Document e0Db5QJmQR5gZ97LyX9j7zDy
i 250
CHAPTER 11
1952 Guide
d = density of air at temperature l,, pounds per cubic foot. . . Wi = vapor density of inside air, pounds per pound of dry air.
W,, -- vapor, density of outside air, pounds per pound of dry air. hig = latent heat of vapor at m., Btu per pound.
If the latent heat of vapor h/,, is assumed to be 1060 Btu per lb, Equa tion 6 reduces to:
Hi = 79.5 Q (Wi -- 'Wo)
(6a)
Equations 5a, 5b and 6a may also be used for determining the sensible and latent heat gains due to infiltration,in cooling, load computations.
SELECTION OF WIND VELOCITIES
. .The effect of wind on the heating requirements of any building should be given consideration for two reasons:
.1. Wind movement, increases the heat transmission of walls, glass, and roof,
'affecting poor Walls to a much greater extent'than good'walls.
2. Wind increases materially the infiltration of cold air through the cracks around doors and windows, and even though the building materials themselves (see Tables
1 ;and 2, Chapter 10).
.
. Theoretically, as a basis for design, the most unfavorable combination of'temperature and wind velocity should'be chosen. It is entirely possible 'that a building might require more heat on a windy day with a moderately
low outside temperature, than on a quiet day with a much lower outside temperature. However, the combination of wind and temperature, which is the worst, would differ with different buildings, because wmd velocity has a greater effect on buildings which have relatively high infiltration losses. It would be possible to compute the heating load:for a building for several different combinations of temperature and wind velocity which records show to have occurred, and to select, the.worst; combination, but designers generally do not feel that such a degree of refinement is justified.
Therefore, since Table 1 lists the average velocity, of winds occurring at temperatures equalled or exceeded 975 percent of .the. whiter; period for each locality, this, value should be the basis for estimating'infiltration
losses. When using the air change method it will, not be necessary, to consider the wind velocities. Designers employing the crack method
generally use values con-esponding to a lfi-mile wind. Due to the small effect of the wind velocity on the transmission, coefficient, the values in
Chapter 9,: based oil a 15-mile wind may be used with sufficient accuracy
for all ordinary conditions.
: ''
Exposure Factors Many designers use empirical exposure factors to increase the calculated
heat loss of rooms, or spaces on the side or sides of the building exposed to
the prevailing winds. However, the use of exposure factors is unneces sary when the Guide method of calculating heat losses is used. Therefore,
exposure factors may be regarded as factors of safety for the rooms or spaces exposed to the prevailing winds, to allow for additional capacity for these rooms or spaces, or to balance the radiation, particularly in the case of
multi-story buildings. Tall buildings may have severe infiltration heat losses, induced by their stack effect (see Chapter 10), which will require special Consideration. Although the exposure allowance frequently is as-, sumed to be 15 percent, the actual allowance to be. made, if any, must to
Heating Load
2511:
a large extent be a matter of experience and judgment of the designer, since there are at present no authentic test data available from which rules-.; could be developed for the many conditions rencountered in practice, ';>!
AUXILIARY HEAT SOURCES
The heat supplied by persons, lights, motors and machinery always should be ascertained in the case of-theaters, assembly halls; and industrial/ plants, but allowances.for such heat sources must be made only after careful;; consideration of all local conditions. In many cases, these :heat sources.: should not affect the size of the heating plant at all, although they may. have; a marked effect on.the operation and control of the system:. -In general,.:, where audiences: are present, the heating system must have sufficient! capacity to bring the building to the stipulated inside temperature before ? the audience arrives. In..industrial plants, quite a different condition; exists, and heat sources, if always available during occupancy, may be substituted for a portion of the heating installation. In no case should the
Table 5. Heat Equivalents of Various Sources*
Machinery (Motor in room = Motor Hp/efficiency x 2544
Btu/hr.
Machinery (Motor outside room) = Motor Hp x 2544
Btu/hr.
Electric Lights ............
= Kilowatts x 3413
Btu/hr.
Gas (Producer = 150) (Manufactured = 535) (Natural = 1000) Btu/cu ft.
* Additional values are given in Chapter 12, Table 29.
actual heating installation (exclusive: of heat sources) be reduced below that required to maintain at least 40 F in the building.
Electric Motors and Machineiy
Motors and the machinery which they drive, if both are located in the room, convert all of the electrical energy supplied into heat. This heat is retained in the room if the product manufactured is not removed until its temperature is the same as the room temperature.
If power is transmitted to the machinery from the outside, then only the heat equivalent of the brake horsepower supplied is used. In some mills this is the chief source of heating, and it is frequently sufficient to overheat the building even, in zero weather, thus requiring cooling: by ventilation the year 'round. Table 5 shows the heat output equivalent of various sources of heat in a factory.. For information concerning the heat supplied by persons, refer to data given in Chapter 6, and also Table 28, Chapter 12. For appliances see Table 29, Chapter 12.
INTERMITTENTLY HEATED BUILDINGS
In the case of intermittently heated buildings additional.heat is required for raising the temperature of the air, the building materials and the ma terial contents of the building to the specified inside temperature. The rate at which this, additional heat must be supplied depends upon the heat capacity of the structure and its material contents, and upon the time in which these are to be heated.13
This additional heat may be computed and allowed for as conditions re quire, but inasmuch as the heating system proportioned for taking care of the heat losses will usually have a capacity about 100 percent greater than that required for average winter weather, and inasmuch as most