EXHAUST SYSTEMS, GENERAL 6 COMFORT VENTILATION
i--w---- 3TANK
r --W------C TANK
SLOlr on TANK
TANK ACTS AS FLANGE
Q= CLW
ONE-HALF Q IN EACH SLOT IF SLOTS ON BOTH SIDES
FLANGED SLOT Q=CLW
Fig. 28*7. Installations that give good results create an air flow past the source to capture the contaminant. In diagrams above Q= required exhaust volume, cfmj 1 = length of slot, feetj W = width of table or tank, feet; and C Is a constant varying from 50 to 500 with the usual choice being 150 to 250, see details In "Industrial Ventilation" Manual Section V and Appendix.
Figures courtesy American Conference of Governmental Industrial Hygienists "Industrial Ventilation"
trolled by passing the air through a narrow slot into a plenum chamber. The flow dis tribution along a hood is fixed by the rabo of the velocity through the slot to the ve locity in the chamber For most purposes, the distribution will be good enough if the velocity through the slot is about twice the average velocity through the plenum Usu ally a slot velocity of 2,000 fpm is sug gested
Canopy hoods seldom provide the control expected There are several reasons for this velocity distnbubon is poor between
canopy and the source of evolubon, greater volume of air flow is required for contami nant control, control may be lost because of room air cross currents, and, frequently, this type of hood forces the employee to work under it, that is between the pomt of contaminant evolubon and the exhaust source
Fig 28-7 shows how the hood should overhang the edges of the tank for best re sults
Canopy hoods are best used where ther mal currents caused by nsmg hot air funnel
28-11