
This set-up is called a three-wire, single phase service. The three wire, single phase circuit provides greater flexibility of service, ease of installation with simple switching on the 115 volt side and safety.
For example, a light circuit in the house is shown in Figure 4-11. Note that by throwing the switch in the hot line it is safe to make repairs on the light socket since the other connection is already grounded.
J G
FIGURE 4-11
The same safety principles are applied for 115 volt circuits at the fuse box.
When 230 volt6 are involved with both wires hot, a double pole switch must be used to isolate both sides of the circuit.
For an additional understanding of alternating current problems, the term Power Factor is important.
Power Factor Oi
true watts apparent watts
Page 4-8
17597
In electric resistance circuits such as lights, toasters and resistance
electric heating the power P used equals El. Therefore, for this type of
equipment the Power Factor =
= 1.0.
In other words, the wattage measured by the electronic meter equals exactly the volts x amperes furnished the user by the utility company.
Electric motors are a different story. The power measured by the electric meter on a motor circuit is often less than the product of volts times amperes that axe supplied by the utility and the resulting power factor becomes a fraction. Thi6 condition is undesirable from the utility viewpoint. The utility is paid on the basis of power used but it must design its equipment, and size its circuits on the larger product of volts times amperes. Where large quantities of power are involved, the utility usually makes an additional charge above the meter reading when power factor conditions exist.
Some Electrical Circuit Symbols
A double-pole, single-throw. designed to make or break both sides of the same circuit at the same time, when neither side i6 grounded and they are both hot.
FIGURE 4-12
A single-pole, double-throw designed to make either one circuit or another or to break both of them
FIGURE 4-13
The symbol used to indicate a ground line.
FIGURE 4-14 -AA/WV-
Resistors, used to reduce current flow.
FIGURE 4-15
Page 4-9
17598
----vWWWWWt t
FIGURE 4-16
TVonsformer
O
Primory {line soitoge) o
oo
Secondory (low vottoge)
Core lomirctions
FIGURE 4-17
SecondOry {low vottoge)
FIGURE 4-18
Variable resistor.. .or rheostat... allows the voltage to be varied between zero and line voltage.
An iron core transformer.
Iron core transformer with midtap giving us two different voltages.
Page 4-10
17599
CHAPTER 5
CONTROL CIRCUITS
17600
CHAPTER 5
CONTROL CIRCUITS
There are two kinds of controls used in conjunction with big boilers.-
(1) Operating Controls (2) Safety Controls
In the early heating systems "tending the furnace" was a common phrase. It was operated almost completely by hand and watched often.
The growth and refinement of controls has been and continues to be a steady, consistent process. For instance, American-Standard electronic controls, optional equipment with our large gas-fired boilers, are one of the latest control systems to be devised. But even they will continue to be researched, developed and refined.
Before we get to the actual controls, this chapter will discuss the four basic ways controls operate.
(1) Electrically (2) Mechanically (3) Pneumatically (4) Any combination of these three
An Electrical Heating Control Circuit
Thermostat Switch
Electrical control circuits always contain a source, a switch and a load.
They can be high voltage (115-230V), low voltage (20-24V) or, in more complex controls, a combination.
Transformer Source
Gas Valve
i
Load
The control circuit shown is a low voltage circuit controlling the main valve in a gas fired boiler.
FIGURE 5-1
While it is hooked into the main 115 volt line, it incorporates a 115/24 volt step-down transformer which is the usual voltage for the load -- a solenoid coil in ghe gas valve.
Page S-l
17601
In this case, the transformer and not the main line is considered to be the source. When the switch closes a current flows through the small solenoid coil. The coil then actuates a valve mechanism causing the ga6 above the diaphragm of the main gas valve to be vented. The line pressure of the gas under the diaphragm will force it upward opening the main valve and permitting the gas to flow to the burners.
The switch is a thermostat which is an example of a mechanical control. Before we discuss it, points should be made about the circuit in Figure 5-1.
(1) This is the simplest kind of control circuit. (2) It is an operating control only. It needs, as a safety
device, other switches which will be discussed in Chapter 6. (3) It shows only one of several kinds of valve6, which will be
covered in future chapters.
A Mechanical Heating Control Circuit
Thermostats, which act as switches in heating systems, by mechanical movements, make or break electric circuits.
Steel Brass
The simplest thermostat is a bimetal strip...two different metals welded together, usually brass or copper in conjunction with steel.
Because both copper and brass have a larger coefficient of expansion and contraction -- than steel, a rise in temperature will cause the bimetal strip to bend in direction of arrow A. A drop in temperature makes it bend in the direction of arrow B.
FIGURE 5-2 B aA
DQ
r-"
J
FIGURE 5-3
Two Wire Thermostat One end of the straight bimetal strip
is fastened rigidly to a base leaving the other end free to warp under tem perature change. Also one wire is con nected to the bimetal at the base and a contact button (A) fastened to the free moving end. The second wire to the thermostat is connected to the fixed contact (B). Wired into the circuit at the base of the thermostat is a small electric heater (c). As the room temperature approaches the control point -- say 72 F -- the
Page 5-2
17602
bimetal warpB toward the fixed contact (B). As the contact points (A) and (B) approach each other, magnet (D) exerts a pull on the bimetal causing a positive contact of the points, thus completing the circuit and causing cur rent to flow.
In the first thermostats there were no magnets or heaters. With the light bimetal elements employed to get sensitivity the contact points did not close or open with a positive motion. Slight vibrations in the struc ture would make the contacts chatter creating an electric arcing condition. This arcing causes pitting of the points. Under severe conditions the points may fuse together or freeze.
Modern thermostat design retains the light bimetal element but intro duces the magnet to insure positive closing of the contacts. It then was found that an approximate 3F rise in room temperature would be required for the bimetal to develop enough warping force to overcome the magnet and open the contacts. Since a 3F swing in room temperature is not com fortable the additional temperature wa6 created artifically under the thermostat cover by the heating element.
The thermostat closes its contacts and completes the electric circuit under room temperature conditions, but opens the circuit under an artificial temperature created under the thermostat cover.
When the thermostat closes its contacts and completes the electric circuit the thermostat heater is activated. Thu6 the thermostat closes under room temperature conditions but opens under an artificial tempera ture condition under the cover. With this arrangement a variation of room temperature from 0.5 F above the control point is achieved which is en tirely satisfactory for human comfort.
The heater in the two wire thermostat presents a problem. It must be matched to the current draw of the load. An improperly sized heater causes improper control of room temperature. Too high an amperage through the heater causes the thermostat to open too quickly preventing the room from reaching the desired temperature. Too low an amperage through the heater slows the build-up of temperature under the cover, delays the opening of the contacts and causes the room to overheat.
The three wire thermostat was designed which put the heater cir cuit in parallel with the load cir cuit thus making the heater perform ance independent of the amperage draw
of the load. Figure 5-k shows how the
current flowing through the heater -- circuit A -- returns to the transformer without passing through the load, per mitting all thermostats to be furnished with the 6ame heater.
Heating installers had difficulty in understanding the three wire principal and thermostats were wired improperly. Consequently, the two' wire thermostat is one commonly used today.
qU
FIGURE 5-4
Page 5-3
17603
The action of the bimetal element, alone, is a mechanical circuit, where physical movement is used to make or break an electrical circuit. The total circuit is, of course, a combination of mechanical and. elec trical circuits.
A Pneumatic Heating Control Circuit
This diagram represents a pneu matic arrangement for handling the function of the main thermostat.
This circuit combines mechanical and pneumatic circuits. The familiar bimetal strip (A) 16 again used as the temperature-sensitive switch to make or break the circuit. Because this time it is a circuit <bf air rather than an electrical circuit we call the switch a valve, and the contact is a pad rather than an electrical contact.
FIGUR3 5-5
Air from a compressor flows through the main which has an inner orifice (B), with the same air capacity as the nozzle (C) opposite the pad on the bimetal strip.
Air flow is constant, and with the switch in the open position, opening (C) will vent to the atmosphere all the air passed by orifice (B), thus preventing the build-up of pressure in bellows (D). The bellows is also held closed by the tension of spring (F).
However, when the space cools, the bimetal element will warp to the left, the pad will cover opening (c) and air coming through orifice (B) builds-up pressure in the bellows (d), overcomes the resistance of the spring and moves the plunger (2) which opens a valve.
Page 5-^
17604
BASIC CONTROL SYSTEMS
17605
CHAPTER 6
CHAPTER 6
BASIC CONTROL SYSTEMS
The modern boiler is almost completely automatic. It has a full set of both operating and safety controls -- all meshed together in a "control system."
These systems did not suddenly appear, full blown. They grew and developed; operating controls out of necessity for supplying customer com fort and convenience and safety controls out of the need for protecting equipment and property.
We have already 6een how the thermostat operated by the room tempera ture can, through a combination electro-mechanical system, operates a gas valve to start and stop fuel flow.
This same principle can be used to operate other kinds of valves or switches. Later in thi6 chapter we will discuss the valves used with American-Standard boilers.
We can now start and stop fuel flow. Some way to ignite the fuel is needed. For gas a pilot light is U6ed. Gas may be supplied to the pilot through a small line tapped off the ga6 main.
Pilot lights are quite dependable. But they may go out for a variety of reasons. So, a safety device is required to prevent gas being turned on in the main burner when the pilot light is out.
The safety device used today on pilots is the thermocouple. It is constructed by joining two dissimilar metals -- for example, two wires -- at the ends only. In between the two junction points the wires are insulated. See Figure 6-1.
Ammeter
FIGURE 6-1
Page 6-1
17606
When one junction of the circuit is heated and' the other cooled, a
voltage difference is created between the two junctions and an electrical
current flows. The greater the temperature difference, the greater the
voltage.
'.
This same electrical system, when a direct current from an external source is passed through/it, will cause cooling of one junction and heating of the other. This phenomenon i6 called the Peltier Effect. It may be used to create refrigeration. Some small capacity refrigeration units have been constructed. Unfortunately, efficiencies are too low at present to permit using this principle except in very,special applications.
The most common application of the thermocouple is the measurement of temperature. By measuring the voltage generated, or in-a circuit'of a fixed'length and resistance by measuring the current flow, (the tempera ture difference between the hot and cold junctions) may be determined. Knowing the temperature of the cold junction, the temperature of the hot junction may be accurately detevnipod.
We use the-thermocouple in a pilot flame to generate the necessary electrical current to hold open.the Baso Valve located in the main burner manifold. Failure of the pilot.flame and the cooling of the thermocouple cuases the Baso Valve to close preventing the gas. from, reaching the main gas valve. See Figures 6-2.
The principle is also applied to the Baso Switch located in the
electrical circuit between the thermostat and the main gas valve. The.
Baso Switch is held in a normally closed position by the,current from
the thermocouple, Failure of the pilot flame-and the loss of electrical
energy from the thermocouple will cause the switch to 'open thus preventing
the main gas valve from opening.
- '.
Page 6-2
17607
Another safety problem Is created when a thermostat, affected by a steady 6tream of cold air from an open door or similar condition, causes the boiler burner to stay on. This continuous burner operation, if permitted to continue, would cause the water in the water boiler to become too hot or excessive pres sure in the steam boiler.
The answer is another switch in the electrical circuit to the gas valve. This switch is normally closed. It is the high limit.
In water boilers the high limit is an immersion control. When the water temperature rises above the control setting the switch opens and stops the burner.
In a steam boiler the switch is actuated by a spring loaded bellows or diaphragm which in turn is moved by the steam pressure to 6hut off the burner.
The thermal element in the immersion control may be a bimetal helix or a bulb charged with a temperature-responsive solid or liquid. When high limits are installed on the external surface of the boiler a light weight metal disc, which changes shape when heated, is used.
Another control used on boilers in which a minimum water temperature is required, is the operating immersion control sometimes called the "lowlimit." Its function is to operate the burner when the water temperature falls below the desired level.
Still another is the reverse acting immersion control. It is called reverse acting because the switch opens with a drop in water temperature. This action is opposite to that of the immersion controls described pre viously.
Its application is;
1. In a water boiler with a tankless heater. It is located in the boiler so that It feels the drop in boiler water temperature when domestic hot water is being drawn from the tankless heater. It stops the circulator and the delivery of heat to the house while the domestic hot water demand is being satisfied. Since the demands for domestic hot water are of short duration this action has no noticeable effect on the house temperature.
2. When installed in boilers without tankless heaters the control may be set to operate at about 100 degrees F. It then stops the circulator when the boiler water temperature is approximately 100 degrees F. or less. This action prevents any tendency toward moisture condensation in the boiler flues and automatically stops the pump during the non-heating months.
Page 6-3
17608
Another control frequently used in hydronic heating systems is the relay. Its purpose is to tie together a low voltage (24 volts) control circuit with high voltage (115 volts) circuit. See Figure 6-3.
115 Volts
FIGURE 6-3
Because low voltage thermostats are inherently more sensitive and low voltage wiring does not require a licensed electrician mo6t thermo stat circuits are 24 volt6. The oil burner motor is for use vith 115 volts. To start the oil burner when the house needs heat requires the simplified diagram shown. When the thermostat closes, solenoid coil A i6 activated creating a magnetic pull on the switch B closing the switch points and completing the 115 volt circuit. When the thermostat is satisfied, the 24 volt circuit is de-activated, the contact arm B falls away and the oil burner stops. By connecting a circulator to the 115 volt circuit as shown by the dotted lines the same relay would activate the circulator. When selecting a relay in the field, always its capacity should be checked to determine if the amperage capacity is equal to or greater than the connected load.
Separate controls and their functions have been discussed. Present trends in the industry are to combine two or more of the Immersion con trols into a single package, which performs the individual functions, using one thermal element. For example, with the G-2 or G-4o water boiler operating with a tankless heater, a combination control is supplied that combines the high limit control, the operating control (low limit) and the reverse acting control. In addition this control includes a built-in transformer and relay.
This combining of more than one control function into a single control package has a number of advantages. It permits a more advan tageous location of the control in the boiler and eliminates the need
Page 6-4
17609
for additional tappings thereby simplifying boiler and Jacket design. Con trol wiring is made easier and boiler appearance is improved.
The same principles are used in controlling oil-fired boilers. The difference in fuels, however, requires a different kind of ignition and a different safety circuit.
When heat is required in an oil fired boiler, oil is forced through a small hole in the nozzle of the oil burner. This action atomizes the oil creating a mist of very tiny droplets. At the same time a high voltagejimpressed on the electrodes, creates an arc. The arc passing through the oil mist ignites the fuel.
FIGURE 6-4
If the oil should not ignite^ the burner must be stopped to prevent a possible explosion.
This safety control may be one of two devices.
The stack switch with a bimetal helix has been used in this safety role for a long time. A6 soon as the oil 6tarts to burn, the flue gas temperature starts to ri6e. A 100 degrees F increase in stack tempera ture tells this control that the oil is now burning and that the oil burner may continue to operate until the demand for heat has been satis fied. If, after about 90 seconds of oil burner operation there is less than 100 F of increase in stack temperature, the stack switch stops the oil burner.
A more recent safety control used with oil burners i6 the light sensing cell. This cell or flame detector tells the primary controller that the oil spray has ignited. The primary controller then permits the oil burner to operate until the demand for heat is satisfied. Should the oil not ignite after 45 6econd6 of oil burner operation, no signal is received from the flame detector and the primary controller stops the burner.
The flame detector is a cell that is sensitive to the oil flame color only. It is located at the back of the burner blast tube and pointed at the flame. The cell acts as a switch. It permits an elec trical current to pass through it when the oil is burning. This cur rent tells the primary control that ignition has been established.
Page 6-5
17610
Ignition of the oil may be continuous or intermittent. With continuous ignition the electric arc operates as long as the burner operates.
In intermittent ignition the arc operates until the oil flame has been established.
In case of ignition failure, the stack switch will stop the oil burner. It must be manually reset.
A drop in line voltage will cause the stack switch to 6top the oil burner. Automatic re-cycling of the oil burner will occur when line voltage is restored.
When ignition fails, the primary control used with the flame sensing cell also 6tops the burner. It must be manually reset. Similar to the stack switch the primary control stops the burner when the line voltage drops to 90 volts or less. On full power resumption the burner automatically re-cycles.
Electronic boiler controls have enjoyed increased application in recent years particularly on large gas boiler installations. They have greater sensitivity, fast action and a high degree of reliability.
These electronic controls are required on both the G-40 and the G-oO boilers when specifications caul for the requirements of either the Factory Mutual Association (F. M.) or the Factory Insurance Association (F. I. A.).
Factory Mutual Association (F. M.)
The electronic control system specifically designed for the Factory Mutual Association requires electric ignition on all pilots (auxiliary and safety) and electronic control of all safety pilots. All pilots must have 100$ shut off. A protector relay is necessary for each combustion chamber. The American-Standard EG-0 or the DPG-0 control packages meet these requirements.
In addition to the electronic controls F. M. requires the following valves on each gas manifold. See Figure 5-6.
1. Two manual shut off valves.
2. One gas pressure regulator.
3- One vent cock inserted in a special pipe nipple tapped l/8 inch.
4. One General Controls line voltage H-0 Hydromotor Valve with iron body and bronze trim. Normally closed.
Factory Insurance Association (F. I. A.)
The Factory Insurance Association specifies the same electronic con trols (EG-0 or EPG-0) as Factory Mutual. In addition F. I. A. requires the following valves and switches on each gas manifold. See Figure 5-7-
1. Two manual shut off valves.
Page b-o
17611
2. One line voltage mercoid type PR high pressure semi-automatic switch set to open automatically at a pressure of 5" of water column. It must be manually reset. The pressure range of the switch is 1" to 30" water column pressure.
3. One line voltage mercoid type PRL-3 low pressure semi-automatic switch set to open when the manifold pressure drops to 2" of water column pressure. Manual reset is required. The pressure range of the switch is 1" to 30" water column pressure.
4. One line voltage General Controls H-0 Hydromotor valve with iron body and bronze trim. NOTE; Both the K-3E 621 solenoid and the H-0 valves are normally closed. They open on the electrical impulse received from the American-Standard pre-wired panel or the MG 890 E relay. This action occurs only after all pilots have been ignited.
5. One line voltage General Controls 3A inch iron pipe size vent valve No. K-10 CA 41+3. This valve is normally open when the solenoid (K-3E) and the H-0 valve is closed. The vent valve closes when these two valves open.
Details of the General Controls valves are to be found in General Controls literature.
H-0 V live
K-3 Valve K-10 Valve
Form No. SDI-H-0V-1
Form No. SDI-K-3-9 Form No. SDI-K-10-4
For the electronic controls details see Electronic Control Systems for G-40 and G-60 boilers, Form No. BP-15095, Revised 12-62.
The foregoing lists and arrangements satisfy the national requirements of both the Factory Mutual Association and the Factory Insurance Association. Local inspectors may request changes at times in the control equipment, and the order in which the components are installed on the gas supply piping.
Page 6-7
17612
FIGURE 6-5
CONTROL ARRANGEMENT FACTORY MUTUAL APPROVED
G -4 0 AND G-60 GAS BOILERS
Page o-8
17613
CONTROL ARRANGEMENT FACTORY INSURANCE ASSOCIATION
FIGURE 6-6
Q
Page b-9
17614
HEATING CONTROL SYSTEMS LARGE BUILDINGS
CHAPTER 7
HEATING CONTROL SYSTEMS -- LARGS BUILDINGS
The control of large heating systems involve the same principles as the control of small systems.
However, because budgets are larger and savings on larger amounts of fuel become important, more expensive control systems are normally justified.
Instead of the "off-on" control system, continuous but modulated heating is frequently employed. The pneumatic control system as briefly described in Chapter 5 is of the modulating type.
Selection of radiation should be coordinated with the type of heating control. Non-ferrous finned radiation works be6t with continuous but modu lated heat delivery. Cast iron works equally as well with modulated heat input, bum is preferred in intermittently heated space because of its heatholding characteristics.
This chapter will discuss the control of both hot water and steam systems, single zone and multiple zone...continuous and intermittent heat delivery.
Hot Water...Intermittent..Single Zone
The boiler is operated at a fixed water temperature to provide domestic hot water with an immersion control in the boiler water controlling the burner. Heat is delivered intermittently when the space thermostat starts the circulator.
Hot Water...Intermittent...Multiple Zone
The boiler is operated the same as in a single zone system. Heat delivery to each zone may be accomplished as follows;
1. Each zone is served by a separate circulator under the control of the zone thermostat. With this type of control the circuit to each zone has a lift check valve installed to prevent a cir culator on one zone creating water circulation in a zone not calling for heat.
2. A single pump can be used for all zones with each zone having a motorized valve under the control of the zone thermostat. On large systems with heavy circulators a by-pass is usually provided between the supply and return mains to permit water circulation through the boiler and circulator when all zone valves are closed. Water flow through the by-pass may be controlled by a throttling hand valve or by a pressure opera ted valve, which opens automatically with the rise in pump head occurring as the system water flow diminishes.
Page 7-1
17616
Hot Water...Continuous...Single Zone
The boiler is operated at a fixed water temperature to .provide domestic hot water. An immersion control operates the burner. '
Continuous heat delivery to the space is achieved by operating the circulator continuously. Aby-pass aroundthe boiler with a three-way mixing valve automatically modulates water temperatures with the severity of the weather. An outdoor bulb controls the three-way valve.
The circulator is controlled by an indoor thermostat set two or three degrees higher than ..the normal indoor temperature maintained by the outdoor control. Should indoor temperatures,,for any reason, rise above the normal control point the thermostat stops the circulator and all heat delivery to the space.
Hot Water...Continuous...Multiple Zone
The boiler is operated the same as in the single zone system.
Three-way automatically controlled mixing valves modulate the water temperature to each zone under the control of'an outdoor'bulb located to reflect the heat loss .of the zone.
A single circulator for the system or individual circulators for each zone may be used.
When zones require no heat it is possible to provide auxiliary switches on the three-way vaives to stop the circulator.
On large hot water-systems with multiple zones, piping may be designed
for using a secondary pumping arrangement.,
.
''
Steam...Intermittent...Single Zone
There are two basic control arrangements.
The first is simple, inexpensive but somewhat slow'in response. The space thermostat .operates the burner." Steam pressure is'developed to force air from the system and 6team into the radiation.
A variation to this method is to use an outdoor thermostat. Here the occupants of the space have no control of space.temperature.
The second method requires the maintenance of steam pressure during the heating season. A combination low limit and. high-limit pressure-stat is employed. The space thermostat operates a motorized valve. This is a'more expensive control arrangement but the response to a call for heat is quicker.
An outdoor thermostat may be used with the motorized valve.-
Page 7-2
17617
Steam...Intermittent...Multi-Zone In the multi-zone steam system the boiler operates at a fixed pressure with
intermittent heat delivery to each zone controlled by motorized valves operated by zone thermostats, either in the space or outdoors. In large two pipe systems each piece of radiation may have oriice6 installed to provide for uniform steam delivery to each radiator.
Staam..Continuous...Single Zone In large house and small commercial installations, single zone steam
systems accomplish continuous heat input by operating as a vapor system. With this type of system, steam is maintained continuously in the
radiation but under a vacuum that varies with the weather conditions. As the vacuum becomes greater, the steam temperature becomes less and the heat output from the radiation diminishes.
When the space cools, the thermostat starts the burner, increases the pressure and steam temperature -- vacuum becomes less -- and more heat is obtained from the radiation. The normal range of steam temperatures in the vapor system is from 170F to 215F. Response to a demand for heat is rapdl and uniform throughout the system.
Steam...Continuous...Multiple Zone To provide continuous but modulated heat delivery in a multiple zone
6team system, a two pipe vacuum Is employed. Boilers are operated at pressures above atmosphere.
Thermostatic control of system pressure is accomplished through opera tion of motorized valves on the steam main and high vacuum pumps on the return mains provide modulated and continuous heat delivery. A number of proprietary systems with the necessary steam specialties have been developed for this type of operation.
Outdoor or indoor thermostats may be U6ed. All radiation is installed with orifices.
Page 7-3
17618
CHAPTER 8
CAST IRON vs. STEEL BOILERS
17619
CHAPTER 8
CAST IRON vs STEEL BOTT.KRS
There are a number of differences between cast iron and steel boilers which every buyer and seller should understand.
Steel boilers may be designed for greater pressures that are necessary for process steam used in manufacturing and power generation.
Low pressure cast iron and steel boilers for heating are designed and constructed in accordance with the American Society of Mechanical Engineers Code for Low Pressure Heating Boilers.
By this AEME Code, working pressures are limited to 15 psig for steam heating boilers and l6o psig for hot water heating boilers with a maximum temperature limit of 250 F.
the
ASAMmE'eCriocdaen-Stotan15daprdsigcawstorikrionng
pstreeasmsubreoialenrds 2a50reo
therefore limited by F temperature.
All American-Standard cast iron water boilers were originally good for 30 psig working pressure. Recently the working pressure has been raised to 50 psig and,on special order, boilers may be obtained for 80 psig. Refer to current catalog information for boilers available at these higher pressures.
Regardless of pressure, hot water heating boilers are limited to 250 F. working temperature.
Within those limits...and for all normal heating requirements...cast iron boilers have a definite edge over steel.
As far as installation i6 concerned there i6 no clear-cut advantage of one over the other. Cast iron boilers delivered in sections require in stallation time to seal and bolt the sections together. Steel boilers are often delivered complete, ready to hook up. However, because of their size they need expensive rigging to handle and jockey them into position.
Steel boilers also suffer from the cost of replacement. In the case of cast-iron, replacement can often be made on a section-by-6ection basis...whereas with 6teel, damage to the shell often involves replacement of the entire boiler.
And, when a steel boiler is installed in a new building with no pro vision for replacement, the operation requires the demolition and recon struction of a considerable wall area.
The biggest advantage in cast iron i6 inherent in the metal itself. Cast iron is much less susceptible to corrosion than 6teel to begin with...and corrosion^ when it does start, has a much more 6eriou6 effect on steel.
Page 8-1
17620
Rust will attack steel much quicker than cast iron and*when it'does, it tends to bore through the metal in a small area. This,has the effect of making the metal thinner and therefore weaker. -
In the case of cast-iron, it resists rusting longer, and rust', .when it does start, spreads across the surface and does not eat -into the iron.
In addition to giving much longer life,, cast iron has one other big, inherent advantage over' steel...it can be poured into molds, while steel must be formed and. shaped in dies and presses, with various.parts Joined by welding.
Internal tubing on a steel boiler, for instance, must be rolled into the plates (tube- sheets) supporting' them much like .the copper, gas line is flared at the connection to the carburetor in your car. .
This Joint represents a weak -point in the steel boiler andj as weak . points often do, is liable to let go Just when it is being pushed hard in severe weather when breakdown will cause the most inconvenience/
Another advantage of molding cast-iron.is that piping connections can
be more flexible. In the case of steel, the practicalities of fabrication '
rather than desire govern the placement of connections.
;
Cast-iron boilers are expandable within limits merely through adding
sections. Many communities, for instance, are adding wings to existing
schools. Where cast iron boilers' are used, adding sections may take care
of the new wing. If the expansion goes beyond the capabilities of a steel
boiler, the entire boiler must be replaced, or a second'boiler added...if
there is room enough.
,
Cast-iron boilers take up less space both in square feet of floor space and in total cubic feet, for the same capacity. This,, too, is a result of pouring iron into the most ideal shape.
Finally, because cast iron uses a number of.smaller combustion chambers, rather than one huge flame, controls can be simpler 'and less costly. And' simplicity means lower,maintenance cost and less down time.
To Sum Up
At pressures above 15 p. s. i. g. steam and 86 p. s. i., g. water...only steel can do the Job.
Installation cost is a stand-off.
Cast Iron Advantages
. '
1. Less susceptible to corrosion.
,, .
2. Longer internal-connection life.
,
\
3. More flexible piping connections.
4. Readily expandable to handle larger loads.. '
5. Easier, less expensive replacement.
6. Smaller space requirements.
7- Simpler, less expensive '-controls.
.; ,, , Page 8-2
17621
CHAPTER 9
STOKER-FIRED BOILERS
17622
CHAPTER 9
STOKER-FIRED BOILERS
A mechanical stoker is a device to provide automatic fuel feed in a coal furnace, to provide a supply of air under automatic control for burning the fuel, and in some cases, to provide an automatic means of removing ash and other refuse of combustion.
Mechanical stokers burn coal much more efficiently than hand-fired furnaces because the fuel feed is more uniform and more perfectly distri buted and because it provides more positive control of the oxygen necessary to combustion.
Stokers may be roughly separated into four classes;
Class 1; burning 10 to 100 pounds of coal an hour are used primarily for home heating.
Class 2;
burning 100 to 300 pounds of coal an hour are usually underfeed motor-driven screw-type stokers and are used extensively in apartment houses, schools, hotels and motels.
Class 3: burning 300 to 1,200 pounds an hour and...
Class 4; burning over 1,200 pounds an hour.
With American-Standard cast-iron boilers it is unnecessary to go beyond the Class 2 stoker.
Coal firing rates for American-Standard boilers sue based upon coal having a calorific value of 13,000 btu per pound.
Two measurements are sometimes confused; headroom and combustion space.
Headroom is the distance between the top of the retort (the stoker basket that holds the burning fuel) and the boiler crownsheet.
The minimum headroom should be governed by this table for the Severn, Exbrook, No. 3 Redflash smd A-7 boilers.
Firing Rate pounds per hour
Minimum Distance
0- 20 21- 30
31- 40 40-100 101-200 201-300
18" 20" 24" 28" 30" 36"
This headroom is necessary when burning bituminous coal because of the
tendency of coke "cones" to grow out of the fire bed like stalagmites underground caves. If they build high enough to touch the crownsheet, they topplf over, carrying with them the coke that has formed at the level of the
fire bed.
Page 99_-1i
17623
This results in a thinning of the fire bed and the exposure of white hot coals. This thinner portion of the bed offers less resistance to the air flow through the fuel bed, creating an intense blast condition. The intense local radiant heat generated is sufficient to cause breakage of the crownsheet directly over it.
American-Standard boilers should not be stoker fired at fuel burning rates greater than those specified. To do so aggravates coke cone conditions and creates risk of boiler damage.
Combustion space is the number of cubic feet required for complete combustion of the fuel. Combustion space must be large enough to avoid too high a btu release per cubic foot per hour.
If too high a release for the combustion space is attempted we are faced with what is known as a bottled heating condition. This excessive heat for the space results in excessively hot front doors, warping boiler fronts, liquifying re fractory brick and damage to the walls of the stoker retort.
The firing rates of stoker fired American-Standard boilers are satisfied by either Class 1 or ClAss 2 6tokers. In most instances, the stokers are of the underfeed type using a screw to convey the coal from a hopper or bin to the stoker retort.
A hopper type Class 1 underfeed stoker, with a round retort.
FIGURE 9-1
FIGURE 9-2
A Class 1 bin feed type of underfeed stoker with round retort.
SIGURE 9-3
A Class 2 hopper type of under feed stoker with rectangular retort.
Page 9-2
17624
These stokers may burn either anthracite coal (pea, buckwheat, rice or barley size) or bituminous coal, usually pea size.
When burning anthracite there is less tendency for the ash to clinker. As the coal burns the dry ash spills over the edge of the retort collecting in a well or on a hearth from which it may be removed manually or automatically.
The burning of bituminous coal presents a different problem. The ash collects principally on the hearth around the retort. As the ash layer gets thicker the heat from the fire melts it and causes a clinker to form. This clinker is removed manually with clinker tongs designed for the pur pose. While a few Class 1 or Class 2 underfeed stokers are designed for automatic ash removal the major portion of them require manual removal of the clinkered ash.
For best efficiency the quantity of air fed to the fuel by the fan must be kept in the proper proportion to the rate of coal feed. This may be done by setting a damper in the air duct but the wide variance in fuel bed conditions (thickness and porosity) make this type of control unsatis factory. Most modern stokers are provided with automatic regulation of the air.
A draft regulator in the smoke pipe is used to control the over-fire draft within reasonable limits for best results.
As with other fuel burning equipment, there must be an ample supply of air made available to the stoker if efficient combustion is to be ob tained. A stoker burning 100 pounds per hour of coal will require an air supply of 1,500 pounds per hour or approximately 375 cubic feet per minute. Usually a direct opening between the boiler room and outdoors is needed.
17625
Page 9-3
CHAPTER 10
OIL-FIRED BOILERS
17626
CHAPTER 10
OIL FIRED BOILERS
Originally, crude oil was put through a straight run distillation process to separate it into various petroleum products; naptha, kerosene, fuel oil, gasoline and lubricating oils. The quantity of each from a barrel of crude oil depended entirely on the field producing the crude. Because of these fixed quantities a high demand for one of the products -- gasoline for in stance -- would result in over production of the others.
To overcome this problem the oil companies developed a thermal-cracking process by which the natural arrangement of the carbon atoms and hydrogen atoms in the oil is changed. This process made possible the production of varying quantities of products from the same crude oil. For example, larger percentages of gasoline could be produced in the summer. During the heating season the production of fuel oil would be increased and less gasoline produced.
In the late 1930's the catalytic cracking process was developed. It has almost replaced the thermal cracking process since the same results sure obtained, but at lower temperatures and pressures.
The development of cat-cracking gave the heating industry some problems. While cat-cracked #2 heating oil can be produced chemically identical to dis tilled #2 heating oil, it ha6 different burning characteristics...it causes smoking, pulsing and noise in burners.
This trouble, however, has been minimizied because burners are now de signed to handle both distilled and cat-cracked oils or blends.
Oil is distributed in several grades.
One of the lightest oils (No. 2) is almost always used in residential burners. Number 6 is the heaviest and is used primarily in the larger boilers. The heavier the oil, the higher the btu value.
Common terminology refers to light, medium and heavy oils. Actually the numbers 1, 2, 4, 5 and 6 as grades of heating oil and 10, 20, 30 as grades of oil in your car's crankcase indicate the relative viscosity.
Viscosity is a measurement of the resistance to flow in a substance. The higher the viscosity, the higher the resistance to flow. The heavier the oil, the higher the viscosity.
This table shows the approximate weight and heating values of standard grades of fuel oil.
Commercial Standard No.
1 2 4
5
6
Weight lbs./gal.
6.951-6.675 7.296-6.870 8.212-7.206 8.488-7-778 8.571-7.882
Heat Value btu/gal. (000's)
137-0-132.0 141.8-135.8 153-3-140.6 155-7-148.1
157-3-149-4
Page 10-1
17627
The basic or standard viscosity of any oil is affected by temperature. As temperature falls, the oil becomes more viscous...develops more resistance to flow, becomes more sluggish.
Obviously, above certain levels of viscosity, flow to the burner nozzle and, much more importantly, nozzle ability to atomize the oil would suffer.
Because of their inherently low viscosity, temperature presents no prob lems in the case of the two lighter grades.
In very severe weather, however, No. h oil must be heated to at least 0F to burn efficiently.
No. 5 must be heated to at least 60F -- No. 6 oil to 120F.
There are three basic types of burners:
1) High pressure atomizing 2) Low pressure atomizing 3) Rotary Cup
The "High pressure atomizing" is the most common,least expensive and simplest in design. It uses the lightest of oils. It is supplied in capaci ties up to about 30 gallons per hour, and makes no provision for modulating oil flow. The oil is forced through the nozzle under heavy pressure (from 75 to lbO psig) so that it breaks up, or atomizes, as it leaves the nozzle. American-Standard burners are set at the factory for 100 psig.
The "low pressure atomizing" burner (from 2-7 psig) is made in about the same oil-burning capacity as the pressure atomizing type, but because it can handle heavier oils (up to No. 5) with greater btu values it can sup ply more heat at any given firing rate in gallons per hour.
Here the oil and air are mixed before they reach the nozzle. Because the oil is emulsified before it reaches the nozzle, this type of burner re quires a larger nozzle which does not clog as readily.
The "rotary cup" burner handles up to No. 6 fuel oil in capacities up to 150 gallons per hour...with the flow modulated as required by the load.
A rotary cup, in the form of a cone, replaces the nozzle. Spinning at 3600 RFM, the cup throws off a thin film of oil mixedwith small amounts of air, called primary air and equal to 10 or 15$ of the total necessary for complete combustion.
The additional 85$ to 90$ of air, called secondary air, is brought through a secondary air door by either natural or forced draft.
To review the four steps in oil-eemoustion, after the combustion ch-ut rr
1) The oil is atomized 2) It is vaporized or gas if led by the radiant he-t of
tr.e combustion chamber
) It combines .;itn oxygen -.1 tr.e air a) It burns
17628
The efficiency of burning is largely determined, by the efficiency of vaporization. This factor makes it necessary to concentrate the radiant heat of the walls of the combustion chamber on the oil spray as it leaves the nozzle.
For this reason, nozzles are designed to give a variety of spray patterns so that the spray can be tailor-made to fit the dimensions of the combustion chamber. Wide angle nozzles deliver a "sunflower" flame in short, wide combustion chambers and an infinite variety of narrow angle nozzles deliver longer, narrower "horsetail" flames depending on the ratio of length to width in longer, narrower combustion chambers.
Oil spray should not be allowed to hit either walls or floor of the combustion chamber for two reasons
1. It builds up carbon on the walls and floor of the chamber which shortens its life
2. It creates excessive smoke which deposits heavy soot layers on flue surfaces, lowering heat transfer efficiency and necessi tating frequent cleaning.
The short, wide "sunflower" flame is quieter when small quantities of oil are used.
In intermittently-fired boilers it is essential that combustion chamber walls heat up rapidly so as to reach maximum efficiency of vaporization as 60on as possible in each firing cycle.
Combustion chamber walls should be high enough to protect the lower portion of the boiler's water legs. Should an accumulation of sludge end scale exist in the water legs, restriction of normal water circulation may occur and dissipation of heat at that point restricted. Boiler damage could result.
The following tables show typical combustion chamber sizes for the various burning rates in gallons-per-hour of low and high pressure atomiz ing "gun-type" burners.
Page 10-3
17629
Burning Rate GPH
I;
5 6 7 8 in 12 14 16 18 20 22 24 26 28 30
COMBUSTION CHAMBERS
DIMENSION TABLE: HIGH PRESSURE ATOMIZING BURNERS
Length Inches
21 23 24 26 28
33 36 39 42 44 46 48 50 52 54 56
Width Inches
17 18 20 22
23 24 26 28 30 32
31 34 36 36 38 40
Height Inches
17 18 18
19 19 19 20 21 22
23 24 26 28 30 32 34
Flame Center to Floor
8 8
9 10 11 12
13 14
15 16 17 17 18 18 19 19
Floor Area Sq.In.
288 396 480 572 644 792 936 1092 1260 1408 1564 1612 1800 1872 2052 2240
Burning Rate GPH Un to
8 10 12 14 l6 16-20 20-25
DIMENSION TABLE; LOW PRESSURE ATOMIZING BURNERS
Flame
Length
Width
Height
Center
Inches
Inches
Inches
to Floor
Rec. Min.
Rec. Min.
Rec. Min.
Rec.. Min.
Floor Area 3q. Inches Rec. Min.
34 32
38 3o
45 40 48 44
5?r-4of
48 50
60 54
21 19 22 21 24 22 26 24 28 26
32 30 3-+ 30
18 16
19 17 20 18 22 20 22 20 24 21 30 26
10 9 715 o40 11 10 840 755 12 10 1080 975 12 10 1250 1125
13 11 1525 1380 15 12 1780 1620 15 12 2040 l84o
This table shows both recommended and minimum dimensions. If the mini mum v/idth is used, the recommended length should be used. In all cases length has more effect and, therefor^ more importance than width.
Burning 4 5 n "h * GPH
"i
_L' 3
2
124
DIMENSION TABLE: ROTARY CUP BURNERS
Length Inches
Width Inches
Height Inches
Flame Center to Floor
39 *9 57 11 90 05 112 lie 130
20
O..
2
2
3-0 30 1O
[ -c .Q
-
10 10 'O
15 iO 24 2o
<-- > 32
Floor Area
790 117o.
: 00: -050 '/O 6720 I j:4 9100
10-1
O CO
CD
h-
Large oil burning systems commonly use automatic draft regulators to produce a draft pressure over the fire of .02 to .025 inches of water.
All oil burners should be installed in American-Standard boilers accord ing to the specifications of the burner manufacturer.
17631
Page 10-5
CHAPTER 11
INDIRECT DOMESTIC HOT WATER HEATERS
17632
CHAPTER 11
INDIRECT DOMESTIC HOT WATER HEATERS
The necessity for heating water, in either a hot-water or a steam heat ing system, naturally enough, gave somebody ideas of using the same boiler to provide domestic hot water.
In the hot-water boiler the immersion control actuates the burner to maintain the desired boiler water temperature, summer and winter.
Steam heating systems have a different problem. In the heating season, a thermostat or pressure-stat is the normal burner control. But in the non heating season it is wasteful of fuel to maintain a steam pressure just to heat domestic hot water. For the time when steam is not required, an im mersion control is installed below the water line of the steam boiler.
By keeping boiler water at or near a specified temperature, domestic hot water is provided even when the space thermostat is not operating.
This means that one unit can provide both heat and hot water, eliminat ing the need of extra expense for separate water storage and water heating equipment..saving both space, and , during the heating season, fuel.
Four types of domestic hot water heaters are used with boilers :
1. Internal Tankless (instantaneous coil type) 2. External Tankless (instantaneous coil type) 3. Internal Coil with storage tank 4. External Coil with storage tank
The internal tankless heater uses a finned copper coil sub merged in the boiler water. To extract the most heat, the coil is fixed near the top of a hot water boiler and just below the surface in a steam boiler, where boiler water temperature is high est .
FIGURE 11-1
Page 11-1
17633
The fins are usually an integral part of the coil and never loosen. They are scientifically sized to minimize the amount of coil necessary to develop water heater capacity.
The coil is designed to give maximum length without, however, restrict ing the flow of boiler water over and around the coil.
Controls must maintain boiler water at the proper temperature during the non-heating season...usually between l80 F and 200 F.
To insure quick response to a demand for hot water, the operating immersion control in the boiler water is usually located just under the cold water inlet to the heater, so it will sense the temperature drop almost as soon as the domestic hot water draw occurs. Immediately the main burner is switched on to keep the boiler water at the proper tempera ture .
With American-Standard coil type heaters to provide maximum sen sitivity, the control Is placed inside the loops of the coil where boiler water cools the quickest when a hot water demand draws cold water into the coil.
During the heating season, controls in a hot water system lock out the circulator pump until any call for domestic hot water is satisfied. The call for hot water is usually completed in a few minutes and has no notice able effect on heating the 6pace.
The external tankless heater carries its coil in a separate small "tank" of its own. Hot water from the main boiler is circulated through this coil tank, usually by gravity. The operating control is again placed adjacent to the coil inlet.
FIGURE 11-2
Page 11-2
17634
In the case of steam, the coil and its tank are dropped dovn so that a horizontal upper pipe enters the boiler Just below the surface of the boiler water.
The internal tank type heater is a specially designed internal heater with a hot water storage tank added so that an initial supply of hot water is always available. Instead of a long lengths of small size copper tub ing, it uses a relatively short lengths of large size tubing to allow for flow by gravity.
The hot water in the coil and tank is constantly circulated by gravity, out of the upper out let of the coil to the top of the storage tank, then out of the bottom of the tank, and back to the lower coil inlet.
FIGURE 11-3
In some cases a mixing valve is installed Joining a cold water line to the output piping of the storage tank where the requirement is for water cooler than l80F.
FIGURE 11-h
The coil of the external tank type heater is designed in the same manner as the internal tank type. It is used when the boiler design does not provide for its installation in the boiler.
Again hot water is circu lated through coil and storage tank by gravity and again, in the case of a steam boiler, the heater is lowered to allow for piping just below the surface of the boiler water.
Page 11-3
17635
Tankless Heater Performance - I-W-H Rated
After extensive research and investigation on the rating of tankless heat ers, the Institute of Boiler and Radiator Manufacturers announced in 1956 the Indirect Water Heater (i-W-H) Code. This code stipulates that the tankless heater must be tested and rated in the boiler in which it is installed.
The I-W-H Code takes into account all the variables affecting tankless heater performance; water temperature rise through the heating coil (40F140F); water flow through this heater coil (G.P.M.); boiler water temperature; water content of the boiler and boiler-burner input. By testing the tankless heaters installed in the particular boiler with which it is used, the code as sures accurate, dependable ratings.
Not all tankless water heaters are rated according to the I-W-H Code. Some domestic water heaters of the tankless type are rated by the manufacturer of the water heater in terms of gallons per minute of water draw at 100F temperature rise (40F - l40F)...and on the basis of the heating surface of the coil that is in contact with the boiler water, plus the temperature of the boiler water.
Usually, these ratings are obtained by laboratory tests conducted with the tankless heater installed in a large hot water tank where boiler water temperatures are simulated.
Advantages of Indirect Water Heaters 1. Initial investment costs are lower for the boiler with tankless heater.
2. Servicing and maintenance is reduced. 3. Life expectancy of summer-winter installations is greater for boilers which are not shut down in summer -- corrosion and pilot problems during sum mer months are minimized.
4. Space requirements are reduced to a minimum. 5. The copper tubing in tankless water heaters is highly resistant to corrosion.
6. In damp climates,summer-winter installations help keep basements dry.
7- Domestic hot water is generated instantaneously.
NOTE;
Where excessive lime exists in the water, tankless type water heaters are not recommended unless provision is made for regular cleaning. Tank type heaters are recommended in hard water areas.
Page 11-4
17636
CHAPTER 12
HOW THE STEAM SYSTEM WORKS
17637
CHAPTER 12
HOW THE STEAM SYSTEM WORKS Basically, any heating system, like any electrical circuit, has three
component s; 1. The generator or boiler. 2. Circuitry or piping. 3. A load...the radiation.
Providing each of the three components is in good working order and connected to each other with tight joints, a steam heating system needs only the removal of air and free return of condensate to function properly.
System air i6 vented to the atmosphere and condensate is returned to the boiler to maintain the proper boiler water level, and to go through the next cycle of boiling to steam and condensing in the radiation as it heats the space.
Air and condensate are removed from the system by a series of vents and traps covered in the next chapter (13).
A steam boiler is not completely filled with water. When heat i6 ap plied to the water it boils and creates steam. As discussed earlier, it will boil at varying temperatures depending on the vapor pressure on the sur face of the water.
At one pound gage pressure, one pound of water (l/62nd of a cubic foot) will create 25 cubic feet of steam. This represents an approximate 1,500 times increase in volume.
This tremendous increase in volume builds up a pressure greater than the pressure in the piping and radiation. Since steam flows in the direction of a lower pressure it flows through the piping to the radiation.
The piping normally, is insulated to prevent excessive condensation of the steam and loss of heat until the steam reaches the radiation.
A steam system transfers heat from boiler to radiation in the form of latent enthalpy of vaporization. A hot water system transfers heat in the form of sensible enthalpy of the water.
17638
Fage 12-1
FIGURS 12-1
In Figure 12-1 the diagram shows a simple one-pipe, up-feed system. The supply main is pitched downward to facilitate the gravity flow of condensate.
Some definitions; The supply main carries steam to all radiators. After the last pieceof radiation the piping back to the boiler is called the return. At the end of the pitched supply main a drop-leg carries condensate back to the boiler room level. Piping from drop-leg to boiler is called a wet return because it is below the boiler water level and com pletely filled with water.
Actually the water level in the drop-leg is always a little higher than in the boiler, during firing cycles. Resistance to flow in the supply main acts to decrease the pressure on the water surface in the drop-leg which causes the water level to rise. And still more height of water in the dropleg is necessary to overcome the resistance in the return. For gravity return of condensate, the minimum clearance between the boiler and the water level and the end of the supply main is l8"
Page 12-2
17639
FIGURE 12-2
Frequently in one-pipe systems it may not be practical to run a wet return from the end of the staam main back to the boiler. In such instances a dry return is installed near the ceiling. As shown in Figure 12-2 with the drop-leg located near the boiler.
The radiator runout creates a possible noise problem if not properly installed since the condensate must flow back through the runout against the flow of the steam. The noise problem is most acute during the heating-up period. Cold radiators condense the steam very rapidly. This means greater steam velocities flowing against greater quantities of condensate.
RADIATOR -TRAP
FIGURE 12-3
Page 12-3
17640
A quieter system, though more expensive, is the two-pipe up-feed, layout. Figure 12-3-
Here the condensate from the radiation is carried out the other end of the radiator and flows through a separate condensate return back to the boiler. Condensate and steam, then, flow in the same direction, eliminating water ham mer.
Note that the return pipe is above boiler water level and is not com pletely filled with water. It is, therefore, called a dry return.
The two pipe system uses a trap at the outlet end of each radiator to allow air and condensate to escape but holds 6team in the radiator. (see Chapter 13).
FIGUR3 12-4 Downfeed -- Figure 12-4 -- where the steam main is above the radiation, are used on larger installations, primarily to eliminate counterflow of steam and condensate in one-pipe systems and because of building geography in twopipe systems. The dripping of downfeed risers also provides drier steam which puts a smaller load on condensate traps in the radiation.
Page 12-4
17641
However, the upfeed system, if dripped properly, can do as good a Job as the more costly downfeed system.
All four of these piping arrangements are possible in a gravity system ...where the condensate is returned to the boiler by gravity alone.
FIGURE 12-5 It Is sometimes necessary, as shown in Figure 12-5, to install a condensate pump to pump condensate back to the boiler;
1) When radiation is below the water level on the boiler. 2) When the system develops great quantities of condensate...
e.g. a system using unit heaters (see Chapter 29) where fans blowing cold air over the steam coil condense it very rapidly, particularly at the beginning of the daily heating cycle. 3) When the geography of the building defeats easy gravity flow.
(a) Radiation considerably removed 'from the boiler when it is uneconomical to enlarge pipe size sufficiently, and there is not room enough to pitch the pipe severely.
(b) When the condensate return must be high to avoid door ways, windows, etc., and also to keep floor-space free.
4) Or any combination of these.
Page 12-5
17642
SUPPLY VALV
uczr^fcz^ RADIATOR TRAP
CITY WATER
r---------r---------- rt^ 4-t--------- ^ ^
VENT <f
fst
TRAP
"C:
RECEIVER TANK
RECEIVER
PUMP-' AUTOMATIC WATER FEEDER^
WATER LINE -- tjT -
"tj ^rrPxUjmMPr
wcrrMOTOR
^-r.CnOwNrDwEwNScAi TION PUMP
FIGURE 12-6
In large steam systems it is usually necessary to have a receiver tank to hold extra vater for the system. This tank receives the condensate from the condensation or vacuum pumps in the system. See Figure 12-6. The boiler feed pump draws water from the receiver and delivers it to the boiler through a feed water regulator.
When the condensate in the receiver is insufficient to satisfy the boiler demand, a float operated valve automatically adds make-up water to the tank.
A receiver must be used when the boiler has insufficient water holding capacity to fill the piping and the radiation with steam.
To repeat; Only two things are essential to the proper functioning of a steam Bystem;
1. Removal of air
2. Removal of condensate
This chapter has discussed four different piping arrangements for steam heating systems. The next three chapters, covering accessories piping, will occasionally refer to system pressure.
The four different kinds of pressure systems, above atmospheric pres sure, subatmospheric, vapor and vacuum systems will be covered in detail in Chapters l6 and 17*
Page 12-o
17643
STEAM ACCESSORIES
CHAPTER 13
STEAM ACCESSORIES
A full range of steam accessories is necessary in all but the small est of domestic systems.
Accessories accomplish just two things;
1. Removal of air. 2. Easy return of condensate.
By accomplishing these two things, they assure proper transmission of steam through the system.
Radiation Air Vent
This iB a typical air vent in one pipe low pressure systems. It iB located as low as practicable on the opposite end of the radiator from the supply.
The float body, with a flexible diaphragm base, has a volatile liquid charge which vaporizes easily under the steam temperature.
FIGURE 13-1
At the beginning of any heating cycle, as steam enters the radiator, it pushes the air ahead of it. The air is vented through the port.
When the steam has filled the entire radiator, having pushed all the air through the vent, it also fills the shell of the air vent. The liquid in the float body vaporizes, the diaphragm base expands, pushes against the base, raises the float body and the float needle which seats in the top of the chamber preventing the steam from escaping.
With the burner off, the steam condenses, the vapor within the float body cools and condenses, the diaphragm collapses and the float needle is withdrawn from its seat, allowing air to re-enter the radiation.
The air vent shown has an adjustable port to regulate the venting rate ...an important feature when several radiators in the same enclosed space do not heat up uniformly. By adjusting the venting rate they can all be brought to full steam capacity by approximately the same time, providing a better balanced system.
Page 13-1
17645
FIGURE 13-2
Vacuum Vent
The Vacuum vent is very similar to the air vent (13-1). The basic difference is the vacuum check valve just above the port.
When the float needle is with drawn from its seat as the steam condenses, this check valve closes, preventing re-entry of air into the system.
These valves are used on one pipe vapor systems...one on each radiator.
FIGURE 13-3
Main Air Vent This larger capacity air vent
is used at the end of steam mains and dry returns -- about 12 inches back from the drop leg.
Its operation is identical to that of the radiator valve described in Figure 13-1. It is used on pres sure systems.
Page 13-2
17646
Base
Float support Atmospheric tube
Syphon
Main vent (vacuum)
FIGURE 13-4
thermostatic
Disc Type FIGURE 13-5
Bellows Typo FIGURE 13-o
The vacuum vent valve illustrated in Figure 13-4 is applicable to mains and dry returns in vapor steam systems.
It vents quantities of air easily and quickly. The check valve pre vents air from re-entering the piping when the system cools down.
Thermal Trap
The most efficient air vent lo cation in steam radiation is at the bottom of the radiator. Unfortunately, in one-pipe systems it is impractical to put air vents so close to the floor, since they may be damaged.
Two-pipe steam systems are more advantageous. The thermal trap which is located at the radiator discharge passes both air and condensate.
Thermal traps are used on all two pipe systems; pressure vapor and vacuum.
There are two common types; disc and bellows. In each the thermostatic element is charged with a volatile liquid.
Air and condensate enter the thermo static trap at the connection marked "in let". If the condensate is cold, the thermostatic element remains contracted and the air and condensate pass through the orifice to the return main. As the condensate gets hot the pressure generated by the volatile liquid expands the bellows and closes the port. The trap will not re-open until the condensate cools. At this time the cycle of performance is repeated.
Exactly the 6ame result is achieves with the bellows type trap - ^igvire 13-6
Page 13-3
17647
VALVE ACCESS PLUG
VALVE
OUTLET
AIR VENT
FLOAT AIR PASSAGE
------ INLET
Float Trap
As condensate builds up in the trap, the float rises, opening the outlet valve.
DRAIN PLUG
Single Port FIGURE 13-7
VALVE ACCESS PLUG
The steam in the chamber forces condensate out of the trap allowing the float to fall and close the valve, before any steam can escape.
The multiport float trap is indicated where the amount of con densate to be handled varies.
The float, depending on its height, will open one or more parts.
These float traps are used for dripping heels of up-feed systems varying in pressure from vacuum to 200 psig.
In the case of low pressure systems (vacuum - 15 psig.) , the trap should be equipped with a thermostatic air vent.
Float traps are better suited to systems where condensate rer.o.al is continuous. They sr.ould be well-made. False economy in float trap pur chases will result in steam leakage and sticking of moving parts.
17648
thermostatic
DISC ELEMENT
Combination Float and Thermostatic Trap
This trap is merely a combination of float and thermal traps.
Air is vented to atmosphere ahead of the steam and condensate because the thermostatic disc element, in its relaxed position, holds the port open.
OFFICE
FIGURE 13-9
When steam or hot condensate gets to the trap, the disc expands and closes the port. As the condensate level rises, the float opens the outlet valve and steam pressure forces the condensate into the return main.
Float and thermostatic traps are used for dripping mains and supply risers in systems varying from vacuum to 40 psig where large quantities of condensate must be returned.
t OUTLET
FIGURE 13-10
Upright Bucket Trap
This diagram shows a typical upright bucket trap. Condensate enters the inlet. As it rises the bucket floats and closes the outlet valve.
Eventually, the outer lip of the bucket runs into the baffle of the body of the trap and is held stationary. The condensate continues to rise, flows over the sides of the bucket and sinks it, opening the outlet valve.
Condensate i6 discharged from inside the bucket until the bucket regains its buoyancy and closes valve.
Page 13-5
17649
OUTLET
Inverted Bucket Trap
The inverted bucket trap il lustrated in Figure 13-11 is dis charging. Pressure at the conden sate inlet is forcing the water out of the bucket and into the trap body. As the water leaves the bucket it is replaced by air and steam, the bucket becomes buoyant, rises and closes the orifice.
The escape of air from inside the bucket through small bleed hole, marked air vent, permits more con densate to enter. Shortly, the bucket loses buoyancy, sinks and the dis charge portion of the cycle is repeated.
FIGURE 13-11
Air is automatically eliminated through the small air vent at the top of the inverted bucket. They are particularly suited to systems handling abnormal amounts of both air and condensate.
They come in sizes from g" to 3" and for pressures varying from vacuum to 2,400 psig. They are particularly suited to high pressure systems.
Both types of bucket traps are used for draining air and condensate from blast coils, unit heaters and steam mains.
They both use large size exhaust ports. They are designed for use in systems where high pressure might collapse a float.
Combination Bucket-Thermal Traps
With blast coils and unit heaters in low pressure systems, bucket traps are equipped with bellows or disc type thermal traps for venting air. The bucket element returns the condensate.
Page 13-6
17650
VENT TO ATMOSPHERE
FIGURE 13-12
FIGURE 13-13
Boiler Return Trap
When the pressure difference between the boiler and the end of the dry return is too great to permit proper drainage of condensate back to the boiler, a boiler return trap is used as shown in Figure 13-12. The trap should be located close to the boiler and about 18 inches above the boiler water line.
During the period the trap is collecting condensate, the float has dropped. See Figure 13-13. Conden sate flows from the end of the dry return, down the drop leg through through check valve A and up into the trap. Check valve B prevents water from leaving the boiler. Also during this process air in the trap may be vented to atmosphere or back to the dry return where it is discharged to atmosphere through a vent valve.
Eventually the float rises, closes the air vent port and opens the steam inlet port, allowing boiler pressure to enter the trap through the balance pipe from the steam main.
Both trap water and boiler water are now under the same steam pressure. The additional head, because trap water level is above boiler water level, closes a check valve A to condensate return and opens a check valve B to the boiler return and condensate flows from trap to boiler.
Page 13-7
17651
Impulse Traps In steam mains, unit heaters, laundry equipment, sterilizers, and
other equipment impulse traps are used for draining widely varying amounts of condensate. Pressure at the trap outlet must be 25$ or less than the pressure at the trap inlet.
Condensate Pump In some steam systems the end of the main is too low to permit the
condensate return to the boiler by gravity. A condensate pump must be used. A condensate pump consists of a motor-driven centrifugal pump plus a
receiving tank with an automatic float level control. Condensate flows by gravity into the return tank, the top of which must,
of course, be below the lowest return. A vent, run to at least 10 inches above the boiler water level, avoids
pressure in the tank, allowing it to fill properly. The float level control in the tank, when it reaches a specified
height, actuates the pump motor. The water in the tank is then pumped into the boiler through a swing check valve located as close to the pump on the boiler side.
Make-up water, regulated by another float valve in the receiving tank is delivered to the tank.
Vacuum Pump The vacuum pump draws air and condensate from the return side of the
system...separates them...and discharges air to the atmosphere and pumps the condensate back into the boiler.
Low vacuum pumps can maintain approximately 10" of vacuum...high vacuum pumps, 20" or more.
Where a return from the system is below the inlet to the receiver, it is necessary to install an accumulator tank below the lowest return along with a pump. The accumulator pump is also controlled by a float lever.
Page 13-8
17652
Vacuum Lift
The vacuum lift demonstrates one of the advantages of a vacuum steam system. It can raise condensate from a radiator or return to a higher level in the return system.
NVERTEO LIFT FITTING OP CLftOWS t NIPPLES
3- B
-LIFT Pipe T OIA. OF VACUUM PC TURN
NO JOINTS IN LIFT pipe 4JFT FITTING
Assume a return main (A) below return main (B). Condensate will accumulate at bend (C) until it fills up the bend sealing off A from B.
Because the vacuum pump reduces the pressure on the outlet side B, the slug of water in the elbow will be drawn up the vertical pipe into return main B.
FIGURE 13-14
TO VACUUM PUMP
TOTAL lift l not OVER S FT.
IF MOPE THAN
a ft use mope
THAN 2 STEPS
VACUUM
RETURN
pipe size
INCHES
A*
IN 7
>'/* e
Va
2 10
14
1 IS 4 IS
S 21
24
.VACUUM ftCTUF
Single lifts should be limited to 5 feet. When lifts are greater than 5 feet, a step lift is employed. See Figure 13-15*
Lifts should be avoided whenever possible.
FIGURE 13-15*
Page 13-9
17653
Generally, steam mains are not sized smaller than two Inches -- fewer hangers required to prevent sagging. On large systems the end of the main is kept at least half the size of the main at the boiler. Mains Bhould be pitched at least 1/4" every 10 feet, and radiation connections should be pitched l/2" per foot. Where radiator runouts longer than 8 feet cannot be pitched l/2" per foot, use the next largest pipe size.
Tables 15-4 and 15-4A show nominal pipe sizes for returns -- both mains and risers -- for varying pressure drops from l/32 psi to l/2 psi. Again the pressure drop is assumed to occur in 100 feet, from an initial pressure of 3-1/2 psi, and the figures in the body of the table represent capacities in EDR. Three columns for each pre66ure drop are shown-wet, dry and vacuum returns. This table can be used in sizing the piping on two-pipe systems. The wet return eolumn is also used for one-pipe systems.
Page 15-5
17654
R e tu rn M ain and R i6 e r C a p a c itie s f o r Low -P ressure System s-----EDR Sheet 1 o f 2
8o
o o
000000000 t--o-Oo*J o*o*\co*u-cc--v--t*j-oo*qo*oj*c-O,-*o
2 rH i-l-d-VOOHMDHCMC\lC(ON-OINOJ
OWOL
s crOuNrO-vQO oroc H OJ oo E-- O MN
OOOOOO
OJ OJ O Q OJ O o- r*- o o c*- o H H 4 VO O VO OJ 00 C\J
H H OJ co VO
CM CVJ OJ
OH M-3*AOOM\TLN
OQQOOOQO OOOOCMCUOO it^-CMO\OC-f-OOi
S *,
H H4-VO OHVHOOOJJ
I
O <
Ncooct-mc^n-oojcvmooj-coyooooocvojoo
H ltnOnlOCVJ-4- C~- O O IA4
> H pqlanco coco H O
H H (OlA
o
ro
CM >H Uo g H
S
4V0400JOOO CCOMOion ON-Hd--zCf"C--3M* COO^Ot
\ s s \ CM COVO CO CO
-3CM
OCMCMOOOOO CO On t-- CM CM O CM UNON IAOJ ro LAN CM co
covo CO coco
H rH
CMN0CMOOOOOOO lAVO^-OJ O CM CM O
u~\ ON ltn CM -J" t*~ O Ovirv^t H COLTNCO CO 0-- H O H H lOlA
CM CM CM O Q ON UN ON O O H -3- On its O i
iii
o
$
CM
UO M 8
CM ro
COO-^QOOOO CM CM <$ -t CQ CM
i CM lpsCOCO O CO CO C-- .
H fO UN t-- H
OCMCMOOOOO O LT\ vTN O CM CM O CM I LOGO COCO C-- LAN O LAN 1
H CM H- h- H LA
CM CM CM Q Q OniaOnO O H -3- ON U"N O *
IIItI)|
&sl
H *h d
Ph w H
s
^
z
CM CM CM
(--I I rHI
H j
H 1
CM CM ro ro 3- pan vO
CO
-=t
CM CM CM
CO ro rH H H H H 1i l 1
OS <--I rH H CM CM ro ro --t its
Page 15-6
17655
Sheet 2 o f 2
CVJVOCVJOOOOO
88o<
m c-- owo cvj cvj -d* o HONmmmO\CVJC\J
CVJ OJ
\o>
miAHCO
hh
Om_3u*-n cvj
Oon irt--s
u
O oo g
o
tiiiiiiii
8 8VO 0J O O O O O
- ON VO 0J QJ O : ON m CO on 0\ (\J C\J > CVJ CVJ
On LA rH go o ltn cvj on its r-j H on VO O C"-
R e tu rn Main and R is e r C a p a c itie s f o r Low P ressure System s-
i i i i i i i
Wi
88o
<
oO oO oO oO Oo oO oO
CO -3- -4 CO 0-4-4
O VO
> CVJ mco (OHN4 f--4
i-i cvj m4 c- cvj
O j- CVJ o
vpvp r-l _ -4 I -5 CMA 00-4
oo
CVJ CVJ oo to i
g rl muv04 rl
H H C\l
88-1 < 1I 88
VO
H CVJ mco rOH W4
h cvj m^t h- cvj
CVJ OJ CVJ Q O ONUNOvO O
H -4- ON ltns O H cn
1111
OQQOQOOQ OOQQOOOO I 44C004400 h' cv? pood' ro h' cvj'-4'
H CVJ M4
COvp4VOOOQOOO< VO On O O\C0 CVJ O CVJ -4 O 1 o in Ov C^VO VO t/v CVJ t-- CVJ 00 <
H CVJ irNOMTNCVJ H -4* C H CVJ m LAC
H CVJ 00 o o o o o
O H VO VO VO CVJ O CVJ CVJ CO rn OsOn o Os rn
CVJ l \ \ % H CVJ ON CVJ ON
uo
M
ffi
CO
88888
O C-- t'-vO -3-
O
8
HHCVJirNONuncvjH H cvj m
11 1 1 1 1 1 1 1
sjn-^sOOOQOOOO
Q\ O CNCO CVJ O CVJ -4- O O ON C--VO vo ir\ CVJ t*- CVJ CO H
HCVJunONirsCVJHJ-CO H CVJ m LfNCO
COVJnCiVaJ oCVnJ oO OQ
H4- ONIAO I v, *\
rH m
I
<D SU033)
tsj O
H d CO H
co -d* CVJ CVJ CVJ
\
\ \ ----
n m rH *H i-l rH
1 1< l } 2 --1rH rH r OJ CVJ
3 3 4 5
6
CO K -d-
cvj CVJ OJ
M CO
M03
m *HI f-HI
rHI
HHHCvjcvjonm^fin.
Page 15-7
17656
m h o o k y .. ...6*4!]
h o o k y , rAllOOl
h o o k .. ,oJ400
17657
FIGURHJ 1 5 -1
The schematic drawing (Figure 15-l) shows a typical one-pipe low pres sure system. Since it is most frequently used, we assume a designed pres sure drop of l/8 psi.
All pipe sizes are shown. However, using our tables, let's see how they were calculated.
Pipe sizing is always started at the top of the steam riser farthest from the boiler -- 1 to 5 in this example.
Since this is a one-pipe system in which the condensate flows against the steam we use Table 15-3 to size all steam risers and radiator runouts.
All runouts are 5 feet in length and can be installed with the proper pitch of l/2" per foot.
Since the smallest radiator on this riser has an EDR capacity of 30 square feet (which is larger than 28--See Table 15-3), the radiator runouts must be at least 1-1/4" pipe, which will accommodate all pieces of radiation up to 64 EDR. The radiator larger than this, upper left, with an EDR of 100 square feet, needs a 2-l/2" pipe.
To size riser #1* which must supply two radiators with a total of l6o
square feet of EDR, we find under the heading "Supply Risers Upfeed" that a 1-1/2" pipe will not do it, but that a 2" pipe will handle up to
288 square feet of radiation which will not only take care of the l60 in the two top radiators, but will also serve the additional 70 square feet in the two radiators on the next floor down. So, we can use two-inch pipe in both Risers #1 and #2.
However, the addition of 80 more square feet of EDR on the next lower floor raises the accumulated total to 310. This, the table tells us, needs a 2-1/2" pipe for Riser 3.
Adding 80 more square feet of EDR for the first floor radiation...a total, now, of 390, is still well below the maximum of 464 for 2-1/2" pipe so that we can use 2-1/2" pipe for Riser #4, too.
All other risers and radiator runouts can be calculated from the table in the same way, except the 50 square feet of EDR radiator to the right of Riser #8 on the second floor. The amount of radiation calls for a 1-1/4" pipe, but because the runout is 10 feet long and we can't get l/2" pitch per foot, we use the next largest pipe size, 1-1/2".
The next step is to size the riser runouts from steam main to risers; 5 to 21...10 to 22...15 to 23...20 to 24. Since these runouts are dripped and do not carry condensate flowing against the steam, they are sized ac cording to Table 15-2, under the column l/8 psi.
Adding up the total load on each riser we get for riser runouts...
Square feet of EDR
5 to 21. . .
390
10 to 22.. .
620
15 to 23... 20 to 24...
610 520
Since all loads are greater than 336 and less than 648 square feet of EDR, all riser runouts will be 2" pipe
Page 15-9
17658
To complete the supply side of the system we calculate sizes for the four
steam main segments. Again, because the risers are dripped we use the l/8
psi column in Table 15-2. The load is increased by the load of each riser
as the boiler connection is approached.
Cumulative
Steam Main
Riser Load
Pipe Size
21 to 22 22 to 23 23 to 24 24 to boiler
390 1,010
1,620
2,140
sq. ft. ""
""
""
2" 2-1/2"
3"
3-1/2"
To figure pipe sizes in the returns use Table 15-4A and the same pres sure drop: l/8 psi.
The "dry" return 21 to 25 has a load of 390 Square feet, so a 1" pipe will handle it.
The riser drips (5 to 27...10 to 28...15 to 29...and 20 to 30) are all "wet" and carry loads of less than 1,000 square feet which is indicated in the "wet" column as needing a l-l/4" pipe...all riser drip6 in our example can safely use a one-inch pipe.*
We complete sizing the system by sizing the wet return by segments: 25 to 26...26 to 27...27 to 28...28 to 29...29 to 30...30 to 31...31 to boiler connection.
As in sizing the steam main segments we increase pipe size as load increas closer to the boiler connection. Again using the "wet" column we get;
Return Segment
Cumulative Load Sq. Ft.
Pipe Size
25 to 26 26 to 27 27 to 28 28 to 29 29 to 30
30 to 31 31 to boiler
390 390 390 1,010 1,620 2,140 2,140
1" 1" 1" 1-1/4" 1-1/4" 1-1/2" 1-1/2"
The following table shows a 6tep-by-step procedure for sizing the pip ing in this example. It is also a form to follow in estimating Jobs. Take the time to study it carefully...then set up a duplicate on a blank paper -- leaving out only the last column. Then using the tables, calculate all the pipe sizes required. Like most old proverbs, it is true that practice makes perfect.
Page 15-10
17659
Table 15-5
Procedure Step
Part of System
Section of Piping
1
Radiator runout
1
Radiator runout
1
It 2
It 2
I! 3
It 3 n4
tt 4
2 Riser
1 to 2
3 H 2 to 3 4 1! 3 to 4
5 II 4 to 5
6
Radiator runout
6
II 6
It 7 M7 t) 8
It 8
tt 9 n9
7 Riser
6 to 7
n 7 to 8
it 8 to 9 n 9 to 10
E.D.R. Sq. Ft.
60 IOO
30 40 30
50
40 40 160 230 310 390
100
100
100 100
50 5o 60 60
200
4oo 500
620
Theoretical Pipe Size
1-1/4 2-1/2 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 2 2 2-1/2 2-1/2 2-1/2
-2 1/2
2-1/2 2-1/2 1-1/4 1-1/2 1-1/4 1-1/4 2 2-1/2
3
Page 15-11
17660
Table 15-5A
Procedure
Part of
Step______________ System
Section of
E.DJl.
Theoretical
_______ Piping____________________Sq Ft_________ Pipe Size
Radiator runout n 1! II M tl It t!
Riser it tt it
Radiator runout n it tt tt
tt
n it Riser
n tt riser runout ti
ii
n 12
12 13 13
l6 16 11 to 12
12 to 13 13 to lli ill to 15
16 16 17 17 18 18 19 19 16 to 17 17 to 13 13 to 19 19 to 20 5 to 21 10 to 22
17661
100 100 100 100
50 1|0
60 60 200
1|00 690
610 100 100
5o 5o 5o
5o 60 60 200 300 100 520 390 620
2-1/2 2-1/2 2-1/2 2-1/2 1-1/li l-l/ll l-l/u
W/lt
2 2-1/2
3 3
2-1/2 2-1/2
L-l/6
l-l/U 1-1/6
W6
1-1/6 1-1/6
2 2-1/2 2-1/2
3
2
2 Page 15-12
Table 15-5B
Procedure Step
Part of System
Section of Piping
10 (contd.) 11
12 13
Hi
Riser runout
15 to 23
II 20 to 2li
Steam main
21 to 22
II 22to 23
II 23 to 2U II 2J4 to boiler
Dry return main Riser drip
It
21 to 23 5 to 27
10 to 28
II l3 to 29 It 20 to 30
Wet return main
It
23 to 26 26 to 27
II 27 to 28 It 28 to 29
II 29 to 30
It 30 to 31 II 31 to boiler
E.D .R. Sq.Ft.
610 320 390 1010 1620 211|0 390 390 620 610 320 390 390 390 1010 1620 21U0 2lU0
Theoretical Pipe Size
2 2 2 2-1/2 3 3-1/2 1 1 1 1 1 1 1 1 i~iA Wii 1-1/2 >1/2
Page I5-13
17662
For two pipe systems (low pressure, vapor and vacuum) pipes are sized in the same way. A pressure drop of l/8 psi is recommended and the same pressure drop should be used for steam mains, risers and condensate return piping.
Tables 15-2, 15-3 and 15-4 should be used. And again, mains should be pitched l/4" in 10 feet, horizontal runouts to risers and radiators should be pitched l/2" per foot and the next larger pipe size should be specified for runouts of over 8 feet where a l/2" pitch per foot is not possible.
17663
Page 15-l4
CHAPTER 16
PRESSURE STEAM SYSTEMS
17664
CHAPTER 16 PRESSURE STEAM SYSTEMS
Steam heating systems operating under pressures higher than atmosphere (gage pressures) are classified as either low pressure (up to 15 psig) or high pressure (above 15 psig...usually 30 to 150 psig).
This chapter will be mainly devoted to the low pressure system begin ning with the review of some of the basic material covered in Chapter 12.
A one-pipe low pressure system uses the same pipe to carry steam to the radiation and condensate back to the steam main.
FIGURE 16-1
Thi6 is a typical one-pipe up-feed system with gravity return usually found in residences. This arrangement has limits on its size and capacity.
As the steam is generated in the boiler, it pushes the air in the sys tem ahead of it and out the vents on each radiator and the main vent at the end of the supply main.
When steam hits any vent, it closes. The supply main is pitched away from the boiler to carry condensate in the same direction as the steam is flowing.
Page lb-1
17665
AIR
J=IT VENT fL- r
zr
--*9
iSTEAM MAIN
-DRIP LEGS WATER LINE
WET RETURN
FIGURE 16-2
This version of a one-pipe up-feed, system shows the risers being
dripped into the wet return.
,
FIGURE 16-3 Another piping arrangement is the overhead main.or dovnfeed system. It is often used in multi-story apartment houses. (See Figure 16-3). The dovnfeed risers are dripped into the vet return. . This arrange ment, of course, also allows for carrying the design load quietly.'
Page lb-2
17666
FIGURE 16-4 This variation...with a dry return...is used where a wet return i6 either impossible or impractical...in most cases where there is only a partial basement. Note that we need the same 18" clearance between the end of the dry return and the water line as at the end of supply mains in earlier examples.
FIGURE 16-5 Occasionally a limited ceiling height in the basement will not allow for this minimum l8" clearance between boiler water line and the end on the steam main. The solution is to dig a pit and set the boiler enough below the floor level to provide the clearance.
Page lo-3
17667
In all one-pipe systems the steam main is vented as well as each piece of radiation to allow for quick elimination of air.
One-pipe systems should use vent valves with adjustable venting rates. This kind of valve provides uniform distribution of steam throughout the system, particularly on automatically fired jobs. By adjusting the venting rates at each radiator, a more uniform heating of each room is obtained. Of course, the boiler must produce enough steam to fill all pieces of radiation.
Another type of vent valve used on radiators is the vacuum vent which allows air to escape but prevents its re-entry into the radiator. These valves are sometimes used on radiators in one-pipe steam systems to convert the system to vapor type operation. These systems so con verted should not be confused with the conventional two-pipe vapor system which is discussed in the next chapter.
FIGURE 16-6 To fully explain the necessity for an 18" differential between boiler water level and the end of the steam main or dry return... Our steam system is, in effect, a giant, closed "U" tube with a boiler built into it. The water in the tube seeks its own level, and with the boiler shut down, will stand as high in the drop leg as in the boiler. With the boiler firing, pressure will build up from the surface of the boiler water and flow in all directions, pressing down on the surface of the water in the boiler and also on the surface of the water in the drop leg. If both pressures were equal, the water in the leg would continue to stand at the same level as the vater in the boiler.
Page lb-4
17668
However, some pressure is lost in overcoming the friction in the steam main.
Assuming 16 ounces of pressure at the boiler end and 2 ounces of re sistance to flow in the steam main, then pressure on the water in the leg would be only l4 ounces...a pressure drop of 2 ounces or l/8 psig.
Since one pound of pressure is equal to 28" of water (see Chapter 2), a drop of l/8 psig means a rise in the water level in the leg of 3-1/2".
Resistance to water flow in the wet return is estimated at 3-1/2 and must also be added.
The normal total rise of water in the drop leg becomes 7 inches. Allowing 11 inches of additional height for the greater pressure drop occurring during heating up of the system and as protection against surging makes the total height between normal boiler level and end of the steam main 18 inches.
^AIR VENT
FIGURE 16-7 When the available head room will not allow the recommended l8" clear ance, the boiler can be pitted, a6 shown in Figure 16-5, or a false water line can be established by the use of a condensate pump and float and ther mostatic (F & T) trap. (See Chapter 13). The water line of the condensate pump is the new theoretical water line of the boiler, eliminating the need for the minimum 18" clearance between water line and the end of the main. The use of condensate pumps allows for a number of variations in onepipe systems.
Page lo-b
17669
FIGURE 16-8
Another problem sometimes encountered with one-pipe systems is the necessity for an exceptionally long main in a low-ceilinged basement.
The answer is to drip the main when it reaches 18" above the.water
line and then use a riser so you can continue the proper pitch from a
higher level.
'
This method of handling head room problems must still consider pres
sure drops to the end of the last main section and pipes must be sized
accordingly.
>
'
This is just one example of the fact that, when the basic fundamentals
of steam flow and pressure drops are observed, steam piping can, literally,
be bent like a pretzel.
'
FIGURE 16-9 The original two-pipe, low pressure system had a number of built-in weaknesses.
'Page 16-6
17670
Here each piece of radiation drips into a dry return (the second pipe). The most obvious fault was steam entering the return leg of a radiator and closing the air valve before the radiator was fully vented, resulting in a partially filled radiator. Another problem was caused by closing the supply valve to any radiator. With the return valve open, the system itself was open to the atmosphere, creating an unbalanced pressure that could back water out of the boiler.
RADIATOR
FIGURE 16-10 With the advent of the radiator steam trap, the two-pipe system took a little different design. The angle valve on the return end of the radiator is replaced by a radiator 6team trap. The trap passes both air and condensate into the return. All air is vented from the system at the one main vent. Because the traps stops its flow, steam cannot pass through a small radiator into the return and feed back up the return side of another radiator, closing the air valve and sealing air into it. However, this system still has the fault of being open to the atmos phere through the single air vent. With the traps closed, the pressure on the water in the boiler can become considerably higher than the pressure in the dry return, causing the water to back out of the boiler and into the dry return, sealing off the air vent and air-binding the system.
Page lb-7
17671
The drawing calls for a differential of 30 inches between boiler water level and vent. This means that if we confine the system total pressure drop to 8 ounces (l4 inches of water) or less, the vent will continue above water and air released properly. In systems where air binding becomes a problem, a boiler return trap can be installed.
Some years back American-Standard sponsored an "adjustable orifice system" which was of this same general design. Orifices in the supply valve6 could be adjusted to the size of the radiator. Theoretically, no traps were necessary to 6top steam flow into the return, because steam was supplied to the radiator in direct relationship to its ability to con dense it. It is still necessary to maintain 30" between the end of the dry return and the water line.
A number of these systems are still in use. These are the principal variations in low-pressure steam systems. There are, too, high pressure systems for very large buildings and for process work where cast iron boilers have little or no application.
Page 16-8
17672
CHAPTER 17
STEAM SYSTEMSPRESSURE BELOW ATMOSPHERE
17673
CBAPTEB 17
STEAM SYSTEMS -- PRESSURE BELOW ATMOSPHERE
There are three different kinds of two-pipe steam heating systems that operate at pressures below atmospheric pressure or under vacuum.
1. The vapor system
2. The vacuum system
3- The subatmospheric system
The Vapor System
Vapor systems are intermittently fired usually under the control of a thermostat.
When starting the system, the burner operates until above-atmospheric pressures are generated and the air has been expelled from the system.
During the off-period of the burner, the condensation of the steam creates a vacuum which is held by the vacuum vent valve as described in Chapter 13- This valve*while permitting air to escape from the system^pre vents the air from re-entering.
As the vacuum is increased and the absolute pressure in the system be comes less, the water continues to boil. The source of heat for the boiling is the heat stored in the water itself and the metal of the boiler.
For example, at 1 psig the boiling temperature of water is 215F, while at 10 inches of mercury vacuum the boiling temperature is only 192F. At 20 inches of vacuum, the boiling temperature drops to l62F.
Once the space is heated and the air expelled, the system stays full of steam but at progressively lower temperatures until the burner is re cycled. At that time there is a uniform increase of pressure throughout the system, a correspondingly uniform increase in steam temperature in all th radiation and even distribution of heat to the space. Usually on the second and subsequent burner cycles, the thermostat is satisfied before the steam pressure gets above atmosphere.
However, the vacuum vent valves are not absolutely tight. During a twenty-four hour period air leaks into the system and the vacuum is gradually destroyed.
On morning pick-up of the space temperature the burner is on a suf ficient time to once again develop stream pressures above atmosphere and cause the expulsion of air from the system.
Page 17 -1
17674
Vapor systems may be identified from the following:
1. Packless steam valves installed at the top of the radiation.
2. Thermal traps on the radiation.
3. Vacuum vent valves on the dry returns.
4. Boiler return trap usually used. See Chapter 13.
The Vacuum System
In the vacuum system the boiler and supply mains operate under pres sures above atmosphere. The return mains--and sometimes the radiation-operate under a vacuum created by a pump which removes the air from the system--and discharges it to atmosphere. The same pump also acts as a condensate pump returning the condensate to the boiler.
Pressure on the supply side of the system vary from 1 to 10 psig and vacuums on the return side are held at approximately 10 inches of Hg.
Packless valves are employed on the radiation. These valves installed at the top of the radiation may be adjusted to vary the steam delivery to the radiation and the heat delivery to the space.
The Subatmospheric System
The subatmospheric system, which is a vacuum system, is designed to provide modulated heat input to the space.
Heat output from the radiation is controlled by varying pressure,tem perature and specific volume of the steam. Unlike the vacuum system with the vacuum primarily on the return side, the subatmospheric system has a controllable vacuum maintained on both the supply and return by a pump.
Pressures in this system may be in excess of atmospheric in severe winter weather and vacuums of as much as 25 inches may be maintained in the system during mild weather.
When heating of domestic hot water by the boiler is required, the boiler operates at sufficient pressure to satisfy the domestic hot water demand. Steam to the system is supplied in modulated quantity by thermo statically controlled floating type steam valve on the main.
If the boiler is not required for domestic hot water, steam genera tion may be thermostatically modulated by controlling the burner.
Radiator supply valves may have adjustable orifices in then. In some systems orifices are omitted.
The thermal traps are designed to operate from 15 psig to 2o inches Hg.
Some of these systems are proprietary.
Page 17-2
17675
CHAPTER 18
STEAM BOILER MANIFOLD SIZING
17676
CHAPTER 18
STEAM BOILER MANIFOLD SIZING
Steam boiler manifolding is important. Manifold boiler connections must be large enough to restrict 6team velocities to 60 feet per second or les6. At the same time, oversized manifolds and boiler connections add unnecessary costs to the installation.
For any boiler being fired- at its specified rate, the velocity of the steam leaving the boiler depends on the size of the connecting piping. Obviously, to carry the same amount of steam, a four inch pipe will require higher velocities than a six inch.
Steam velocities higher than 60 feet per second are to be avoided because-.
1. Noisy steam flow 2. Steam carries entrained water particles out of boiler -- is wetter 3. Increases possibility of priming or slugging 4. Greater chance of water hammer with unnecessary water in the mains.
In the larger sizes of sectional cast iron boilers, multiple outlets are desirable to maintain a uniform water level.
For example, if steam were taken from one end of a long boiler, the steam pressure at the end of the steam outlet would be lower than at the opposite end. The water in the boiler would behave as in a U-tube with the level sloping upward toward the 6team outlet end. The possibility of priming, slugging, or other erratic operation is prevalent depending on the location of the low water cut-off and boiler feed control.
All of these factors have been considered in the design of the recommended piping arrangements shown in the Technical Catalogue Bulletins issued on AmericanStandard boilers.
The pound rate-of-flow of dry or nearly dry steam through a pipe is deter mined by the size of the pipe and the specific volume (cubic feet per pound) of the steam.
The basic flow equation is;
Volume = Area x velocity
To determine the proper pipe size the above equation is re-written:
Volume area - ye]_oc;j_ty
'/here;
Area is expressed in square inches Volume is expressed in cubic inches of steam per second Velocity is expressed in feet per second
Page 18-1
17677
We know that about 1,000 Btu per hour or 1 Mbh of gross boiler capacity is equivalent to the heat required to produce one pound of steam at 1 psig and a standard barometer. A pound of steam under these conditions occupies approxi mately 25 cubic feet.
To substitute properly in the basic equation;
Volume in cubic inches per second
Mbh x 25 x 1728 !5oo
Mbh x 43,200
Velocity in inches per second
Velocity in ft./sec. x 12
Substituting the values for volume and velocity in the equation;
Area
-
Volume Velocity
Area in square inches
Mbh x 43,200 _____ ____________ Velocity (ft./sec.) x 12 x 36OO
Mbh x 43,200 " Velocity (ft./sec.) x 43,200
Mbh Velocity (ft./sec.)
Example 1
Determine the size of the outlet piping from a steam boiler with a gross capacity of 1,000,000 Btu per hour (1,000 Mbh) at a steam velocity of 55 feet per second.
The total cross sectional area of the outlet piping in square inches equals
- - 18.18 square inches
Referring to Table 18-1 it is found that one 5" outlet has 20.00 square inches of cross sectional area
or two 3?" outlets have a total of 19-78 square inches of cross sectional area.
Either one 5" pipe or two 3|"" pipes is adequate.
Page 18-2
17678
Example 2 What size piping is necessary to handle the steam flow at 60 feet per second
velocity from a G-6013 boiler with an output of 1,392 Mbh? The equation is; Area - 1392 - 23-2 square inches
From Table 18-1 it is found that a 5" pipe ha6 20.00 quare inches of cross sectional area
and a 6" pipe has 28.90 square inches of cross sectional area
Therefore, the 6" pipe is used.
Example 3
If the six inch outlet is installed what will the actual steam velocity be?
Transposing the equation
Mbh Mbh Area- velocity to Velocity -5^ to
Velocity -
= 48.57 feet per sec.
Table 18-1 may be used directly to determine the size of the steam out let on piping.
Example 4
An 710-S0 boiler has a gross I:B=R rating of 1,760,000 But per hour. It also ha6 four 4-inch flow tappings. If all four flow tappings are connected to a header, what will be the approximate steam velocity through each.
Dividing
1,760,000 Btu/hr. 4 flow pipes
440,000 btu/hr. per pipe
Referring to Table 18-1 on the 4-inch pipe size line, it is found that at a velocity of 45 feet per second a 4-inch line can handle 572,900 Btu per hour. Obviously, four flow connections are very safe. They are also more costly to make.
Page 18-3
17679
Let us try three four-inch supply connections to the boiler. Each four-
inch line will carry 1,760,000
3 or approximately 586,700 Btu/hr. The vel
ocity (Table l8-l) is slightly greater than 45 feet per second.
Three 3'g'-inch supply connections could be used with a load of approximately 586,700 Btu per hour and a velocity under 60 feet per second.
Several sizes of manifold can be selected depending on what steam velocity is desired. (Table 18-1) The total load is 1,760,000 Btu per hour.
6-inch manifold------- velocity under 60 feet per second
7-inch manifold
velocity under 45 feet per second
The most economical combination becomes;
Three 32"inch flw connections to the boiler One 6-inch manifold.
17680
Page 18-4
B tu /h r ----- Square F e e t o f R a d ia tio n
P
*
o
P
03 C3 (0 CO
p
p
o
u x
.o
3
P
m
o
IT\
o\
PV
eS
o
r-
s
-4-x iPx
oQ
8*x
g
x
o
ss
oo -4
x
P P CVI ro -4 OJ OJ O CO
rH rH OJ OJ
Qoo ooo
x roX V0X
P c-- CO
o CO -4
OJ 0J -4
OOO
O P
x
SX
O
-4#x
oo t-x
oo r**-x
ro on O On On
On LTN
VO 0-
O
OJx
8X
8 X
H ro ro
o o rH*x
Q Q
ox
uo CO
ON
CO-X
-4 VO
pP
a
0(0)
O'
CD
cro*--
LTN LTV o o o
ON
oX
ON
VO*v
VO
C\JX
p Onx
o VOX
P P OJ OJ -4
QOOo
O C--X
tO-*x
LTN
VOX
o rox
H
rH
rH rH
CO rH
VOOJ
>
P
o o 13 >
p
p
u
U"N
LT\
X
3 P
qo
VO
-2o4x
oo
VO x
Q
Or-X
Q o
0J x
5$
m VO VO O
-o4n
Qo
P OJ -4
LTN 0-
Q (f)
ro x
Q 5
Ovx
O
O
OnX
o o
OJ x
oooX
Q ro ro r^ -4
O rH rH CO rH
Px
CO x
CO
-4
ro
rH OJ 0? -4 VO
p0)
CO
p P
r--
Oo oooOo
Q O
4" U"N
VoO
LP\ vO VO rH
LTV LTN
VO vO
ooo
o o
on
aa1>0
o(0*
x P rH
*x X x
OJ OJ -4 o O
rH rH
X
CroU
03
uo a
u<u >
P
PT0?)
O <y
N
P(0
0) bO
Oh H h r^
pH CD ('0-3-
Oh p<
d d
<X r--j d d
O<
a5 03
C9
s:
CD p
o
u U3 M to
3 m
CO
03
U3
'.3 `HCD P-H 0.
03 u
CD CD
r- c
Ph V rH
u
U
03
Oh
P0
c0d3
03 P
o cd
bO 03
O
P
<
b0
P
s
P H
Oh
oo oo
CO -d*x x
O O
X
oo
ro
O O LTN
X
Q O ro
x
oo
LTN x
Oo
rH x
oo
ro
X
o Oo
LfN
3 P
vo
rH
On ON -4 VO O rH CO ON o'
ro OJ
VO ro
ON -4
no
vo
O O
-4 -4
LTN LTN
fo--
-4 r^
0) U 3 CD CD CD 13 PU
3 P P
CQ
X X *x *x *x
03 Oh
03
rH rH OJ -4 LTN
rH P Ch
P cd
3O
H
O3
bO o
P
o
ro
NOeN
LTN 00
o
LTN
LTN
o
VO
oo
oo
o o
o
o
vo CO
ro CO CO X x ro
c*-
X
-4X
VO x
-4 X
LT\
X
O*
rH r--\
-X no LTN On LTN
CD OJ rH OJ
UP 03 CD d P<
O rH x>
d o
0 p
'd *3 <<
u
p0
CQ
xbt
o oQ
oO
LTN
Qo
oo
CO
Q O ON
o Oo
O O -4
Oo
ro
ooo
o CN
o
Xx X X X x *\ -X
X
aJ p p 03 33
uo,
p a
to bD
3 P
X LTN rH rH LTN OJ
OJ -4 ro -4 ro -4
OJ c-- LTN
oo
ON
ON OJ
Ol
o
ro
vo
VO vO
m rH
X X
rH OJ ro LO
Ph U PP 3 O 03
U u cd
cd P P
aP 03 CO
p
bO c
ro lo
p
03 >
rH CD
0
0l vo
0U3
ro
ON
On ON o
ro CO
0-
oo
o
ON OJ x
vOo
coO
< ro -4 r-- On OJ o CO
rH -4
H
o
p
03
h3
bfl
p
po
p
rH OJ OJ LTN CO rH rH
p
P
0)
CD p p
CD 03
p
03
N
ro-Hnj
OJ OJ
Hoj
ro
-4
LTN vo cO
O
OJ
P 1--(
CO
O CD
03 3 3 -C P
03 CO
* PD
Page l8-5
17681
CHAPTER 19
HOT WATER-FORCED CIRCULATION
17682
CHAPTER 19
HOT WATER -- FORCED CIRCULATION There are gravity feed hot water heating systems, but they are found only
in residences in older systems. Forced circulation is used in all large hot water heating systems. They
are rated in two different categories, depending on water temperature. High temperature hot water systems operate above 250...usually 300 or higher and require high pressure boilers.
We will discus^ in this chapter, low temperature hot water (LTHW) systems operating below 250. These systems also fall into two basic classifications according to whether they use one or two pipes as mains.
However, sometimes both basic piping arrangements are used in the same system...two-pipe systems can be either direct or reverse return...and some times a "series loop" is incorporated in the,system.
So, there are four terms describing piping arrangements for forced circu lation hot water systems:
1. One-pipe 2. Two-pipe (reverse or direct return) 3. Series Loop 4. Combinations of items 1 through 3 One-pipe
Page 19-3
17683
The one-pipe system is often the least expensive piping arrangement for large hot water systems. Its major problem is the drop in water tem perature around the circuit. On carefully designed systems the water temperature drop is readily estimated and radiation sized for its average water temperature. Two-Pipe
FIGURE 19-2 The two-pipe reverse return system with the water flowing in the same
,direction in both the supply and return mains provides an inherent balance.
In general the distance the water must flow from the boiler to any one radiator and return to the boiler is the same as the distance to and from smother radiator.
Page 19-2
17684
ZONE VALVE
BALANCING VALVE
*r
T k-SUPPLY RISER
\ RETURN RISER
FIGURE 19-3
In some large systems the circuits connected to the supply and return risers perform as though they were on a two-pipe direct return system. For best operation the circuits should be installed with balancing valves to prevent possible short circuiting and insure the delivery of proper water quantities to each.
Zone valves may be installed on each circuit in addition to the balancing valves, when thermostatic control is desired. This circuiting is adaptable to apartments.
Page 19-3
17685
FIGURE 19-4 Figure 19-4 shows a combination of a two-pipe reverse return system in the basement, with a two-pipe direct return riser arrangement and series loop circuits for baseboard between the risers. This circuiting is adapt able for apartments. Balancing valves are needed on each circuit to prevent short circuiting. When thermostatic control is required^ zone valves on each circuit are used with the balancing valve.
Page 19-U
17686
HOT WATER-SIZING AND LOCATION OF PUMP
CHAPTER 20
HOT WATER -- SIZING AND LOCATION OF PUMP
Proper pipe-6izing in large hot water systems will help to guarantee these two important items in any heating system; economical installation and. reliable, trouble-free operation.
In this chapter we will discuss only LTHW...low temperature hot water... defined by the American Society of Heating, Refrigerating and Air Condition ing Engineers as "any temperature up to 250F."
Hydrostatic pressure...the pressure created at the base of a column of water by the weight of the water itself...is a consideration in hot water system design.
From Chapter 2 "Fundamentals of Pressure";----^
1 ft. of water *
.433 lbs./sq. in
1 lb./sq. in. " 2.31 ft. of water
1 lb./sq. in " 27*72 in. of water
Example 1
An American-Standard boiler is to be installed in the basement of a six-story building. The highest piece or radiation is 65 feet above and 100 feet to the west of the boiler.
The lateral distance is not a consideration. Only the height of the water affects hydrostatic pressure.
Therefore, since 1 foot of water equals .4-33 psi, 65 feet of water equals;
65 x .4-33 psi or 27.1 psig
Example 2
In the same system, the fill line to the system is connected at the boiler. To what pressure must the reducing valve on the fill line be adjusted to pro vide a pressure of 5 psi in the topmost piece of radiation?
The pressure at the point of fill must equal the hydrostatic pressure plus the pressure at the topmost piece of radiation...or 27.1 psig + 5 psig... or 32.1 pounds per square inch gage. The reducing valve must, therefore, be adjusted to supply against a pressure of at least 32 psig.
Example 3
What theoretical height of system measured from the boiler to the highest piece of radiation will an American-Standard boiler fit when it is designed for 50 psig pressure when 5 peig pressure is required in the topmost radiator?
Page 20-1
17688
Deducting the radiation pressure from the total pressure, the boiler can withstand 45 psi in hydrostatic pressure.
Since 1 psi will support a column of water 2.31 feet high, 45 psi will support:
Pumps
45 x 2.31
or
103.95 feet of water
All large hot water systems are mechanically circulated .by a pump. In heating systems the head -- or pressure -- of the pump is expressed in feet or the height, to which it will pump water in an open system.
Another way of 6aying it is that the feet-of-head of a pump is equal to the height of a column of water that creates a hydrostatic pressure equal to the difference between the water pressure at pump suction and pump discharge.
1. R
FIGURE 20-1 The difference in height between A and B, measured in feet, is the head of the pump. Standard design practice today is to drive hot water heating system pumps by direct drive from the motor... sometimes with a flexible coupling between motor and pump shafts.
Page 20-2
17689
This means that pump speed, is equal to motor speed. For any given motor the pump has one characteristic performance curve which plots the pump's ability to create a pressure in feet of head related to the number of gallons of water per minute circulated.
For any one pump, the pressure (feet of head) at which it pump6 will decrease as the amount of water it pumps increases. This characteristic is common to all centrifugal pumping devices.
: 1 i . i : rs.i i i
0 10 20 JO 40 50 60 TO 80
DELIVERY IN GALLONS PER MINUTE
FIGURE 20-2
This is a typical pump characteristic curve. Assume that a pump with this .performance curve is being considered for a job designed for a 20F temperature drop with a 300,000 Btu/hr heat loss.
The minimum number of gallons per minute of water required is established by the equation;
Btu/hr
(gpm x 60 x 8-1/3) x (l x 20) gpm x 10,000
where; Btu/hr heat load gpm " minimum gallons per minute required 60 = 60 minutes per hour 8-1/3 " 8-1/3 lbs. of water per gallon 1 = specific heat of water (Btu per pound per degree) 20 " 20F temperature drop in system
therefore: 300,000 " gpm x 10,000 gpm 300,000 -r 10,000...or 30 Page 20-3
17690
I
FIGURE 20-3
Now.. .entering the base line at 30 gallons per minute, a vertical line is erected until it meets the curve at A. A horizontal line from A, .on the vertical Beale, will show the feet of head available from this pump.
j Small System Pipe Sizing
i In small systems for. residences and small commercial buildings^it
is good practice to select the. pump, determine the head it will deliver
when circulating the minimum quantity of water, then' size the piping against
this head.
'.
Since pipe-sizes axe no larger than 1-1/2" and resulting water velocities are less than the critical 48" per second, this procedure works well.
' Large System Pipe Sizing
On large systems, where pipe-sizes exceed l-l/2 inches, piping i6 sized on the basis' of pressure drop per foot of.equivalent length at water velocities that will assure quiet flow.
A safe-and practical rule of thumb is to assume that; feet of equivalent length equals 1-1/2 times the feet of linear length.
Resistance in each pipe-size-segment of the system is calculated separately by multiplying the equivalent length in feet.by the resistance per foot. They are all added together to establish the total resistance of the system.-
The pump is then selected-whi-ch will have ;a head equal to or greater
than the resistance of the circuit while circulating the minimum water re
quirements of the system.
'
Page 20-4
17691
t
FIGURE 20-4
Ab a demonstration, assume a system requiring the circulation of 50 gpm against a friction of 14 feet of head. This point iB plotted at point "C".
Friction head for other circulation requirements can then be determined by the formula; friction varies as the square of the velocity...or, as the square of gpm.
Dropping a vertical from "E", where the friction curve intersects the characteristic curve of pump A, indicates a circulation rate of only 46 gpm.
To be safe, we must specify pump B with a surplus capacity (52 gpm). Actually, of course, in practical usage, it is only necessary to establish point "C". Always specify the next larger pump rather them an undersize. The total resistance of the circuit includes friction loss through piping, fittings and the boiler. Recent studies by pump manufacturers have demonstrated that placement of both pump and expansion tank on the supply side of the boiler is more de sirable .
Page 20-5
17692
c
6 C
Figure 20-5 Figure 20-5 shows a schematic drawing of the pressures in a hot water system with both pump and expansion tank on the supply side of the boiler. The solid line ABCD indicates the constant pressure level throughout the system with the pump idle. When the pump starts up, there is a slight pressure drop at I, the pump intake, and a rise to E at pump discharge. The difference between E and I is the head of the pump. The line JE shows the pressure increase in the system when the pump is running. From E to F the pressure decreases due to friction in the piping. This loss continues around the circuit through G, H and finally to A, where the pressure is equal to system pressure whether the pump is running or not.
Page 20-6
17693
With the pump in this location, the lowest pressure is at I -- the pump suction. Assuming a pressure of 15 psig with the pump not running, then pres sure at I, because of friction, will be only slightly below 15 psig -- maybe 14.9 or 14.8 psig. Still well above the atmospheric pressure.
B
Figure 20-6 But! With the same pump on the return side, sucking water around the circuit instead of pushing it, the pressures change. The solid line ABCD again represents system pressure with an idle pump. A, at the expansion tank, is the constant pressure point in the system.
Page 20-7
17694
Again, the lowest pressure is at the suction.end of the pump (H). Going backwards around the circuit, the pressure is higher at each succeeding point G, F and E because the pump is pulling rather than pushing and lowering pres sure constantly around the circuit.
Note that pressures all around the circuit, now, are lower than the pres sure in the system with the pump not working.
With a low head pump in the same 15 psig system, pressure H might be
as low as 11.8 psig instead of the 14.9 or 14.8 psig with the pump on the
supply side.
.
While 11.8 psig is still substantially above' atmosphere and would operate the system satisfactorily, trouble would arise if; .
1. The system static pressure fell too low 2. The pump had a high head
For either or both of these reasons;, pressure at pump suction point H might fall too low. This situation could set upltwo problems: . .
1. If pressure fell below atmosphere, the pump might suck air into the system around the shaft seal which is designed to hold water but will let air in.
2. The pressure might fall low enough to cause the hot water to flash into steam...creating noise a6 well as damaging the pump.
The relation between pump and expansion tank location is not important normally in residential systems, because pump heads are low.
In large hot water systems with high pump heads, safer, more dependable and quieter operation demand that both pump and expansion tank both be lo cated on the supply side of the boiler.
Except in noisy factories, piping is always designed for quiet operation, which means air-free water traveling through the system at less than 4 feet per second.
Table 20-1, showing gallons per minute, indicates design limit's in pipe size and friction for quiet operation.
Gallons per minute can be converted to'Btu/hr. by multiplying by 10,000 for a system designed for a 20 drop, 5,000 for a 10 .drop.
Friction is expressed in milinche6 which are equivalent to a loss of pressure equal to a column of water l/l,000ths of an inch high.
One foot of head, then, will overcome 12,000 milinches of friction.
Page 20-8
17695
heavy lin e 6 w ill provide n o isy w ater flo w . For values fo r 5 and 6 in ch pipe in q u ie t
o o CO o CM ro cd
CM CM o LTN LTN r- -d ON O -d C-- LA
cvi -d ON o rH rH CM -d rH CM ro
o CM CM
c--
cvj
CM
CM
CVJ -d
O CO
ON
rH VD ON On
CO m VO CM NO rH rH CM -d
rH CM -d
CM CM ro o ro CO CM On
CM c-- CVJ no
C\j
ON
-d* CO
LP\ cvj
rH cvj -d co
rH
rH
ro LA
CM lf\
o
CM -d-
o rH
CVJ rH ro NO rH _d ro LA ro CO -d r-
LO o CO
rH rH ro LA
rH ro -d CO
m t"- O
C-
rH
O
CM
o
On LA ro o ro ON vo
CM
LTN o
VO rH
CM rH no LO
no rH ON
rH
ro VO
m CO CM
ro CM
LA rH
ON LTN rH o t- YJ -d CM
-d CO -d-
VO
no -d
92
rH
CVJ
no vo
rH ro LTN On
ON IPs t"CM ir\
E'- ro t*- ro ro VO CM cvj * o LA rH o rLTN vo rH rH CM _d vo
rH ro LO
cO m u~\
CM CM
VO
r- -d *
<8
rH VO
VO CM
rH CM
00 vo ON rH rH CM -d
rH ro ITS
LA o c--
> 0
0 o
a o
P O 0 rH 0 CO
Tfdi
o o <I) CO
&
CO 0 X! a a H
00
la CM
O CO
no vo
CM rH
-d ro o
ON CO
CM
rH ro VO
no CO rH vo rH rH
vo o no -d CM -d
LA no
f-
J3 -P
03
vo m CM CM
rH
CM
H
LA LA vo -d
r*- -d
LA VO
U3 a>
m VO ro O ON -d rH rH CM -d c--
o rH CM ro VO
CVJ 03
0)
NO
c*--
r- o *
rH
Ho CVJ CO
ro CM
o
LA r- On
rH -P
oo VO ro o rH VO rH rH CM -d
tH
rH CM -d vo
O
0
r- LA C"- CM m vo
LTN VO CO VO f- CM o o cvj 00 V0 ON CM
rH CM 00 rH rH CM -d CO CM -d vo
0 >
0
C--- ON C--
on vo
-d' rH
rH O
CM -d CM -d
o On ro rH LA UA CVJ ON r- o -d
rH f--J rH CM LA CO r-
aJ >
Jh
ao 00 ro
t-- m rH ro CO o H CM no On CO CM
LTN CM LTN ro H rH CM LA CO rH CM -d
Cm
UJ 0 A
co
On no
ro r^-
LTN
-d- LTN -d
ro VO
LTN
ro rH
ro On O CO CM CM
f- CO no On LA CO
CM _d
ON -d"
ro- VO
t- O -d -d -d
-d- ON On CM -d
LA no -- LA H O vo -d CM no LA On
o CO
CM
ON CM
o vo
O LA CM
LTN CM CM ON ON
CM co t"-- LTN rH ro rH CM ro LA ON
rH CM LA CO
d00
CVJ -d-
-1 CM
CM
CM
H 0P<i MN 10 B tI rl C (--1 ro
rH rH
i--1
H
O P-i CO H
r--| rH rH CM CM ro ro d LA VO
> cd 0 X!
0 > O JP A
-P a 0 rH 0 03
*
Page 20-9
17696
Consider a 2" pipe. The table indicates that it can handle 4l gpm at a milinch friction of 400 per foot.of length. If it'is asked to carry 42.6 gpm, milinches of friction rise,-to 425 per foot of length and water velocity exceeds the permissible limit of 48 ft/sec.
Similarly, the safe, quiet loading of a 2-1/2" pipe is 59-4 gpm; for a 3"
pipe, 93 gpm.
-
Note that as pipe size increases, allowable friction for quiet operation diminishes.
This table can be used to specify pump.size. For instance, the system will use 265 feet of pipe. By rule of thumb we multiply this by I-1/2 to get 397 --
or 400 feet of equivalent length.
Requirements are for 40 gallons per minute. The smallest pipe that will carry 40 gpm is 2" and it will set up 400 milinches of friction per foot.
400 milinches X 400 feet - 160,000 milinches of friction. 160,000-7 12,000 -1 13-3 feet. A pump with at least 13-3 feet of head is required, for a circu lation of 40 gpm.
Two or more pumps in series in the same circuit are not frequently used. Since their heads are additive, the effect on the system is that of a single large pump having a head equal to the sum of the heads of the two smaller ones.
! When the quantity of water to be circulated is small and the head require ments are high, two small pumps in series may be more economical to install than one large one.
A small but growing practice uses two pumps in series but in separate zones or circuits of the same system. This arrangement is called primary and secondary pumping.
Primary and secondary pumping for zone control is relatively new.
It has certain advantages.
1. A better degree of control is achieved than with motorized valves.
2. Pump and pipe sizes can be reduced by allowing for greater
temperature drops in the primary circuit.
. .
1 3. Hydraulic and heat balance is achieved with economical
operation.
.
4. Total pumping horsepower is usually less.
' 5. Continuous water circulation with modulated temperatures and heat delivery to the zone is possible.
6. Installation costs are frequently less than other control systems.
Page 20-10
17697
FIGURE 20-7 Figure 20-7 illustrates a basic piping arrangement for a system using . primary and secondary pumping. Its principal of operation is simple. When a secondary circuit is connected to a primary circuit, such as in a one-pipe system, the resistance created in the primary circuit between the supply and return tees will cause a water flow in the secondary circuit. However, when two ordinary supply and return tees are placed close together on the primary circuit, the resistance becomes so small between them as to cause almost zero circulation in the secondary piping. With this piping arrangement, pump6 may be selected to overcome the resistance of each of the two circuits. The primary pump operates continuously. The secondary pump is put under thermostatic control to supply heat to the zone needed.
FIGURE 20-8 Figure 20-8 illustrates the development of multiple zones from the basic diagram in Figure 20-7-
Page 20-11
17698
The primary circuit performs similarly to a one-pipe system and is nor mally designed for a 20F temperature drop. When temperature drops of more than 20F are UBed, the radiation must be selected on the basis of the
average water temperature available at each zone.
FIGURE 20-9
Primary and secondary pumping may be used with either a two-pipe direct return or a two pipe reverse return primary circuit. The reverse return arrangement is preferred as shown in Figure 20-9.
FIGURE 20-10
FIGURE 20-10A
In all of the previously described arrangements the secondary pump is operated intermittently.
Figure 20-10 illustrates an arrangement for continuous pump operation in the zone with a two-way (open - close) valve, thermostatically controlled, that admits hot water from the primary circuit. The zone still gets heat in shots.
Page 20-12
17699
An identical effect can be obtained with a three-way (open - close) valve. See Figure 20-1QA.
ONE rtPE PRIMARY OR
FIGURE 20-11
FIGURE 2G-11A
When modulated water temperatures are desired for continuous heat delivery to the zone, the piping arrangement illustrated in Figures 20-11 and 20-11A are required. Modulating valves, either two-way or threeway, are under thermostatic control.
Page 20-13
17700
b i
HOT WATER SIZING THE EXPANSION TANK
17701
CHAPTER 21
CHAFT3R 21
HOT WATER -- SIZING THE EXPANSION TANK
Tanks are necessary in hot water heating systems to allow for water volume expansion as it is heated. Economical sizing of this component as well as others is important to the sale.
Originally, open expansion tanks were used above the highest piece of radiation. They allowed for water expansion but had no effect on system pressure.
Modern tanks are closed...containing about 60$ water and 40$ air. As system water expands it moves into the tank, compressing the air cushion and raising the system pressure.
Water logged tanks...insufficient air...cause too great a rise in system pressure...spitting by the relief valve and the necessity for replacing the lost water.
Factors governing the sizing of expansion tanks are the same for all systems. They are;
1. The system volume of water 2. Maximum average water temperature 3. The fill pressure of the system 4. Tank location in the system
However, small system tank sizing is commonly accomplished by allowing one gallon of tank capacity for each 5 >000 Btu/hr of heat loss.
This "rule of thumb" does not work for large systems because of the greater importance of the four factors listed above.
In the guide published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers, tank volume is determined from the ASME equation;
vvt "
(.0004lt - .04661 Pa Pa
Pt " Po
x vs
This equation assumes expansion tank temperature of no greater than 70F.
whe re;
V6 t Pa
P-j-
PQ
" Minimum gallonage of the tank * System volume in gallons " Maximum average water temperature in F " Absolute pressure in tank when water first enters...
usually atmospheric (l4.7 psi at sea level) " Absolute pressure in tank created by initial fill...
psig fill pressure plus atmospheric " Maximum absolute operating pressure...maximum psig pressure
st tank plus atmospheric
Page 21-1
17702
To develop a similar working formula we will substitute "C" for the first factor in the right hand side of the equation...for sea level conditions.
Vt C x V6
.0004lt - .0466 vhehe C=
Pjj. - ^
Pt p0
Let's solve for C;
t -230F
Pa - 14.7 psi absolute...atmospheric pressure
Pt*=26.7 pei absolute.. .12 psig initial fill pressure
PO" 59*7 P6i absolute...45 psig maximum operating pressure
then
,, C"
then...if;
.0004lt x 230 - .0466
14.7
i4.7
2E77 " 59-7
"
Vt " C x V6
and...the specified system has a volume of 960 gallons
Vt = .157 x 960 or 150.7 gallons
EQUALIZING CONNECTION
FIGURE 21-1
To supply an expansion tank volume of 150.7 gallons, it would be common to pipe three tanks in parallel.
,Page .21-2
17703
The tables in this chapter will supply the information necessary to easily and readily determine expansion tank 6ize.
Tables 21-2 through 21-6 specify gallonage in different segments of the system. Simple addition will establish VB...total gallonage in the system.
Table 21-7 provides factors for C under varying pressures and temperatures. Simple multiplication of the established system volume by this factor will determine the minimum size of the expansion tank.
When expansion tanks are located in an area where the temperature may become considerably more than 70F, the ASME equation must be corrected for the following reasons:
1. The air cushion becomes hotter. Since the air has no place to expand, it6 pressure increases.
2. The hotter water in the expansion tank causes additional vapor or steam to mix with the air cushion. This action increases the pressure on the water in the tank and, hence, the system pressure.
The corrected factor C becomes:
C--
.0004lt .0466
T-tx_i
Pt - Pvf Tf P0 - I vt
where:
t -Maximum average water temperature in degrees F.
Pa "Absolute pressure in tank when water first enters...usually atmospheric
P-t -Absolute pressure in tank created by initial fill.
P0 -Maximum absolute operating pressure.
Pvf -Absolute vapor pressure in psi at the fill temperature.
P^ =Absolute vapor pressure in psi at the tank operating temperature.
Tf -Absolute temperature of the tank at operating conditions... 460 plus degrees F.
Tp -Absolute temperature of the tank at fill conditions...460 plus degrees F.
To illustrate the effect of a heated tank, it is assumed the system waB filled at 40 F- With the system in operation the tank temperature gets to 125F. All other conditions remain the same as in the example immediately preceding.
Page 21-3
17704
Solving for C
t = 230F Pa *= 14.7 psi absolute--atmospheric pressure
=26.7 psi absolute--12 psig initial fill pressure
PQ c 59.7 psi absolute--45 psig maximum operating pressure
Pvf = .122 psi absolute at 40F tank temperature. See Table 21-1
P^ " 1.942 psi absolute at 125F tank temperature. See Table 21-1
Tt = 585 Absolute--460 + 125 - 585
Tf = 500 Absolute--46po + 40 " 500
.ooo4i x 230 - .0466
C s lV. 7
555 14~?J " *186
(26.7 - -122) " 550 x 59.7 - 1.942
Therefore under these conditions
Vt - -186 x Vs
for a specified system volume of 960 gallons
= .186 x .960 *= 179 gallons
Because the tank operates at a temperature of 125F -- all other conditions in the two examples remaining the same -- its volume must be increased 19$.
Warning This percentage increase applies only to the conditions in the examples
and should not be used for other operating or fill pressures.
To illustrate the use of the tables a three-story garden type apartment with a boiler in the basement requires 390,000 Btu/hr. The linear feet of N85-L Heatrim installed is 550.
Linear feet of piping in the installation is:
2" pipe -- 50 ft 1-1/2" pipe --400 ft 1" pipe ---200 ft
3/4" tubing-----200 ft.
(not including radiation)
Page 21-4
17705
Boiler used is a G-4010
Volume of water in system
Boiler 50 ft. of 2" pipe 400 ft. of 1-1/2" pipe 200 ft. of 1" pipe 200 ft. of 3/4" tubing 550 ft. of 3/4" Heatrim -
77-4 gal.
8.7 " 42.4 "
9.0 " 5.0 " 14.8 "
(See
It H
11 It
U
table
II tt
tl tt
11
21-2 21-6 21-6 21-6 21-6 21-4
TOTAL
157-3
Assuming expansion tank located in a cool 6pace in the basement and allowing 10 feet between each floor of the apartment building, the radiation on the third floor will be approximately 22 feet above the expansion tank. Using the line showing a minimum height of the system above the tank of 27.7 feet (see Table 21-7) with the corresponsing fill pressure of 16 psig and an average system temperature of 210^ a constant "C" is found to be .16. The expansion tank volume is 16$ of the system volume. Therefore the tank volume is;
Vt = .16 x 157-3 gallons
= 25 gallons
Generally, in large systems, expansion tanks are located in a reasonably cool area making Table 21-7 valid.
Should the tank or tanks be located over the boiler, where the heat rising from the boiler will warm the tank, a correction of tank volume for a temperature of 125F should be adequate.
Table 21-8 has been prepared to provide correction factors. These factors are applicable only to Table 21-7- They are used as multipliers.
Example The value of C used in the problem solved on page 21-5 was .160 as
suming the tank wa6 located in a space of 70F or less. If the tank had to be located immediately over the boiler, a new constant "C" must be obtained. At 16 psig fill pressure the correction multiplier from Table 21-8 is found to be 1.20.
Therefore the new value of C equals .16 x 1.20 or .192 and the tank volume for the system in the example becomes
157-3 x -192 or 3 gallons
Page 21-5
17706
Tank Temperature Degrees F 40 45 50 55 60 65 70 75 80 85 90 95 100 105 no 115 120 125 130 135
Table 21-1
Vapor Pressure psi absolute .122 .148 .178 .214 .256 .306 .363 .430 507 .596 .698 .815 .949 1.102 1.275 1.471 1.692 1.942 2.222 2.537
Page 21-6
17707
Table 21-2
VOLUME OF WATER IN GALLONS - AMERICAN-STANDARD HOT WATER BOILERS
:tions
G-4o
G-oO A-5 A-5
3 26.6
4 33-6
57.5
1--l u~\ --1 1
3 41.1
64.0
6
48.4
91-5
75-5
167
7
55-5
105.5
84.0
189
8
62.9
119.0
93-0
211
9
70.1
133-0
102.0
234
10
77-4
146.5
111.0
256
11
160.5
118.5
278
13
225.0
302
15 253-0
17 280.0 19 308.0
21 336.0
22 387.0
25 427.0 28 470.0
31 510.0
33 575-0
37 630.0
4l 685.0
Page 21-7
17708
Table 21-3
VOLUME OF WATER
in
CAST IRON RADIATORS AND BASEBOARD
Thin Tube (Arco Radiators)
8A gallons per 100 sq. ft. (EDR)
Large Tube Radiators----------------- 15-25
""
"""
"
Sunrad -- 5 x 20 ............... .............. 9.00* "
-- 7-1/2 x 23 ----------------- 10.00* "
" .................................
Radiantrins New Model 0----------------------- 18.0 Gallons per 100 linear feet Model 10----------------------- 2k. 0
* Applies to radiators of 10 sections or larger. For radiators less than 10 sections, multiply indicated capacities by 1-5-
17709
Page 21-8
Table 21-4
VOLUME OF WATER IN
FINNED TUBE RADIATION
Heatriro N50 N85 N110
Element ------------------------ 1-32 gallons per 100 linear feet
" 2.69
................................................
" 4.42
Temtrim or Similar
Finned-tube Radiation
2" Steel tube element ----- 17.4 gallons per 100 linear feet
li'................................
lj...............
"
--- 7-8
-- 6.8
.....................................
..............................
Table 21- 5
VOLUME OF WATER IN
CONVECTORS
Multifin
74 Element ------------ ------------- .24 gallons per 100 inches*
16 --8 A10
" " '
------------ ------------ .43 gallons per 100 inches
------------ ------------- .67
" tt
H
............. .-------------1/12
"
11
Arco
#4 Element ------------------------- I.87 gallons per 100 inches*
#6 A8
j(-10
" "
"
------------ ------------- 2.89 gallons per 100 inches
------------ .............- 3.84
nn
------------ -------------4.85
it tt
* Inches of length taken as length of cabinet
Pa.g~ 21 - 9
17710
Pipe Size
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4 5 6 8 10
Table 21-6
VOLUME OF WATER IN
STANDARD PIPE AND TUBS
Gallons per 100 linear feet
Std. Steel Pipe
Copper tube
1-57 2.77
4.49
7-79 10.6 17-4 24.9 38.4 51.4 66.1 104.0 150.0 266.0 419.0
1.21 2.51 4.29 6.53 9.24 16.1 24.8 35-4 47.9 62.2 97-0 13.9 24.3 37-8
Page 21-10
17711
Table 21-7
Fill Press. (psig)
Max. ht. of system above
Tank
(ft)
Value of Constant C
(A) Max. temp. 230F
(B) Max. temp. 210F
12 18.4
.148
.123
16 27-7 20 37-9 24 46.2 28 55-3 32 64.7
193 .242 .312 .408 .542
.160 .201 .259 338 .450
NOTE;
1. For this table to apply, tank temperatures should be no more than 70F.
2. This table is based upon a relief valve setting of 50 psig. Smaller size tanks result.
3. Maximum temperature equals maximum system average temperature.
4. For multiple story structures of three or more floors use column B (Max. temperature of 210F).
5- Fill pressure determined by maximum height of system above fill points - 4 psig allowed in highest piece of radiation.
Table 21-8 Multiplication Applicable only to Table 21-7
6sure psig
Correction Factor
12 1.55
16 1.20
20 1.30
24 1.4?
28 I.05
32 2.14
Page 21-11
17712
CHAPTER 22
HOT WATER BOILER MANIFOLD SIZING
17713
CHAPTER 22
HOT WATER ROTT.ER MANIFOLD SIZING
As in sizing steam boiler manifolds (Chapter 18) it is necessary to re strict water velocity to insure quiet flow.
Unlike steam manifolds, there is no fixed velocity limit in manifolds. For pipes two inches and smaller, water flow should be limited to 1 feet per second, while velocities up to 10 feet per second are frequently used in 6-inch or larger pipes. It should be kept in mind that in large systems the mains with the high water velocities are a considerable distance from the radiation where water velocity noise would be objectionable.
To arrive at the proper manifold size with hot water boilers^the basic equation is;
Volume = Area X Velocity or
Volume Area Velocity
where
Area is expressed in square inches Volume is expressed in cubic inches per second Velocity is expressed in inches per second
In low temperature hot water heating, the volume is based ur.cn a :"0F temperature drop of the system.
The weight of one cubic foot of water is taken as ox.1) wounds. Vnen cooled 20F it gives up 62.5 X 1 X 20 or 1250 Btu.
Volume in cubic feet per hour
-B--t-u----p-e--r----h--o--u--r- or M--bh--
1250
1.25
Volume in cubic inches per hour
Mbh X cubic inches per cubic foot = 1-25
Mbh X 1728 S 1-25
Volume in cubic inches per second
= --Mb--h -------X---1--7--2--8- --. seconds per hour
Mbh X 1728 i Mbh 1.25 X 3630 ' 2.0
Velocity in inches per second equals velocity in feet per second X 12.
3age 22-1
17714
Therefore, the equation for cro6s sectional area in square inches becomes:
Area jj-g- 12 x Velocity (ft/sec)
_ Mbh 2.6 x 12 x Velocity
_ _______ Mbh 32 x Velocity
or Velocity (ft/sec)
Mbh 32 x Area (sq. in.)
Example:
Calculate the velocity necessary to supply 336,000 Btu through a 2-inch pipe, which has an area of 3-356 square inches.
w
, 336
336
,
Velocity
3.3^6 x 32 " p07.lt " 3-13 ft/second
Table 22-1 has been prepared to aid in selecting manifold pipe sizes on hot water boilers.
; , f,
t: ^
It may be used as follows.
Example No. 1
The G-6022 and G-6028 boilers have respective outputs of 2,436,000 Btu/hr and 3,132,000 Btu/hr. Minimum piping recommendations for these two boilers, as shown in the Technical Catalog Bulletin, specify two 4 inch supply risers ana a 6 inch header. Under conditions of maximum output, what water velocities will be obtained?
The G-6022 Load per riser = 2,43o,OQO . p^218,000 Btu/hr.
Referring to Table 22-1 on the 4 inch pipe size line, it is found that a load of 1,218,000 Btu/hr requires a velocity of 3 feet per second.
The 6 inch header, after it has picked up the entire boiler capacity
of 2,436,000 Btu/hr is working at velocity of less than 3 feet per second.
Page 22-2
17715
The G-6028 Load per riser
3,132,000 = 1,566,000 btu/hr.
Referring to Table 22-1 on the 4 inch pipe size line it is found that a 4 inch pipe with 3-5 feet per second velocity is good for 1,1+25,000 btu/hr. and at 1 feet per second the capacity is 1,630,000 btu/hr. Obviously, the water velocity is less than 4 feet per second and more than 3-5 feet per second. By interpolation the actual velocity is shown to be approximately 3.8 feet per second.
The velocity in the 6 inch header after it has picked up the entire boiler capacity of 3,132,000 btu/hr is slightly less than 3-5 feet per second.
Velocities in the return header and risers are identical.
Example No. 2
The A-710-W0 boiler has a gross I:B:R output of 1,760,000 btu/hr. It is supplied with four 4" flow tappings and two 6 inch return tappings. To carry the full capacity of the boileq how many supply risers and return risers will be required and what manifold size is needed. -
Referring to Table 22-1 it is found that a 4 inch riser with e velocity of 4 feet per second is capable of handling only 1,630,000 btu/hr. Obviously, it is desirable to use two supply risers instead of one.
The load per riser = f?70,000 - 680,000 btu/hr. From the table it is found that a 3 inch supply1riser is good for the 880,000 btu/hr. at a velocity about halfway between 3-5 arid 4.0 feet per second, which is en tirely satisfactory.
The neader carrying tne full load of 1,760,000 btu/hr. must be 5 inches since 4 inch pipe is too small. The velocity in the header will be less than 3 feet per second, again a satisfactory condition.
Return risers and manifold will be sized identically.
Tappings selected icr both sup.-iy and return risers must be chosen to provide goo:, distribution of water to the boiler.
it is suggested t.nat tne Ft an i first CX sections be used for the flow risers. The returns snouiu be eivi/ed between the two 6 inch return tappings (bnsnea so 3 inches) in the re secpi.-n.
Page 22-3
17716
Pipe Size Inches
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2
3 3-1/2 4
5 6 8 10
TABLE 22-1
Btu/Hr. Capacity of Steel Pipe for
20F System Temperature Drop
I. D. CrossSection
Pipe Area .304
533 .8413 1.496
2.036
3.356 4.788
7-393 9.885
12.730 20.006 28.830 51.162
81.585
Flow R a t e -- F t / S e c
3.0 3-5
4.0
29,200
34,000
39,900
52,000
59,600
58,100
80,700
94,000
107,800
143,500
167,200
191,000
195,500
228,000
260,000
322,000
376,000
429,000
460,000
535,000
612,000
710,000
827,000
950,000
1,108,000
1,265,000
1,220,000
1,425,000
1,636,000
1,925,000
2,240,000
2,560,000
2,770,000
3,230,000
3,820,000
4,910,000
5,730,000
6,540,000
7,840,000
9,130,000
10,430,000
OOO
LT\
C\
Page 22-4
17717
CHAPTER 23
CONVERTORS
17718
CHAPTER 23
CONVERTORS
A convertor i.6 a heat exchanger that is used specifically to transfer heat from steam to water. These unit6 are employed when;
1. A hot water heating system is connected to a 6team 6y6tem with the steam boilers being the initial source of the heat.
2. Steam i6 purchased from a district 6team system but hot water heating is desired.
3- Hot water heating is desired in tall buildings, where the hydrostatic pressure created by the water would become too severe on the piping and radiation at the lower levels. In Figure 23-1 the method for supplying hot water heating in tall buildings is illustrated. Here the solution is to use one steam boiler in the basement to generate the 6team necessary to operate a convertor for each group of four floors. Each con vertor acts as a hot water boiler supplying heat to a zoned four-6tory segment of the building. Hydrosta tic pressures are brought within practical limits, and only one lowpressure 6teara boiler is necessary even though it operates three separ ate and distinct heating systems.
FIGURE 23-1
The small individual systems thu6 created use relatively smaller pip ing and less costly pumps and accessories.
Page 23~1
17719
FIGURE 23-2
Figure 23-2 shows a convertor as manufactured by the Industrial '-'V
Division of American-Standard. The steam enters'the top of.'`the ,shell
?'
at the right and fills the space around the water tubes. .The water, flow- ,
ing through the tubes becomes heated and the condensate formed from the
condensed steam drains off from i the bottom of shell at the left hand.end.'.
The water enters one..side of the cast iron bonnet flpw'ing through the '
Uj-tube bundle and returns to the other side.. This flow;.;arrangement is.
called a two-pass. By rearranging, the spacing of thettubes,and the ;-,
../;
partitions cast into the ..bonnet, a four-pass flow can be obtained. The
two-pass flow is advantageous to use because the pressure drop, of the
water through the heater is less than for, the four-pass'arrangement. ; V' I
The U-tube design with the tubes fastened to a -tube ,sheet...at one, :,end only >:;
of the unit permits a free expansion of the- tube bundle..; With a steam - ,
to water heat exchanger, baffling is not as much-a problem asrwith the water
'
to water type. The,round plates'.seen, in the illustration ^serve'to: support' '' v
and hold the tubes apart so the steam can completely surfound:them.
Page,23-2. ` .
-VpV:;
17720
FIGURE 23-3
Figure 23-3 illustrates a convertor piping arrangement which is selfexplanatory. In this illustration the thermostatically controlled steam regulator holds the water leaving the convertor at some fixed temperature, in the same manner as a boiler operating on a fixed water temperature. To control the space temperature, the pump could be cycled by the space thermo stat or a three-way valve, thermostatic control by either indoor or out door thermostat can be provided to modulate the water temperature to the space. In this last instance, the pump would operate continuously.
Sizing the piping for the system would follow conventional engineered design. The heat loss of the space served by the 6team is determined and a decision made to design for either a 20F or 10F temperature drop. The gallons of water to be circulated is then determined. If the g.p.m. are large, pipe sizes will be selected and the resistance of the piping and fittings determined. To this valve will be added the resistance of the water flowing through the convertor. A pump is then selected that has a head equal tc^ or greater thar^ the total resistance of the system.
Page 23-3
17721
CHAPTER 24
SIZING THE BOILER
17722
CHAPTER 24
SIZING THE BOILER
To size a boiler accurately for either 6team or hot water, its capacity must be equal tc^ or greater than, the load. Either a net installed radiation load or a gross load may be estimated.
These requirements can be any or all of the following defined loans;
1. Radiation Load
-- the estimated heat emission in square feet,E. D. R. or Btu per hour, of the connected radiation.
2. Piping Load
-- the estimated heat emission in Btu per hour of the piping connecting the radiation and other apparatus to the boiler. A close approximation for this can be considered at 15$> of the net load when 1" magnesia pipe insulation is used.
3. Pick-up Load
-- the estimated load in Btu per hour re quired to bring the space up to daytime temperature following a nighttime set back of the thermostat. This load can also be considered as 15?j of the net radiation load.
L. Miscellaneous Load -- any load other than those listed above such as domestic hot water, snow re moval systems, industrial processes, etc.
In residential application it is common practice to size the boiler on the net installed radiation load, since allowances have been built into the net rating of the boiler to allow for pipe loss, pick-up and the heating of a nominal amount of domestic hot water.
Where abnormal conditions exist, such as a heavy domestic hot water demand or excessive piping losses, the piping, pick-up, miscellaneous and radiation loads should be added to arrive at the total gross load requirement. The gross capacity or output of the boiler selected must be equal to or greater than the gross load.
page 24-1
17723
FIGURE 24-1
Referring to Figure 24-1, it is seen that only a fraction of the heat input to a boiler gets into the boiler water and becomes the boiler's gross capacity or output. In gas boilers that are rated by the American Gas Association this fraction is 0.8 .. this figure also says that the boiler efficiency is 80?. In oil boilers the fraction varies. It may be 0.7 to 0.75 depending on the boiler and the burner adjustment.
The I=B=R net installed radiation capacity of the boiler is about 75?; of its output or gross capacity.
It is noted that while some of the btu/hr. difference between in put and output is lost from the boiler jacket, the major portion of this heat quantity goes into the chimney.
From Figure 24-1 it is evident that the 20,000 Btu/hr. allowed for pick-up, pipe loss and the heating of domestic hot water is about 33-1/3? of the net I=B=R rating.
This allowance is divided approximately as follows;
Pipe Loss----------------------- 15?
Pick-up--------------------------- 15?
Domestic HotWater------- 3-1/3?
TOTAL
33-1/3?
Page 24-2
17724
Example No. 1 For examples of these various conditions, let'6 assume a hypothetical
modernization job involving a boiler replacement. Our problem will be to size a 6team boiler in an old four story home of an unknown heat loss. The boiler must be replaced and the owner is desirous of changing from stoker-firing to oil. When the existing boiler is examined, it is found to be an American-Standard Ideal Water Tube S-36-T-T with a net steam rating of 2,070 square feet.
It was common practice years ago to oversize the boiler to insure adequate grate area and sufficient capacity for quick pick-up after long shut-down periods. A further examination disclosed that, by actual count of radiators, only 1,470 square feet of radiation or 352,000 Btu per hour was connected to the boiler. Piping and pick-up loss was considered normal because all piping was insulated with 1" magnesia insulation.
Based on both loads indicated above, a decision was required to select a size between an A-509S boiler which i6 equal to or greater than the old boiler size, or an A-507S which was equal to or greater than the net load requirements of the system.
Since the owners indicated that the existing radiation maintained good comfort conditions during the 25 years of operation, satisfying the radiation load of 1,470 square feet with an A-507SB boiler is all that is required. The maximum requirements for domestic hot water are esti mated to be 34 gallons per hour.
To determine the adequacy of the boiler selected, an analysis may be made as follows;
Gross Capacity of the A-507SB
508,000 Btu/hr.
Net Load (1,470 sq. ft.)
352,800 Btu/hr.
Pick-up Load - 1% of 352,800
52,920 Btu/hr.
Pipe-loss - 1% of 352,800
52,920 Btu/hr.
* Domestic Hot Water (34 gph x 833) = 28,320 Btu/hr.
Total Gross Load
"=
486,960 Btu/hr.
Surplus Boiler Capacity =
21,040 Btu/hr.
*N0TE: 1 gallon of water heated 100F requires 8-1/3 x 1 x 100 or 833 Btu.
Example No. 2 If this same hypothetical house could be made into a multiple apart
ment structure by merely inserting partitions and adding bathrooms, with out necessitating any major change in the heating system outside of an isolated relocation of a radiator, then a parallel can be made to the original example, and an illustration of how increased water heater requirements can change the boiler size.
Page 24-3
17725
Let's assume the house can be converted into a total of lb apartments, one bedroom with single bath and kitchenette for each one. The total domestic not water demand is estimated at 153 gallons per hour.
To size the boiler for this example a similar analysis to the one made for Example No. 1 is in order.
Installed Radiation (l,470 sq. ft.) = 352,800 Btu/hr.
Pipe Loss (1% of 352,800)
52,920 3tu/hr.
Pick-up (15& of 352,800)
52,920 Btu/hr.
Domestic Hot Water (153 x 833)
127,450 Btu/hr.
Gross Load
568,090 Btu/hr.
The gross capacity of an A-508SB boiler is 588,000 Btu/hr. Therefore the eight section boiler would be adequate.
Page 24-4
17726
SIZING-CHIMNEY AND BREECHING
17727
CHAPTER 25
SIZING -- CHIMNEY AND BREECHING
Proper draft in the combuBtion space of a ooiler i6 of utmost im portance to the satisfactory operation of the burner. Without adequate draft, sooting will occur, efficiency of combustion is lo6t and noisy burner operation can result.
Excessive draft conditions can be as troublesome as insufficient draft. Usually this condition i6 readily corrected by flue dampers, draft regulators, divertors or these devices in combination.
What is draft? Draft is really a difference in pressure exerted by a column of hot gases in a chimney and a column of cold air of the same height outside the chimney.
To illustrate, assume two columns, each 30 feet high, and each 1 square foot in cross sec tional area, supported by the pans of a giant balance. See Figure 25-1.
Further assume that one column is made up of flue gases at 450F, the other of air at 30F.
Each column, then, will con tain 30 cubic feet. Each ha6 a different weight.
FIGURE 25-1
Weight per cubic foot Number of cubic feet Total Weight (pounds) Pressure (lbs/sq. ft.)
Hot Gases
30. 1.32 1.32
Cold Air .081
30. 2.43 2.43
The greater weight of air would tip the scale, raising the column of hot gases. The degree to which it tips depends on the pressure difference --in this case 1.11 pounds per square foot.
Page 25-1
17728
1.11 pounds per square foot divided by 144 gives .0077 pounds per square inch.
Because draft is measured in inches of vater -- and 1 pound per square inch equals 27.72 inches of water -- we multiply .0077. x 27-72 to get .21 inches of water draft. Thi6 i6 a very tiny force. Because it is so tiny the boiler room must be open to plenty of air for ready combustion.
This .21 inches of water is the theoretical draft available from a 30-foot high chimney when the stack gases, weigh .044 pounds per cubic foot and the outside air weighs .08l pounds per cubic feet.
The draft would increase if the outside air-cooled, or if the gases got hotter or more humid. It would decrease if the opposite occurred.
Other factors affecting draft are:
1. The tightness of the chimney. If it leaks, the cold entering air lowers the temperature of the gases and adds to the volume of gase6 to be vented.
2. The roughness of the chimney lining.
3. Off-sets in the chimney and other obstructions in the path of the gases.
4. Outside air turbulence, either natural on a gusty day or caused by adjacent trees or buildings, may create down drafts.
The draft calculated above is theoretical. As the gases start to flow, the friction in the chimney causes a loss so that there is less draft at the chimney thimble where the smoke pipe enters.
Friction in the smoke .pipe and the boiler flues reduces the draft still further so that the draft available in the combustion chamber is usually a very small force.
Draft may be classified as;
1. Natural 2. Forced 3 Induced 4. Combinations.of two or al 1 three.
Natural draft occurs when a chimney is employed to overcome all resis tance to the air flow into the combustion chamber .and the friction of the flue gases flowing through the boiler, the smoke pipe and the chimney itself.
Forced draft is the case where a fan is used to force the air into the combustion chamber. With gun type oil burners add mechanical stokers forced draft is employed.
Page 25-2
17729
Induced draft uses a fan to suck the flue gases through the boiler and deliver them to the chimney, The use of draft booster fans is an example of thi6 type of draft.
The use of either the forced draft or the induced draft principle re duces the natural draft requirements on a job -- which reduces the required chimney height.
Within limits, chimneys may be increased in cross sectional area to reduce the gas velocity and the flow friction through it. If the cross sectional area is made too great for the quantity of flue gases flowing, these gases will not fill the chimney. Air will flow down inside the lining mixing with the flue gases and retarding their flow. The draft will be materially reduced to unsatisfactory levels.
When chimneys are too large in area, but sufficiently high, a smaller size liner may be inserted from the top. The space between the new liner and the old must be capped off at the chimney top to prevent oold outside air from circulating down between them.
The chimaey height is determined by the draft requirements and the area by the Btu per hour input to the boiler.
The height and cross sectional size of chimneys required by AmericanStandard boilers are specified in the Technical Catalog Bulletins.
Chimneys serving more than one appliance should have separate flues for each.
Where it is necessary to hook up two fuel-burning appliances to the same flue, they must each have their own smoke-pipe with the smaller ap pliance connected to the chimney at a higher level.
If they are not connected separately, the pipe not in operation may damp off the operating pipe. The smaller appliance should be piped into the chimney at a higher level where its effect will be minimized.
Ga6-fired boilers must be equipped with draft hoods to let air into the vent and to divert down-drafts that might blow out pilot flames.
The same result is achieved for oil-fired or stoker-fired coal boilers by installing a draft stablizer in the smoke pipe.
Adjustment is made by moving a weight on the damper door.
Boilers should be installed with not more than one 90 elbow in the smoke pipe between the boiler and the chimney. If additional elbows or fittings are used, which add resistance to the flow of combustion products within the venting system, the equivalent length of 6ucn fittings should be added to the measured length of the venting system. Never use connectors smaller than the boiler flue outlets.
Page 25-3
17730
A breeching is essentially a manifold. Its prime purpose is to collect the gases from a large boile^ with multiple smoke pipe% or the gases from a battery of boilers and deliver these products of combustion to the chimney. A constant size breeching i6 recommended. It must be large enough to handle the combined flue gases from all connections to it.
The breeching size i6 usually greater than the chimney, a situation requiring an adaptor, to make the connection of the breeching to the chimney.
For example; The problem is to tie a 30" square piece of breeching into a circular chimney with a 20" diameter.
Obviously, the breeching mu6t be brought down to a width of 20 inches.
This means that in order to main tain the same 900 square inches of cross-sectional area, the 20-inch width will need a 45 inch height.
The solution is to add the extra 15 inches in height at the top of the breeching to introduce the flue gas into the chimney in a rising pattern.
FIGURE 25-2
When batteries of boilers are step-operated -- one on at a time and one off at a time -- it is advantageous that the boiler nearest the chimney be operating first on the "on" cycle and last on the "off" cycle.
This arrangement with properly designed breeching will eliminate the problems of "spillage" of flue gases from one boiler to another.
Breeching for more than one boiler should, at a minimum, have the total cross-sectional area of all the smoke-piping for each individual boiler.
If the requirements of space or dollars dictate a smaller breeching area, it may be reduced to a maximum of 10$, providing stack height and cross-sectional area are adequate, and a straight breeching can be designed.
Breeching sizing is based on one square inch of area for each 9,000 Btuh of heat release in the fuel.
Page 25-4
17731
Column A Diameter
inches
12
13 14
15 16
17 18
19 20 21 22
23 24
25 26 27 28
29 30 31 32 33 34 35 36 37 38
Table 25-1
Column B Area
Square Inches
113 133 154 177 201 227 254 283 314 346 380 415 452 491 531 572 615 660 . 706 754 8o4 855 907 962 1017 1075 1134
Column C Equivalent in Rectangular size
12 x 10 12 x 12 14 x 12 14 x 14 15 x 14 15 x l6 17 X 16 17 X 18 19 X 18 21 x 18 20 x 20 22 x 20 22 x 22 24 x 22 26 x 22 26 x 24 28 x 24 30 x 24 32 x 24 34 x 24 36 x 24 39 x 24 41 x 24 36 x 30 38 x 30 40 x 30 42 x 30
Page 25-5
17732
Example No. 1 Design the flue headers, manifolds and breeching for two G-6022 boilers
in a battery.
Heat input
= 3,045,000 btuh per boiler
Header & manifold area =
= 339 square inches
Diameter of Header D2 - y^JLx 4 , ^32
D - V432 or 21"
Example No. 2
Breeching area for two boilers equals twice the area for each header
or 2 x 339 or 678 square inches.
x
If the breeching is circular then;
^.ysjrrr
D - 29-3" or 30"
If the breeching is rectangular, it could be: 32" x 24"
To save time, use Table 2`;-l. Having determined that the breeching area required is 339 square inches (Example No. 1) enter Table 25-1 in Column B, going down the column to the area in square inches that is equal to or greater thaD 339- In this instance the number is 346. Reading to the left a round manifold of 21 inches is indicated. Reading to the right a rectangular manifold of 21 x 18 is shown as being satisfactory.
See Figure 25-2 for breeching arrangement.
To summarize, helpful hints are listed below.
HELPFUL HINTS
1. Always use individual vents in preference to combined vents, when pos sible and practical.
2. Never use connectors smaller than the boiler flue products outlet(s).
3. Always make the rise above the boiler flue products outlet(s) as great as possible. This is especially important when connecting more than one boiler to a single chimney.
Page 25-6
17733
4. Keep the length of connectors as 6hort as possible.
5. Use an inside chimney in preference to an outside chimney, when possible and practical.
6. Use insulated vents, when long connections to chimney cannot be avoided. Insulation on the rise from the boiler flue products outlet(6) is par ticularly important.
7. Eliminate all possible flue turns in the connection to the chimney. Remem ber that when more than one elbow is used between the boiler flue products outlet(s) and the chimney, allowance for the added resistance must be made by adding equivalent length of such fittings to the vent system measured length before applying draft loss curves.
8. Never let the connector protrude beyond the inside wall of the chimney nor permit projections into the flue gas passage.
9. Avoid caps on chimney that will restrict the free area of the chimney.
10. "Streamline" the vent system a6 much as possible -- changes in direction, shape and flow area should be accomplished separately and as gradually as possible.
11. Round connectors are to be preferred over square or rectangular. Square or rectangular flue pa6sa6es are apt to promote unpredictable turbulence that will interfere with the normal flow of combustion products. Also, flat sides of square or rectangular connectors are more likely to develop noise due to resonance.
12. Lateral connectors should be run horizontal, or with minimum slope per mitted by local code, to keep the rise above the boiler flue products outlet(s) a6 great as possible.
13- Breechings that connect two or more boilers to a common chimney must be sized to handle the combined load. A single size manifold of sufficient size for the load should be used.
14. Never connect 2 or more chimneys together to increase flue area available for a boiler installation. The ASHRAE Guide says "When two chimneys are connected at the bottom, hot gases in the U-tube thu6 formed would be in unstable equilibrium. Cold air from the top would descend through one such chimney and drive the hot gases out of the other, thus annulling the draft." If 2 or more chimneys are used, each chimhey should be used separately for part of the boilers. Never use a continuous manifold between the chimneys.
Page 25-7
17734
2
^5, 7^35
CHAPTER 26
LOCATING THE BOILER
17736
CHAPTER 26
LOCATING THE BOILER There are three possible places to locate a boiler:
1. Below the system...in a basement.
2. Above the system...in a penthouse, on the roof of the building.
3. Alongside the system...in a separate room close to, but detached from, the space to be heated...industrial.
Below the System -
Locating the boiler below the system creates...for any building...the best possible draft condition. Chimney height is at its maximum.
For steam systems, the basement is the ideal location because gravity helps to bring condensate back to the boiler, even though, for reasons of fuel economy, a vacuum system using condensate pumps is often specified.
Even in tall buildings, low pressure steam boilers operate successfully out of a basement location because steam does not build up high hydrostatic pressures.
For any single hot water system, hydrostatic pressures in tall buildings present insurmountable problems. The solution (see Chapter 25) is to use a steam boiler and a series of convertors.
Our present line of large boilers, improved from 30 psig operation to 50 psig, can be used in buildings 80$ taller than for former maximum ca pability .
Because of hydrostatic pressures, expansion tanks must be larger as building height increases.
Above the System
Roof or penthouse systems are rarely, if ever, acceptable for either coal or oil-burning boilers because of chimney height.
The use of steam boilers on building roofs is possible but impractical because head requirements on condensate pumps become too great.
Because of the help from gravity, low pressure hot water systems can be used in roof installations. In addition, expansion tank sizes are economical.
Alongside the System
Because of the low chimney height, ga6 is the ideal fuel for industrial heating systems, though oil and stoker-fired boilers with somewhat higher
Page 26-1
17737
chimney requirements are often used. Hand-fired coal boilers usually present architecturally unacceptable chimney height specifications.
For steam systems, the smaller installations can usually be set up to return condensate by gravity. Usually, however, condensate pump6 are used.
For hot water systems, industrial applications eliminate the major problems of high hydrostatic pressures and large expansion tanks. Locating the Second Boiler in a Steam System
When more than one boiler is used in a 6team system, it is imperative that all boiler water lines be at the same level.
While the water line problem makes it desirable to U6e boilers of the same design in new installations, it is not always possible.
When, for instance, an estimated heating load indicates the use of a G-60 boiler with a 44" water line plus a G-40 with a 35-l/2*water line... it would be necessary to install the G-40 on an 8-1/2" concrete pad.
At times it may be necessary to pit a steam boiler to effect the equalizing of water lines.
Page 26-2
17738
CHAPTER 27
BLAST COILS AND UNIT HEATERS
17739
CHAPTER 27
<*
BLAST COILS AMD UNIT HEATERS
Two types of concentrated heat loads on a boiler are blast coils and unit heaters.
In both cases a coil, either steajn or hot water, is U6ed to heat forced hot air.
The difference is that blast coils are used in duct systems while unit heaters hang free in the space being heated. Propeller type fans are mounted on the unit heaters, either manually or thermostatically controlled, and the air leaving the heater is directed by louver as it leaves the heater.
The forced circulation of air condenses steam 60 rapidly, particularly at start-up of the daily heating cycle, as to create a vacuum in the heater which can suck water from the wet return up into the heater itself.
To overcome thi6 vacuum and to insure adequate removal of condensate, steam systems using unit heaters normally carry a condensate pump for each heater, or for a battery of heaters.
With the heaters installed at a high level, a direct, vertical, drop-leg to the condensate pump allows for fast and positive drainage of the condensate.
Unit heaters, for best results, should be operated at a minimum of 2 psig steam pressure at the heater inlet. Where entering air temperature, however, is below freezing, pressure should be at least 5 psig.
Pages 27-2 and 27-3 illustrate recommended piping arrangements for unit heaters.
Blast coils serve two functions;
1. To temper ventilation air.
2. To supply heated air.
In blast coil systems, air is circulated through the ducts by centri fugal blowers.
The following pages show piping diagrams for individual blast coils in various systems plus a list of "do's and don'ts".
Page 27-1
17740
PIPING DIAGRAMS HORIZONTAL UNIT HEATERS
)
m
LOW PRESSURE GRAVITY SYSTEM
VAPOR OR VACUUM SYSTEM
HOT WATER SYSTEM
Page 27-2
17741
PIPING DIAGRAMS VERTICAL UNIT HEATERS
LOW PRESSURE GRAVITY SYSTEM
VAPOR OR VACUUM SYSTEM
HOT WATER SYSTEM
Page 27-3
17742
PIPING DIAGRAMS BLAST COILS
\Typical piping diagram--vacuum tyttom, low prat*
sura ttoam--coil luboc horizontal
'> >
Coil Installation Coils must be accurately
Install casings of all heavy duty coils level for either horizontal or vertical air flow. Install coils accurately with a spirit levSl, not by measurement from building members.
Coil Piping Multiple Coil Banks
The diagram on preceding pages show the piping arrangements for single coils. The same arrangements should be used on multiple coil banks, the most satisfactory arrangement being to build up the proper system by dup licating the diagrams on each coil in the bank. However, colls in parallel (side by side) or in series (one behind the other) in the air flow may, If desired, be controlled by a common valve. Sach coil in a coil bank, whether individually controlled or controlled by a common valve, must have its own trap and air venting system.
Provide All Coils with Air Vents
On low pressure systems (with steam pressure 13 psig or less} where non-venting traps are used for condensate removal to a vacuum return, a l/2" thermostatic air trap should be located in an air line bypassing the con densate trap. The air line to the trap should be of 1" pipe and the trap located at least 12" above the coil return connection. On low pressure systems where non-venting traps are used for condensate removal to a gravity return, 3A" individual return line automatic air vents are recommended. These vents should be located at least 12" above the coil return connection and vent to the room. The use of thermostatic traps for air removal is permissible (but not recommended) with a gravity return, provided the return line is vented ade quately to the outside atmosphere.
Provide Vacuum Relief
A vacuum breaker must always be provided when automatic steam control is used. Under many conditions of operation with modulating control, or when steam is shut off by a two-position on-off control, a vacuum will occur in the coil unless proper relief is provided. The vacuum holds condensate in the coil tubes causing water hammer and, when sub-freezing air is being handled, allows the tubes to freeze. It is recommended that vacuum breakers also be used with manual steam control to avoid the possibility of condensate hold-up when the valve is 6hut off.
On gravity systems, install a l/2" check valve in a riser at the return connection from each coil. On vacuum systems, install a check valve in a bypass line around the trap to prevent the coil vacuum from exceeding that in the return.
Page 27-5
17744
Allow for Removal of Heating Element
Make steam and return connections to the coils through an elbow to a union as shown in the piping diagrams. This leaves the coil connection end free of piping allowing removal of the heating element when the unions' are diconnected. This procedure is not necessary on Type HA Coils since the heating element is removed from the end opposite the coil connections.
Avoid Lifting Condensate and Pressure Returns
Lifting of condensate above the coil return into an overhead main should always be avoided if po66ible and must never be done with automatic control. Temperature control by modulating or by on-and-off automatic steam valves must not be used with systems in which a pressure is maintained in the return lines.
Protect Automatic Control Valves, Coils and Traps by Strainers
Automatic valves operate much of the time at small openings and are easily plugged by scale and dirt. Each valve should be preceded by a line strainer to assure continuous operation. Each coil should be preceded by a line strainer to protect the supply tube orifices against plugging. If traps are not equipped with strainers, they should be preceded by line strainers to protect their small orifices against plugging.
Avoid Rigid Piping Connections
All steam and return piping must be provided with swing joints.at or near the heating coils so that piping and expansion strains are not communicated to the coils. All piping should be supported and anchored independently of the heaters.
Drip All Steam Lines
Steam line condensate should never be passed through heating coils. Steam mains should be dripped from the pressure side of the valve to the return line through a drip trap. Supply branches should be pitched back to the drip ped steam main. Failure to observe this precaution will result in damage to coils through hammer and corrosion.
Do Mot Bush Return Connections
Return piping must be made the full size of the coil return connection from the coil to the manifold or trap. Coil outlets must not be bushed. Piping from the coil return connection should have a vertical cooling leg at least 12M long and a dirt pocket at least 6" long -- all full size of the return connection.
) N.
Page 27-6
17745
Traps Should, be of Ample Size Blast heating coils should have traps of ample size to handle the high
condensation rate of these coils during the starting up period. In general, traps should he selected for 2-1/2 times the calculated coil load. Isolate Colls, Valves and Traps
Aside from any question of control, each coil in a multiple coil bank should be provided with a gate valve in its steam supply line and in the condensate line beyond the trap to permit servicing of coils and traps without shutting down the entire system. For the same reason, each automatic control valve should be preceded by a gate valve. Turn Steam On Before Starting Fans
Steam should be turned on to heat up coil6 before air flow is started, particularly when sub-freezing air is being handled. A 10-minute warm-up period before starting fans is desirable. This will help to reduce the flood of condensate which occurs when steam i6 suddenly admitted to a cold coil* The possibility of freezing and water hammer due to the coil filling with condensate will thus be reduced.
17746 Page 27-7
DOMESTIC HOT WATER
17747
CHAPTER 28
CHAPTER 28
DOMESTIC HOT WATER
The estimating of domestic hot water requirements for apartments, motels, hotels, clubs, office buildings, schools and the like is open to considerable question.
A number of different methods are employed. For example, the manu facturers of commercial hot water heaters usually use a figure of 15 gallons per hour per person. In a motel of 30 twin bed room units, allowing l-l/2 people per unit, the total hot water requirement at peak load would be esti mated at 30 x l-l/2 x 15 or 675 gallons per hour. This approach for large apartments, hotels, housing projects and hospitals results in astronomical amounts of hot water, which are not realistic.
There are reliable data available^ on hot water demand of fixtures, which may be used in estimating connected hot water loads. It is suggested that
these demands tabulated in Table 28-1 be used, particularly in cases of large requirements.
To illustrate its use assume a 60 suite garden apartment each with a single bath, with shower and kitchen with dishwashing. Using Table 28-1, the estimated connected load is
60 lavatories
X 2=
120gallons per hour
60 showers
X 30 1,800 gallons per hour
60 kitchen sinks X 10 600 gallons per hour
60 dish washers X 15 =
900gallons per hour
Total connected demand 3,^20 gallons per hour
Not all fixtures will be in use simultaneously. For apartments the use
factor is estimated at .3 making the actual hourly demand .3 x 3*^20 1,026 gal Ions per hour.
Warning
Obviously, 1,026 gallons per hour averages out to 17*1 gallons per minute. But, do not assume that a tankless heater good for 17*1 gallons per minute would be satisfactory. During the hour instantaneous demands for hot water might be at a rate of several hundred gallons per minute,. Such an amount would be inpractical to supply with a tankless heater unless there was un limited boiler capacity available.
The preferred method of handling large hot water demands is with a separate boiler (the IS method) or with tank-type heaters installed in the space heating boiler. In each case a storage tank is used.
It is also possible to use the tankless heaters supplied with the A-5 boiler and the two largest sizes of those furnished with the G-40 as tank type heaters. When this is done a pump must be used to circulate the water through the heater and the tank since the small size of tubing used in these heaters has too much friction to permit adquate water circulation by gravity. In
Page 28-1
17748
Table 28-1
Hot Water Demand per Fixtures for Various Types of Buildings
Gallon* of water por hour por fixture, calculated of o Anal temperature of 140 F
Apartmunt
Houao
Chib
Gym*
natium
Hospital
Hote/
llldvifftol Wont
Office
Building
Private Korideiico
School rjncA.
1. Basins, private lavatory.... 2. Basins, public lavatory....... 3. Bathtubs................................ 4. Dishwashers*......................... 5. Foot basins............................ 8. Kitchen sink......................... 7. Laundry, stationary tubs . .. 8. Pantry sink........................... 9. ShowerB.................................. 10. Slop Bink................................ 11. Hydro-therapeutic showers 12. Hubbard baths . ... 13. Leg baths................ . 14. Arm baths ......................... 15. Bits baths ............................ 16. Continuous-flow baths......... 17. Circular waBh sinks............. 18. Semi-circular wash sinks 19. Demand factor .................... 20. Storage capacity factorb...
2 4 20 15 3 10 20 5 30 20
0.30 1.25
2 6 20 50-150 3 20 28 10 150 20
0.30 0.90
22
2
2
86
8
12
30 20
20
50-150 50-200 20-100
12 3
3
12
20 30
20
28 28
10 10
225 75
75
225
20 30
20
400
600
100
35
30
165
20 20
30
10 10
15
0.40 0.25 0.25 | 0.40
1.00 0.60 0.80
1.00
2 2 22
6 16 8
20 30
15 20-100 20-100
3 3 12
20 10
20 20
20 28
10 5 10 10
30 30 225 225
20 15
20 20
20 10 0.30 2.00
0.30 0.70
30 15 0.40 1.00
0.40 1.00
* Diahwwber requirement* should be taken from Table 14 or from manufacturer*' data for the model to be u*ed, if tkua ia known.
.,
b Ratio of storage took capacity to probable maximum demand per hour. Storage capacity may be reduced where an unlimited aupply of ateam i* available from
a central street steam system or large Doiler plant.
Reprinted, by permission from ASHRAE Guide and Data Book - 1962
Page 28-2
17749
making such application the Hydronic Product Group should be consulted.
The tankless heater capacities,when used as tank-type heaters,are as follows:
Heater No. 530 232
445
Btu/hr. 160,000 249.000 299.000
There are tank-type heaters on the market, produced by heater manufacturers, that will fit American-Standard boilers.
IS Domestic Hot Water
The IS in the title stands for "indirect steam". In this kind of system a steam boiler is used to heat domestic hot water in much the same way steam is used with a convertor to supply forced hot water to a heating system.
The IS system has a number of advantages over the DW or direct water heating.
1. The hot water has no discoloration. In DW systems the water becomes slightly tinted from its contact with cast iron of the boiler.
2. Scale forming substances which would normally be deposited on the inside boiler surface with EW systems are now deposited on the outside of the steam coil in the external heater. Since these heaters are designed for coil accessibility or removal, they can be readily cleaned when liming becomes excessive.
3. The boiler is working on a closed system with the condensate being returned to it, thereby reducing internal liming to an inconsequential minimum.
G-2 boiler prices are quoted only for IS use. However, any steam boiler in the American-Standard line can be used in an IS system. Choice depends on the load required and the fuel desired.
Boiler requirements for an IS system are;
1. Standard steam equipment including steam gauge. 2. ASME safety valve.
3- Pressure limit control.
4. Gauge glass with trimmings.
5- Resetting low water cut-off.
In addition, the system should be supplied with a CA-666 immersion operating control, installed in the water storage tank at or near the cold water inlet.
Page 28-3
17750
Heat is transferred, to the water through either a coil in the storage tank or an external indirect heater. In both cases, the equipment i6 supplied by other manufacturers who should specify the sizing of the heat exchange equipment.
The principle of sizing the boiler in these installations is Bimple be cause the domestic hot water demand i6 the only load...and, in addition, the storage tank i6 located close by the boiler.
The boiler's ability to heat domestic hot water is based on its I*BR gross capacity or its A. G. A. output.
Computing the gallons of hot water any boiler can supply is a simple problem of multiplying the gross capacity of the boiler in MBH by a factor dependent on the temperature rise desired.
Factors are ....
for .... Various Wi Temperature
1.2 100F
1.3 90F 1.5 80F 1.7 70F 2.0 6of
The equation;
Demand (GPH) = MBH x Factor
Example;
How many gallons of water per hour, at a 100F temperature rise can be supplied by an American-Standard G-25 boiler, which has a gross capacity of 96,000 Btu/hr.
GPH * 96 x 1.2.... or 115.2 gallons per hour
Similarly ...
GPH (at 90F rise) GPH (at 80F rise) GPH (at 70F rise) GPH (at 60F rise) -
96 x 1.3 96 x 1.5 96 x 1.7 96 x 2.0
or 124.8 GPH or 144.0 GPH or 163.2 GPH or 192.0 GPH
For economy reasons, particularly with severe peak demands, it is usual to employ a storage tank in an IS system to permit the heating and storing of water during off-peak periods.
Page 28-4
17751
The size of the storage tank and boiler will, of course, depend on the length of peak demand.
The equation, with "IT" being number of hours of peak demand Is;
H x Demand (GFH) - N x Boiler Capacity (GIB) + .7 x Tank Volume (GFH)
OR: Tank Volume (Gals) - W (Demand - Boiler Capacity)
7
The following tables show various combination of boiler capacity and tank volume to meet various demands of both gallonage and temperature rise.
Table 28-2
Hot Water l.p.h.
100 150 200 250 300 350 Uoo U50 500 550 600 650 700 750 800 850 900 950 1000
1050 uoo 1150 1200 1250 130-3
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
_________________
100P T--paratgf M.H
G--2 Bollar-SlMa
O-iiO BoUer-Siaes
G-60 Boiler-Siees
23 21* 25 26 27 26 29 210 211 1*03 1*01* 1*05 1*06 1*07 1*08 1*09' 1*010 606 687 608 609
60
131 92 50 163 121 80 207 151 no
70
80 166 1*9
223 181 Da 100
223 120
253 213 171 130
295 192 89
281* 21*3 201 160 366 263 160
58
311* 273 231 105 303
335 2 32 129 1*06 303 200
98
371* 375 272 169 66 1*1*6 31*3 21*0 137
312 209 106
Tank vol(gals.) N(damand[gphj-boiler caj .CBh])l0.7 N Number of hours of peak demand
383 280 177 75 1*55 352 21*9 11*5 77
1*23 320 217 11*9 392 289 220
1*63 360 291 93 1*32 362 161* 1*31* 236
506 307 109 379 180 1*50 251 521 323 123 391* 191* 1*66 265
Page 26-5
17752
Assume gas as the fuel and a demand for 200 GFB. Opposite the 200 GFH demand, under G-2 boiler sizes there sure 3 possible combinations to meet these requirements.
1. G-24 boiler and 163 gallon tank (min)
2. G-25 boiler and 121 gallon tank (min)
3. G-26 boiler and 80 gallon tank (min)
Naturally, the proposal will suggest the most economical combination.
If the peak demand time were doubled to two hours, tank size would have to be doubled. If peak demand went to three hours tank 6ize would have to be tripled. Tank sizes cannot be increased indefinitely. At some point, both economy and necessity will dictate the next larger size boiler.
Table 28-3
Hot Water g.p.h.
100 150 200 250 300 350 I4OO 1*50 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250' 1300
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
80F Ttt^erftture Rlas
G-2 Batlar-SlMe
G-4i0 Bailer-Sitas
G-40 Boiler-Sitea
23 21* 25 26 27 28 29 210 211 1(03 1*01* 1*05 1*06 1*07 uoe 1*09 1*010 606 607 608 609 610
u 103 62 181* 133 82 30 256 201* 153 101
50
30 100
276 221* 173 121 70 296 21*1* 193 lla 90 316 261* 213 161 no
172 1*3 21*3 111* 59 311* 136
57
o
2
H
r~> CM
-3
CO CM
$
r*-\
386 257 129
356 301* 253 201
329 200 71
375 321* 273
U00 272 11*3
396 31*1*
31*3 211* 86
1*15 1*15 286 157
Tank vol.{gala.)- N(demandgpfcQ-boiler cap.g >hj)l 0.7
357 229 100
N = Number of hours of peak demand
U29 300 172
372 21*3 111* 1*W* 311* 186 57
386 257 129
1*57 329 200 Ill* 1*00 272 186 1*71 31*3 257 las 32?
80
U96 1*00 152
1*71 223
29k
366 U7
17753
Page 28-6
Here a demand, for 700 gallons an hour with an 80F temperature rise dictates either;
1. G-406 boiler with 357 gallon tank
2. G-407 boiler with 229 gallon tank
3> G-408 boiler with 100 gallon tank
Again, one will cost less...and, again tank sizes will have to be doubled, if peak demand stretches out to two hours.
The following table covers the same three boilers with a 60F temperature rise, and still smaller tank requirements.
Table 28-4
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
Hot Water Denarri g.p.t.
100 150 200 250 300 350
uoo
U50 500 550 600 650 700 750 800 650 900 950 1000
60P Teupermture Rise
G-2 ^oiler-Sises
0*4*0 Boiler-Sires
G-60 Boiler-Sirea
23 21 25 26 27 26 29 210 211 103 lol 105 1*06 107 loe U09 Ho 606
77
119 80 220 152
83
223 155 86
86
295 226 157 67 366 297 229 160 91
369 300 232 163
91
157 229 57 300 129
110 372 303 231i 166 98
372 200
512 113 375 306 237 169 100 li*3 272 100
116 377 309 210 172 515 3U3 171
119 380 312 213
115 213 72
152 383 315
586 311 1U3
155 386
386 211
157 1x57 286 115
529 357 186
129 257 86
500 329 157
1*00 229 57
1050
noo
1150 12 0C 1250 1300
_ Tank vol.{gals.)-N(demandphJ-boiler cap.g h])r 0.7
N Number of hours of peak demand
U72 300 129511 372 200
113 272 100 515 313 171 57
115 213 129 586 331 200
Page 28-7
17754
The following three tables provide the same kind of information on Arcoliner, A-5 and A-7 boilers.
Table 28-5
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
100F Temperature Rise
Bot Water DeaaaA
Aroolinar-Sitea
A-5 Boller-Slees
A-7 Boiler-Sitea
153 154 iss 156 504 505 506 507 50a 509 510 511 705 706
100
iso 49
200 120 60
250 191 131 76 300 263 203 147 106
frH
H
CM
r-- (M
350 53 Uoo 406 346 290 24? 124
450 417 362 320 196 so
500 433 392 268 1Z1
550 463 339 193 56 600 410 264 127
650 482 336 199 57
700 407 270 129
750 479 342 200 63
800 413 272 134
850 485 343 206 69
900
105 278 HiO
Tank vol. (gals.)-N(demandQgph]-boiler cap.fgphjji 0.7
950
486 349 211 74
N Number of hours of peak demand
1000
U20 283 1U6
1050 noo 1150 1200 1250 1300
492 354 217 77 426 269 149 67 497 360 220 158 432 292 230 503 363 302 435 373 123
Page 28-8
17755
Table 28-6
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
Bot Water Deaead C.p.b.
100 ISO 200 250 300 3S0 boo Ii50 500 550 600 650 700 750 800 850 900 950 1000
1050 1100 1150 1200 1250 1300
Arcolinsr-Slses
A Boiler -Si*ea
153 151* 155 156 501* 505 506 507 508 569 510 511
80
166 51
?23 123 31
295 191* 103 366 266 171* 106
1*37 337 21*6 177
1*09 318 21*9
1*80 389 320 111 1*60 392 183 463 255
83
326 155 397 226
1*69 297 69
369 11*0 1*1*0 211
512 283 35U 1*9 1*26 120
1*97 191
263
331* 106
1*06 177
Teak Tol.(gals*)M(leaBidtiph)-baUer cep.gphj) 40.7 N - Nunfcer of hours of peek rle--rri
Page 28-t9 17756
Table 28-7
MINIMUM STORAGE TANK CAPACITIES 1 HOUR PEAK DEMAND
80F Ta^aratur* Rlae
Aroollaar Slsea lot Veter
A-5 BoHer Sites
.p.h.
153 154 155 1*> 504 505 5bi 507 508 509 510 511
MO
ISO
200 79
2$0 150 7U
300 222 11*6 77
350 29U 217 149 97
U00 365 289 220 169
450 436 360 292 2i*0 83
Soo 507 1*32 363 312 155 550 503 1*35 383 226 1*4
600 506 1*55 297 116
650 526 369 187
TOO 1*40 259 87
750 512 330 160
000 401 232 54
BSo 473 303 126
900 950 1000
S45 375 197 1*46 269 97 516 340 169
Tank Tca.(galfl.)-N(domand[gph]-bailer cep.fgpKJJ-j-0.7 N Number of hours of peak demand
1050
412 240 69
1100
483 312 140
u5o
555 383 211
1200
455 283 111
1250
S26 354 183
1300
1*26 254 79
Page 28-10 177=17
CHAPTER 29
GREENHOUSE HEATING
17758
CHAFTER29
GREENHOUSE HEATING
Greenhouse heating is, of course, different from space heating for human comfort.
Temperature is frequently maintained at less than 70F, which increases the emission rate of radiation.
Studies of greenhouse heat I06S indicate that the glass area is a good base for calculating the load. The necessary allowances for wadi loss and small amounts of infiltration have been made in the tables that make up the body of this chapter.
These Babies, 29-1 through 29-7, have been prepared for 1,000 square feet of glass...they cover an outdoor temperature range of 20F down to -30F and an indoor range from 40 to 70F. They are based on data compiled by the United States Department of Agriculture and published by the"Heating and Ventilating Magazine"
Knowing the number of thousands of square feet of glass in a greenhouse, the following information can be obtained;
1. The total Btu per hour heat loss for sizing the boiler or boilers.
2. The square feet of radiation required for a. Steam at 220F. b. Gravity circulated hot water at l60F. c. Forced circulated hot water at 210F.
3- Linear feet of pipe radiation required for a. Steam at 220F b. Gravity circulated hot water at l60F c. Forced circulated hot water at 210F
As the tables themselves indicate, only two additional pieces of in formation are necessary;
1. The indoor design temperature
2. The outdoor design temperature
As a general rule the greenhouse owner will know what maximum inside temperature he requires for his crops. If there is any question Table 29-9 provides a list of vegetable and flower crops and their customary tempera ture requirements.
The outside temperature is the outdoor design temperature for heating that is in common use in the area.
Let's see how they work.
Page 29-1
17759
The problem: A greenhouse is being built for general purpose use. Its glass area is 9,500 square feet...the outdoor design temperature is -10F, the indoor design temperature 55F.
The builder plans a forced hot water system and you have sold him on using cast iron radiation.
Inside design temperature of 55F is covered in Table 29-4. Then under the -10F outside temperature heading, you will find on the last line "Forced hot water 210F" that 326 square feet of EDR is needed for each 1,000 square feet of glass area. 9,500 square feet of glass, then, will require 9-5 x 326 or 3,097 square feet of EDR. On the top line, you will note the heat loss of 85,300 Btu/hr. per 1,000 square feet of glass. This greenhouse will need a boiler with a capacity of 9*5 x 85,300 or 810,350 Btu/hr. of net installed radiation.
To size supply and return mains for steam systems, use the standard pipe sizing tables given in Chapter 15. The figures should be used in conjunction with the Btu/hr. load equated to EDR by dividing by 24-0.
To size supply and return mains for forced hot water heating, use the standard milinch method discussed in Chapter 20.
For supply and return main sizing on hot water gravity systems, use Table 29-8 on Page 29-10.
Page 29-2
A7760
Inside Temperature 40F
Table 29-1
REQUIRQiEHTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10 0 -10 -20 -30
Heat Loss Btu/hr.
28,600 41,000 53,800 66,800 79,200 92,200
Linear Feet of 1-1/4" Pipe Steam
Linear Feet of 2" Pipe Gravity Hot Water
Linear Feet of 3-1/2" Pipe Gravity Hot Water
Linear Feet of 2" Pipe Forced Hot Water
Cast Iron Radiation Square Feet
Steam
Hot Water Gravity
Hot Water Forced
132 189 116 120
88 154
97
190 271 167 173
126 220 139
250 358 220 226
165 289 162
305 443 272 280
204 360 225
366 425 525 610 323 374 333 388
242 283 426 495 268 312
Page 29-3
17761
Inside Temperature kf?
Table 29-2
REQUIREMENTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10 0 -10 -20 -30
Heat Loss Btu/hr.
34,800 47,^00 60,100 72,600 85,300 98,000
Linear Feet of 1$" Pipe Steam - 220F
168 230 292 352 414 475
Linear Feet of 2" Pipe Gravity Hot Water - l6o
242 330 419 505 591 680
Linear Feet of 3^" Pipe Gravity Hot Water - l60F
150 205 258 313 366 422
Linear Feet of 2" Pipe Forced Hot Water - 210F
Cast Iron Radiation Square Feet
Steam - 220F
Gravity Hot Water - l60F
Forced Hot Water - 210F
153
111 198 122
209
152 270 166
264
192 342 211
320
232 413 254
374
272 485 299
429
313 555 343
)
i
Page 29-4
17762
Inside Temperature 50F
Table 29-3
REQUIREMENTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
Heat Loss Btu/hr.
20 10 0 -10 -20 -30 1H, 200 53,800 66,450 79,000 91,700 104,500
Linear Feet of l" Pipe Steam - 220F
207 270 333 397 46o 524
Linear Feet of 2" Pipe Gravity Hot Water - l60F
304 397 490 582 676 770
Linear Feet of 3i" Pipe Gravity Hot Water - l60F
188 245 302 360 419 475
Linear Feet of 2" Pipe Forced. Hot Water - 210F
189 247 305 362 420 478
Cast Iron Radiation Square Feet
Steam - 220F 140 182 224 267 310 353
Gravity Hot Water - l60F 248 324 398 474 550 626
Forced Hot Water - 210F 150 196 242 286 234 380
Page 29-5 17763
Inside Temperature 55F
Table 29-4
REQUIREMENTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10 0 -10 -20 130
Heat Loss Btu/hr.
47,500 60,500 72,800 85,300 98,500 111,000
Linear Feet of l" Pipe Steam - 220F
245 315 377 440 508 571
Linear Feet of 2" Pipe Gravity Hot Water - l60F
368 472 568 663 763 862
Linear Feet of 3^" Pipe Gravity Hot Water - l60F
231 296 356 415 48l 541
Linear Feet of 2" Pipe Forced Hot Water - 210F
228 292 350 409 472 532
Cast Iron Radiation Square Feet
Steam - 220F 166 212 255 299 345 308
Gravity Hot Water - l60F 300 382 46o 540 623 702
Forced Hot Water - 210F 182 221 278 326 376 424
Page 29-6 17764
Inside Temperature
60F
Table 29-5
RBQUIREMEHTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10
0 -10 -20
-30
Heat Loss Btu/hr.
53,700 66,600 79,100 91,700 104,500 117,300
Linear Feet of l" Pipe Steam - 220F
289 358 426 ^93 562 629
Linear Feet
of 2" Pipe Gravity Hot Water - l60F
446 549 654 768 862 971
Linear Feet of 3i" Pipe Gravity Hot Water - l60F
278 342 408 472 541 606
Linear Feet of 2" Pipe Forced Hot Water - 210F
270 336 397 46l 524 588
Cast Iron Radiation Square Feet
Steam - 220F 196 243 289 334 381 427
Gravity Hot Water - l60F 360 447 531 615 700 788
Forced Hot Water - 210F 215 267 315 367 4l8 469
Page 29-7 17765
Inside Temperature 65P
Table 29-6
REQUIREMENTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10
0 -10 -20
i30
Heat Loss Btu/hr.
59,700 72,600 86,400 98,300 111,000 123,000
Linear Feet of l" Pipe Steam - 220F
Linear Feet of 2" Pipe Gravity Hot Water - l60F
Linear Feet of 3i" Pipe Gravity Hot Water - 160 F
Linear Feet of 2" Pipe Forced Hot Water - 210F
Cast Iron Radiation Square Feet
Steam - 220F
Gravity Hot Water - l60F
Forced Hot Water - 210F
336
529
333
313
228 427 250
403
641
403
379
277 519 304
479
752
476
446
326 610 357
550
870
549
513
375 702 4ll
621 690
980 1,087
617 685
578 645
424 470 792 877 464 515
Page 29-8
17766
Inside Temperature 70F
Table 29-7
REQUIREMENTS FOR EACH 1,000 SQUARE FEET OF GLASS
Outside Temperature
20 10
0 -10 -20 -30
Heat Loss Btu/hr.
66,250 79,200 91,700 104,800 117,500 129,500
Linear Feet of l" Pipe Steam - 220F
39b 470 546 621 700 770
Linear Feet of 2" Pipe Gravity Hot Water - l60F
613 735 855 971 1,099 1,205
Linear Feet of 3^" Pipe Gravity Hot Water - l60F
Linear Feet of 2" Pipe Forced Hot Water - 210F
391 467 543 617 694 763 361 431 503 571 645 709
Cast Iron Radiation Square Feet
Steam - 220F 265 317 367 419 470 518
Gravity Hot Water - l60F 505 605 700 798 896 988
Forced Hot Water - 210F 289 346 400 457 513 565
Page 29-9 17767
\
Table 29-6
Size of Mains for Gravity Hot Water Pipe Coils (Based on l60F water, and a total length of supply
and return mains of not over 200 feet)
Size of Supply and Return, In
1-1/4 1-1/2 2 2-1/2 3 3-1/2 4 5 6
Diameter of Pipe in Coil, Inches
3-1/2
2
Linear Feet of Pipe in Coil
50 80
8o 140
190 320
O
CO
650
660 1,100
1,000
1,700
1,500
2,600
3,000
5,000
5,200
8,700
rage 29-10
17768
Table 29-9
Customary Temperatures for Greenhouses
Type of Plant , Carnation Conservatory (general collection,
winter, garden, etc.) Cool Cucumber Fern Forcing General Purpose Lettuce Orchid, warm Orchid, cool Palm, warm Palm, cool Propagating Rose Sweet Pea Tomato Tropical Violet
On0 1
vOnN
Temperature Range, Degrees F 45 - 55
60 - 65 45 - 50 65 - 70
60 - 65 55 - 60 4o - 45 65 - 70 50 - 55 60 - 65 50 - 55 55 - 60 55 - 60 45 - 50 65 - 70 65 - 70 4o - 45
Page P9-U
17769
CHAPTER 30
HEATING SWIMMING POOLS
17770
CHAPTER 30
HEATING SWIMMING POOLS
There are two common methode for establishing the heat loss of the water in a swimming pool. They are based on;
1. The volume of water
2. The surface area of the water
The volume method considers only the heat necessary to raise the water volume a certain number of degrees fahrenheit in an hour. Arbitrarily, the industry has a set standard for sizing boilers to heat swimming pools on the basis of raising the water temperature by 20 in a kO hour period in the South and with indoor pools...in a 30 hour period across the middle part of the country and in 20 hours in the North.
These factors can be converted to degrees of water temperature rise per hour*
1. l/2F per hour in the South and in indoor pools
2. 3/4f per hour across the middle part of the country o
3. IF per hour in the northern part of the country
These are arbitrary and there may be minor differences in any one locality, depending on altitude and humidity.
However, since the quantity of heat estimated at these levels is greater than the heat loss, once the pool is up to temperature this procedure ha6 been found to meet the requirements.
The equation is; Btu/hr Input - L x W x D x __--^2 ----------- x T Boiler Efficiency
Where L " Length of the pool -- feet
W " Width -- feet
D ' Average Depth -- feet
62 * Weight in pounds of 1 cu. ft. of water
T " Degrees of Temperature rise per hour
Actually, of course, any similar equation involving any substance other than water would also include the factor of the specific heat of the substance. Since the specific heat of water is "1", and anything multiplied by "1" is unchanged, it is not necessary to use the factor in this kind of equation when water is the substance.
Page 30-1
17771
Example: In Connecticut, what size gas-fired, boiler, operating at 80$ efficiency, is
needed to heat a pool 30 feet long, l6 feet wide, with an average depth of 5 feet?
Our equation now is;
Btu/hr. Input 30 x 16 x 5 x
x 1 " 186,000
.8
A boiler with at least a 186,000 Btu/hr. input is required.
If, however, the boiler were rated at 70$ efficiency, the equation for the same pool would be;
Btu/hr. Input - 30 x 15 x 5 x
xl- 212,570
7
If the pool in question were the same dimensions but in a gymnasium in a school in Connecticut or outdoors in Georgia, the equation for the same boiler, at 70$ efficiency would be;
Btu/hr. Input
30 x 16 x 5 x - x 1/2 7
106,290
The area method of "sizing the boiler" is based entirely on the cooling action of both the wind and surface evaporation. Depth of the pool, there fore, is not a factor.
Experience indicates that the pool will lose 12 Btu per hour per square foot of surface area for every degree of temperature difference between the water and the surrounding air temperature.
The area method equation is;
Btu/hr. Input *= L x W x if:_____________________ x (T - Ta) Boiler Efficiency
Where L - Length W Width
T " Temperature of Water in F Ta Average air temperature in F
Example:
Assume the same pool, outdoors in Connecticut. The owner wants to use the pool between September 15th and October 15th. During this period the average air temperature get to 55F. He wants to keep the pool water at 60F. Again, a gas boiler with 80$ efficiency has been decided on.
Page 30-2
17772
The equation;
or; 30 x 16 x 12 x 25 _ 180,000
With a boiler rated at 70$ efficiency we would have;
30 x 16 x 12 x 25 . 205,700 7
Again, let'6 move the same pool with a gas boiler operating at 70$ efficiency, indoors. Assume the gym is kept in use from 8;00 a.m. to 10;00 p.m. with a space temperature of 70. After 10;00 p.m., it is allowed, on the thermostat's night setting, to cool to 60 , with the morning cycle set for 7:00 a.m.
Average temperature under these conditions would be 66. Then;
Btu/hr. Input = 30 x 16 x ^ x (80-66) I
30 x 16 x 12 x Ik 7
108,350
Thus, the two methods of calculating the boiler capacity in Btu/hr. for three different situations involving the same pool size are;
Outdoors, Connecticut, 80$ efficiency
Volume 186,000
Area 180,000
212,570
205,700
Indoors, " 70$
106,290
108,350
Page 30-3 17773
CHAPTER 31
MAINTENANCE
17774
CHATTER 31
MAINTENANCE
Regular, methodical maintenance of any heating system pays off in longer life and more economical operation.
Burners -- oil, gas and stokers -- should be checked, cleaned and ad justed according to manufacturer's recommendation6 at least once a year.
Controls, too, need an annual inspection. Changes in calibration can be detected and corrected. All electrical contacts should be checked and cleaned. Minor pitting can be cured by smoothing...severe pitting only by replacement.
New boilers, either hot water or steam whether in new systems or re placements in old systems, require daily inspection for the first several weeks of operation.
Water should be drained from the boiler at each inspection. If the water is muddy, draining should continue until it runs clear.
Draihing should be accomplished with the water hot and burner off. With dry base boilers more than one drain may be desirable.
The most common problem with new steam boilers is "foaming".
In new steam systems, the condition is aggravated by oil in the piping, left over from the pipe threading operation, which floats back to the boiler with the condensate.
Almost every time a new steam boiler is put into operation oil and sand will be found floating on the water in the boiler, particularly when the boiler is part of an entirely new system.
The strength of the film of oil... surface tension...is much greater than that of water. Instead of the bubble of steam breaking easily through the surface of clear water, it now blows a 6oap-like bubble.
These bubbles form a froth which blankets the entire surface of the water, which holds back the pressure being built up in the hot water until it becomes strong enough to lift large portions of the blanket and blow it out of the boiler. Often some of the boiler water is lifted with the foam and carried along into the system. This action i6 called "priming" and results in a rapid lowering of the water level and burner shut-down by the low-water cut-off.
With oil burning boilers, too frequent action by the low-water cut-off has a secondary effect on the stack switch.
Rapid cycling cauaes the stack switch to go to safety position, pre venting the burner from re-starting. An inexperienced service man might replace the stack switch which is operating perfectly and miss the real reason for its action.
Page 31-1
17775
In addition to frequent action by the low-water cut-off, there are a number of other "indicators" of foaming.-
1. Because of the blanket of foam the boiler does not generate enough steam to fill the radiation.
2. Because of the periodic priming action, water in the gage glass, following the water in the boiler, surges up and down, violently, in wide swings.
3. When the safety valve is opened both water and steam will blow out instead of. steam alone. .
4. A small amount of boiler water drained into a sauce pan and put on a hot plate will -foam up and boil over
To eliminate foaming, it is common practice with large 6team boilers to drain condensate into a sewer for the first couple of weeks of operation.
Periodic "saucepan" tests of the condensate will tell when it is clear of oil and sand and 6afe to return to the boiler.
The smaller water content of ga6 boilers, of course, aggravates the foaming problem.
Once a boiler foams and primes, it should be cleaned by the blow-off
method.
..
The chemical treatment is easy but never sure.
The blow-off method is sure but it may have to be. done several times... weekly for about three weeks.
American-Standard oil and coal-fired steam boilers are provided with . blow-off tappings;
To give a 0-60 boiler a surface blow-off the 6afety-valve tapping may be used. On the G-40 use tapping B. See Technical Catalog Bulletin, for G-40.
Remove the safety valve 1 or plug as the case may be and..install a
nipple, a gate valve and some drain piping.
*
The water level is raised to the blow off tapping and the boiler fired until steam pressure is developed. The gate valve is then opened end the outrush of steam sweeps the foam off the top of the water and into a drain.
After the pressure has dropped, water is fed' into the boiler slowly
and the burner kept operating. Amy dirt and oil. is floated out the blow-
off. This process may have to continue for a considerable period depending
on the water, conditions.
The blow-off is now closed and steam pressure allowed to build up to 10 psig. The gate valve is opened once more to blow-off any additional foam that may have formed. -
Page 31-2
17776
The burners are shut off and the boiler drained. After refilling the boiler, start the burner and raise the 6team pressure to 10 psig. Open boiler drain to flush any dirty water out of the boiler water legs. In dry base boilers a drain valve should be installed in each leg or on the return manifold. The water must not be allowed to rise above the blow-off valve as it would trap the dirt and grease above the valve allowing clean water to drain off. A boiler cannot be cleaned of grease and oil if it is not hot. Merely draining the boiler to clean it will result in surface grease and dirt clinging to its sides, and rising to the surface when the boiler is re filled. In hot water systems, excess dirt and oil sometimes cause the liberation of substantial amounts of marsh gas which slows water circulation. This situation can usually be handled by a chemical cleaner in accordance with in structions of the cleaner manufacturer. Boilers not in Operation In winter, the boiler, returns and system -- if hot water -- should be completely drained. Flues should be cleaned and all access.doors left open. In summer, the boiler flues, especially on coal and oil fired boilers, must be completely cleaned. Gas fired boiler flues stay clean when burners are in proper adjustment and ample air is available for combustion. Leave all access doors open. Leave water in a hot water boiler and system during summer months. Fill the steam boiler completely with water during the summer. This stops internal corrosion at the water line during shut down. Be sure to drain excess water out before firing the boiler in the fall.
Page 31-3
17777
CHAPTER 32
COMPETITIVE COMPARISONS
17778
CHAPTER 32 COMPETITIVE COMPARISONS
Competitive comparisons, while not often made specific, are one of the salesman's strongest assets...if he knows them.
This chapter provides these comparisons...as of the date noted on each chart.
Products will change and as they are changed, it is important that you revise these charts so that you are always ready to:
1. Stress your product's advantages. 2. Be aware of competitive claims and have the best answers to them. Since convenience and cost of assembly are important in any sale, we note several basic assembly factors. 1. Wet base boilers are easier to assemble than dry base boilers
because each section has its own base (American-Standard A-5) N. B. However certain American-Standard dry base boilers (A-7 and G-60) are furnished with bases to facilitate assembly. 2. American-Standard boiler sections pull tightly together, elimi nating the need of asbestos wickir.g between sections. 3. Smaller sections are more easily handled and assembled than large double sections.
Page 32-1
17779
Table 32-1
COMPARATIVE DATA ON 0-1*0 GAS-FIRED BOILERS
Competitive Features
AR & SS National Peerless Burnham Weil*^cLain Bryant Bryant H. B. Smith 0-1*0 U.S. 16C Series 50 Holiday 70 Type H 222 (W) 223 (S) Century 11
Common section
for or less
tankless
Yes
No
No No
No
No No
No
Common tank
less heater
with steam &
vater.
Yes Yes
Available in sections factory
assembled.
Yes 'up to G-l*06)
Only
3 & 1* sect.
No No
Yes Yes No No
Available for
dual fuel.
Yes Yes
No
No
Non-protrud ing draft hood Yes
No
No No
No No
No No
Yes
Yes Yes
No
Yes Yes
No
No No No
Optional Jacket ex tension cover ing left hand end section.
Yes
Yes
No
No
No
No Yes Yes
Available for
50 lbs. PSI
Yes No
Yes No
Yes
No No
No
Integral
air eliminator Yes
No
No
No
No
No No No
Deluxe jacket standard
Yes
No
Yes Yes
Yes
No No No
No separate base required
Yes
No
No
Internal vater
heater-capacit ies bot i steam & water | 3-9gpin
1
both 3|-6gpm
--
No Yes No
3-3A-l5gpir for water. 3-7-l/2gpm for steam.
3-10 1/2 gpm
---
No Yes
both -- 2.2 - SID gpm
rage 32-2
17780
Table 32-3 A-5 Feature Comparisons
Features
AR & SS
Burnham
National
"A-g" "PaceKing" "2gB"
H. B. Smith "27-37 Series'1
Weil-McLain 200 &2gOA-72 & A-82
Water Line 1*6 lA"
Wet Base construction Yes
52 1/2"
No
1*5" 1*5 lA" to 51" 1*7 3/0" to 57" 1*7 1/1*" to 55" Yes No No No
Section Assembly
Jacket Extension
A-5 util izes one set of tie rods & bot tom slip nipples
Available
Same
Not avail.
Same Avail.
Same
Not Avail.
Require short individual tie rods
Not Avail.
Requires short individual tie rods, asbestos rope needed to prevent air leakage.
Jacket extension avail on A-72 only.
Boiler-
Burner Unit Yes
No No No
No
Yes
Common in ternal tank less heater Yes
with mani fold arrange ment
No No No
Provisions for singl or double domestic No water heaters - A-62 only.
Water work ing pressure 50 lbs., re g. 30 lbs. 30 lbs. 30 lbs.
40 lbs.
30 lbs.
Number 4 Tapping sizes
a) supply 2-h" b) return h-2 1/2"
h-h" 2-h"
"27" "37"
3-3"
2-3" 2-3"
2-1*" h-h"
2-3" 2-3"
M72M
2-3" 2-3"
"82"
2-5" 2-h"
Internal Water Heater 1*-I6gpm Capacities (both)
water l4-l5gpm steam
3-9gpm
27** 37"
3i-6gFm
(both'
3-7gpm (both)
"200" water
l*-8gpm steam !*-6gpm
"250" water
l*-12gpm steam i*-6gpm
i72
l*i-6gpm (both)
n32"
7-9gpm (dual 16-1?
Page 32-h 17781
Features
Deluxe Jacket Standard
AR & SS Q-60
Tes
Table 22-2 G-60 Feature Comparison
National-U.8. "66 Series"
Peerless "150 Series"
Weil-McLain Type f
Tee No
Yes
Bryant Model 630
No
Water Work ing Freesure
501be. reg. 301bs. reg.
301bs. reg.
Bolbs. opt. 501bs. opt. N.C, 801bs. opt.
aided charge
Added charge
301bs. reg.
301bs. reg.
75lba. opt. N.C. no options
Height
66 1/8-
69 l/U"
55 1/2"
65 3A"
67 1/2"
Water Line
UU"
U5"
Ul 1/2"
U5 3A"
UU"
Boiler Base Cast Iron
Steel
Cast Iron
Steel framed
Steel
Section Availability
6 to Ul
U to 23
5 to 37
5 to 37
10 to 36
Flue Connection
Assembly Boiler
No. & sice of tappings
a) flew b) return
12" - 30-
all Hi" except 10" - 30" Model 5(12")
G-60 utilise! one set of ti 9 Jec^?PconB. rods 4 top 4 bottom nipple 8 on both ends of section
2-nipple sect, cons.
5-6" 5-6"
2-6" 2-6"
2-6" 2-6"
Available for
Dual Fuel
Tes
Tea
Vo
10",12",lU" only all A" excluding Model 10 (12")
requires short individual tie rods, 2 nipple sect. cons.
2-nipple sect. cons.
5-6" 2-It"--3-3"
2-6" 2-6"
Tes No
Page 32-3
17782
Table 32-1* A-7 Feature Comparison
Feature
AR A SS "A-7"
Natlonal-O.S, "47 Series"
Weil-McLain "HO-40"
Domestic Water Heater Arrange ment.
Furnished with ex ternal heater tap
ping.
May be equipped with an integral type tankless heater or a storage tank heater.
Not available
H. B. Smith 340 and 440
Available with mani fold heater on special order.
Water Working Pressure.
50 lbe. regularno optiona.
30 lba. regular.
40 lbs, regular 30 lbe.regular- 80 lbe. option 50 lbe.option N.C. Added Charge.
Jacket Availa bility.
Available with atardy 20-gauge eteel jacket.
Available with jacket.
Assembly Boiler.
A-7 utilises one eet of tie roda A top A bottom alip nlpplea.
Same as "A-5".
Available with jacket.
No jacket available.
Requires short
individual tie rods, multiplicity of parte in ex cess of slip nipples.
Requires special
tools A special uppwr and lower manifold connections for all sections.
Dry of Wet Top Nipple.
Height
Top nipple part
for ateam partial
ly aufamerged in
water Boiler rear
aection tapped for Wet top nipple -
external water
moderate tapping
heater, eliminating and manifolding
header connections of sections.
from eectiona for
external heater.
3" tappings furnish
ed regularly for
this purpose.
70 7/8"
69 3/8"
Dry top nipple requiring ex pensive heater manifold A spec
ial tappings.
Dry top nipple re quired special mani fold A heaters.
79 1A"
78" and 76"
Width
49 3A"
L9 1/2"
50" 51" and 64"
Length
U1 1/2" - 9b"
42 1/L" - 105 1/h" 42 3/4" - 114 3/4" 49" - -- 85"
Page 32-5
17783
Table 32-^ (Cont'd)
Features Water Lina.
Flue Connection.
Steel Pedestal Base Option.
AR L SS "A-7"
59 1/2"
A-7 Feature Comparison
Na tional-U.S. U7 Series"
59 1/2"
WeiJ-McLain "HO-^O"
67"
16" 16*
18"
Yes Yes
Yes
Boiler-Burner Unit
Yes
Yes
Yes
Tapping Sizes a) Flow
b) Return.
5-U" 2-6"
2-6" U-L"
ii-5" 2-5"
H. B. Smith 310 and UUO 56" to 61 1/2"
18" It 20"
Yes
Yea
3hO"
tzt
2-h"
"U1*0"
TV 2-5"
32-0
17784
GETTING THE ORDER
CHAPTER 33
GETTING THE ORDER
Which, of course, is the sole reason for preparing, writing, printing... AND READING...this book.
Product knowledge is a salesman's byword...the basis for his most potent selling arguments.
The more technical, the more flexible, the more varied, the more it resembles a complex system than a single component, the more important... and potent...knowledge of the product becomes.
This book will not give you all the answers. No single book can. Dozens of sources were used to gather this material.
It was designed to give you a basic understanding of the problems...a method for solving them...and an appreciation of the extent of product knowledge necessary.
The final step in any large heating system sale will often be the formal submission of a proposal with specifications.
This is, of course, a very important step in getting the order and this chapter contains some sample proposals to act as a guide.
Even more important are the inspections, conferences and conversations that precede proposal preparation, and in many cases...particularly in the replacement market...are the only steps to the sale.
Here it is that product and system knowledge pays off. Do you understand the problems? Can you help solve them? Can you suggest better values... either by improving the quality of the system or by finding a lower cost way of accomplishing part or all of the job?
The more money a man spends for a product...the more he wants to be sure that it, the company behind it, and the salesman in front of it are right.
And a large heating system represents a lot of money. Product and installation costs are high, but they're only a fraction of the money he'll be spending on it for the next 20 or 30 years -- or longer.
And so, differences in price in competitive proposals -- occasionally even reasonably large differences -- are sometimes less important than the quality of the salesman's product knowledge.
The important thing he needs is reassurance that your system, your product, will do the job, without overdoing it.
An undersized system will create serious trouble for him -- and you -and American-Standard.
Page 33-1
17786
An oversized system will take money out of his pocket, and in the long run, out of yours -- and American--Standard
In the early stages, off-the-cuff estimates on costs, Btu/hr. can cover a reasonably wide range.
Sizing a pipe, a pump, a toiler or an expansion tank cannot cover any range at all.
Be precise. Make your answers to his questions precise. .And make them only when you are absolutely, one hundred percent guaranteed sure. If you're almost absolutely, ninety-nine and forty-four one-hundredths percent, warranteed sure...don't answer. Tell him you don't know the answer but that you'll get it for him, fast. Then get it for him...fast I When you've got all the facts and figures, use the following samples as a guide and make up your proposal.
Page 33-2
17787
Sample Specification for Gas Fired Boilers
Contractor shall Install where indicated on plan*gas fired boiler(6) having a net lBR rating offor automatic operation on gas. Boiler(s) shall be constructed in accordance with ASMB Code for Low Pressure Heating Boilers, and bear it6 symbol. Section IV. Boiler(s) shall be A. G. A. approved for a maximum input ofBTU per hour. Boiler(s) shall be constructed of cast iron sections with Vertical flues with one at mospheric drill port or removable ribbon burner per flue way.
Manufacturer shall supply each boiler with main automatic gas valve, safety pilot with thermocouple as required by A. G. A., Gas pressure regulator (except for LP), high limit control, water or steam boiler trim as required by ASMS, Integral canopy and drafthood. (For G-2 and G-4-0 boilers an air eliminator as an integral part of the boiler and tankless coil of Gffl capacity)
Additional equipment required as follows; (Select one of the following specific equipment desired)
Manufacturer will furnish, in addition to the above, basic additional controls necessary to meet F. M. & F. I. A. requirements including electronic controls to provide electronic supervision and all primary gas pilots and electric ignition on all pilots and 100 per cent safety shutoff. Boiler(s) 6hall, after equipment i6 properly installed by contractor, be fully auto matic in operation with intermittent pilot ignition on all pilots.
or
Manufacturer will furnish boiler, in addition to the above electronic controls, to provide the following: (select one of the following)
1. Manual ignition non 100 per cent shutoff continuous pilot 2. Manual ignition 100 per cent shutoff continuous pilot 3. 100 per cent shutoff with electric ignition on primary
boiler pilot providing equipment component check of each boiler cycle.
Manufacturer will furnish factory wired and assembled electronic control panel suitable for wall hanging with main power on and off switch, pilot and gas valve switch, indicator lights for power,on, pilot off, gas valve on.
Boiler shall be as manufactured by American-Badiator & Standard Sanitary Corporation, New York, New York, Model No.or approved equal.
Page 33-3
17788
Sample Specification for Oil Fired. Boilers Contractor shall install vhere indicated on plansoil fired steam
or water boller(s) having a net I*B*R rating ofat a firing rate of gph. Boiler(s) shall be constructed in accordance with ASME Code
for Low Pressure Heating Boilers, Section IV. Boiler(s) shall have a gross I*B"R output of __________BTU/hr.
Manufacturer shall furnish each boiler with steam or water trim in ac cordance with ASME requirements, with UL approved oil burner designed and tested for boiler described above. Controls shall include high limit con trol, primary control, fuel pump, draft stabilizer. Where required, manu facturer will furnish special pedestal base to raise boiler to correct height to provide proper combustion area required by burner.
Additional equipment required for firing rate of 7 gph or more; (Select one of following specific e cipment desired) Boiler manufacturer will furnish oil burner equipped with flame safe
guard equipment with basic controls to meet F. M. and F. I. A. approval with control panel to provide 15 second trial for Ignition and 2 to 4 second flame failure shutdown. Photocell mounted in burner. Oil valve, motor trsmsformer and Photocell to be factory wired.
or Boiler manufacturer will furnish oil burner equipped with flame safe guard equipment as required by UL to provide 15 second trial for ignition and 15 second flame failure shutdown. Photocell mounted in burner. Oil valve, motor, transformer and Photocell to be factory wired. Boiler & Burner shall be as manufactured tod equipped by American Radiator & Standard Sanitary Corporation, New York, New York, Model No.or approved equal.
Page 33-4 17789