EMERGENCY ACTION PLANS
hazard control points in the plant. Being
able to give undivided attention to matters
of plant security, they can relay information
to fire or police departments without delay. The signal received at the fire department or assistance agency should locate specific* ally the site of the fire, or at least the building or area, so the fire can be found quickly.
Automatic sending stations (thermostatic detectors) may be used, but should not in terfere with the sending of the manual alarm.
Fire alarm sending stations should be near the natural path to exits and as far as possible from the probable source of fire. The fire alarm system should also he de signed and located for the convenience of the local plant or fire fighting brigade. In some plants the fire alarm bell located m indi vidual departments is augmented by a sys tem of shop whistle signals which are es pecially helpful if any of the employees or the fire fighting brigade members are on the outside of the plant
Regular checks should be made on the alarm system All stations should be in spected on a monthly basis by a responsible person, and the overall system should have a daily test to ensure it is in proper operat ing condition These daily tests should be conducted at a prearranged tune and under a variety of wind and weather conditions to determine whether the signal can be heard m all parts of the plant at all times
Baste principles of alarm systems The National Fire Protection Association lists0 five basic principles that are important to all evacuation alarm systems
That the alarm signal must be dis tinctive is a major reason for not adapting existing programing or paging systems to be used as fire alarm systems, for not using fire alarm systems for other,purposes, and for not combining fire alarm elements, dur ing installation, with those of devices used for other purposes The type of signal must be suitable to die circumstances in which it is used audible signals cannot warn the deaf, nor can visual signals effectively warn the blmd.
The alarm must be seen or heard by all occupants for whom the warning is in tended. Location and type of alarms and their sound intensity must be carefully planned If an alarm system is used for
evacuation purposes only, it is unnecessary and may be confusing to sound a coded sig nal. A continuous one is preferable.
The system must be arranged so that it can be tested periodically Tests are best conducted m connection with evacuation drills, and alarms sounded in the tests should be the same as those used for emer gency conditions.
Equipment should be designed and installed so that malicious operation is, at least, difficult In general the operation of a station should show that the station has been operated, such as by requiring a glass to be broken before the alarm can be acti vated.
The probable reaction of people in a protected premises must be considered when deciding whether a general (public) alarm shall be given (which may induce panic) or whether the alarm should be recognizable only by selected personnel who can prompt ly handle the evacuation
Electrical industrial signals There are a number of major types of electrical indus trial signals available They differ in rec ommended use, and tone and range of sig nal00
The various types of signal equipment available include
Homs are probably the most fre quently used signals They have loud, sharp, dearly defined tones, ana a wide range of power, making them suitable for use m a variety of industrial, commercial, and insti tutional areas Units are available for in terior or extenor installation and may be operated electncally, manually, or pneumat ically.
Sirens command the most attention and have the longest effective range, some
National Fire Protection Association, 60 Batterymarch St, Boston, Mass Fire Protection Handbook, 12th ed. Section 14
00This discussion is taken from Robert J Barnard, "Three Keys to Specifying Electncal Industrial Signals Proper Type, Proper Loudness, Proper Location" Actual Specifying Engineer, Medalist Publications, Inc., 5 90-91 (May 1961).