Document dap27vG5R06M8pnGQeJw1K1Re

oSg "w,2 If1 oSlu &>> 1@ tr go _j Zqco LjJ OS oo ol S o O a:. - S o 1=1 GO z 2 o tQC C o Oootc|sl o-u-< O S^ 08 O 0:2= S< 0:00 UJ Lu < h- O U<J rGd 270 MOTOR and WIRE RATING DATA Wire and Conduit Tables (Continued) -- Based on 1962 N.E.C. TABLES 310-12, 310-14 ALLOWABLE CURRENT-CARRYING CAPACITIES OF INSULATED COPPER (Cu.) AND ALUMINUM (Al.) CONDUCTORS IN AMPERES - Not more than three conductors in raceway or cable or direct burial -- Based on room temperature of 30C., 86F. Paper Rubber Thermo-plastic Type R Type RW Type RU. Rubber Type R, RW, RU, Rubber Type RH RUH (14-2) Asbestos Type 1A Thermo-plastic Type TBS Type RUW, RUW Type RH-RW Silicone Type SA Wire (14-2) (12-2) (See Note 9 below) Var-Cam Type V Size Type RH-RW Type RHW Asbestos Asbestos AWG (See Note 9 below) Thermo-plastic Var-Cam Type AVB Var-Cam or Thermo-plastic Type THW Ml Cable In* 4VA MCM Type T, IW THWN 0 RHH Type AVI Impregnated Asbestos Type Al (W-8) Type AIA Asbestos Type A (H-8) Type AA Cu. 041. Cu. 0AL Cu. 041 Cu. Al. Cu. Al. Cu. Al. 14 15 15 ... 25 30 30 ... 30 ... 12 20 15 20 15 30 25 35 25 40 30 40 30 10 30 25 30 25 40 30 45 35 50 40 55 45 8 40 30 45 40 50 40 60 45 65 50 70 55 6 55 40 65 50 70 55 80 60 85 65 95 75 4 70 55 85 65 90 70 105 80 115 90 120 95 3 80 65 100 75 105 80 120 95 130 100 145 115 2 95 75 115 90 120 95 135 105 145 115 165 130 1 110 85 130 100 140 110 160 125 170 135 190 150 0 125 100 150 120 155 125 190 150 200 160 225 180 00 145 115 175 135 185 145 215 170 230 180 250 200 000 165 130 200 155 210 165 245 195 265 210 285 225 0000 195 155 230 180 235 185 275 215 310 245 340 270 250 215 170 255 205 270 215 315 250 335 270 ... 300 240 190 285 230 300 240 345 275 380 305 ... ... 350 260 210 310 250 325 260 390 310 420 335 ... 400 280 225 335 270 360 290 420 335 450 360 500 320 260 380 310 405 330 470 380 500 405 ... 600 355 285 420 340' 455 370 525 425 545 440 700 385 310 460 375 490 395 560 455 600 485 750 400 320 475 385 500 405 580 470 620 500 800 410 330 490 395 515 415 600 485 640 520 900 435 355 520 425 555 455 ... ... 1000 455 375 545 445 585 480 680 560 730 600 1250 495 405 590 485 645 530 ... ... 1500 520 435 625 520 700 580 785 650 ... 1750 545 455 650 545 735 615 ... ... 2000 560 470 665 560 775 650 840 705 ... ... CORRECTION FACTORS, ROOM TEMPERATURES OVER 30C. or 86F. 40 104 .82 .88 .90 .94 .95 45 113 .71 .82 .85 .90 .92 50 122 .58 .75 .80 .87 .89 ... 55 131 .41 .67 .74 .83 .86 60 140 70 158 75 167 80 176 .58 .67 .79 .83 .91 .35 .52 .71 .76 .87 .43 .66 .72 .86 .30 .61 .69 .84 90 194 100 212 120 248 140 284 .50 .61 .80 .51 .77 ... ... .69 .59 0 For AWG sizes 12, 10 and 8 use capacities listed for Type RH. 0 Far 3 wire, single phase service and sub-service circuits capacities of conductors RH, RH-RW, RHH, RHW and THW shall be: #2-100A., #1-1104., #0-1254., #00-1504 #000-1704. and #0000-2004. APPROXIMATE VOLTAGE DROP (Copper Conductor) Per Ampere Per 100 feet -- Wire 80% Power factor Size AWG or MCM Single Phase Three Phase 14 .4762 .4167 12 .3125 .2632 10 .1961 .1677 8 .1250 .1087 6 .0833 .0714 4 .0538 .0463 3 .0431 .0379 2 .0370 .0323 1 .0323 .0278 0 .0269 .0231 00 .0222 .0196 000 .0190 .0163 0000 .0161 .0139 250 .0147 .0128 300 .0131 .0114 350 .0121 .0106 400 .0115 .0091 500 .0101 .0088 600 .0094 .0082 700 .0089 .0077 750 .0086 .0075 800 .0085 .0074 900 .0081 .0071 1000 .0079 .0069 NOTES TO TABLES 310-12, 310-14 8. More Than Three Conductors In a Raceway or Cable. Tables 310*12 and 310-14 give the allowable current-carrying capacities for not more than three con ductors in a raceway or cable. Where the number of conductors in a raceway or cabte exceeds three, the allowable current-carrying capacity of each conductor shall be reduced as shown in the following Table: Number of Conductors 4 to 6 7 to 24 25 to 42 43 and above Per Cent of Values in Tables 310-12 and 310-14 80 70 60 50 Exception -- When conductors of different systems, os provided in Section 300-3, are installed in a common raceway the derating factors shown above apply to the number of Power and Lighting (Articles 210, 215, 220 and 230) conductors only. CUTLERH ANIMER 270 Where single conductor or multi-conductors cables are stacked or bundled without maintaining spacing and are not installed in raceways, the individual currentcarrying capacity of each conductor shall be reduced as shown in the above table. 9. Where Type RH-RW rubber insulated wire is used in wet locations the allowable current-carrying capacities shall be that listed in columns 2 or 3. Where used in dry locations the allowable currentcarrying capacities shall be that listed in columns 4 or 5. 10. Overcurrent Protection. Where the standard rat ings and setting of overcurrent devices do not corre spond with the ratings and settings allowed for conduc tors, the next higher standard rating and setting moy be used. Except as limited in Section 240-5. 11. Neutral Conductor. A neutral conductor which carries only the unbalanced current from other conduc tors, as in the case of normally balanced circuits of three or more conductors, shall not be counted in de termining current-carrying capacities as provided for in Note 8. In a 3-wire circuit consisting of two phase wires and the neutral of a 4-wire, 3-phase WYE connected system, a common conductor carries approximately the same current as the other conductors and is not therefore considered as a neutral conductor. 12. Voltage Drop. The allowable current-carrying capacities in Tables 310-12 and 310-14 are based on temperature alone and do not take voltage drop into consideration. (See table above -- right.) 14. Aluminum Sheathed Cable. The current-carrying capacities of Type ALS cable are determined by the . temperature limitation of the insulated conductors in corporated within the cable. Hence the current-carrying capacities of aluminum sheathed cable may be deter mined from the columns in Tables 310-12 and 310-14 applicable to the type of insulated conductors employed within the cable.