Document damzR4LgJLE3KZxbyygDJnvKe
HEATINC VENTILATING AIR CONDITIONING GUIDE 1942
It is evident that any pipe size adequate to take care of the probableflout will also be more than ample to take care of the average flow, and hence the latter has no bearing on the pipe size.
MAXIMUM FLOW
An estimate of maximum flow for various fixtures regardless of type of building with the water at about 35 lb pressure is given in Table 1.
To obtain the probable flow from Table 1, it is necessary to multiply the maximum flow by a factor of usage, and this factor varies with the
Table 1. Approximate Maximum Flow from Fixtures under Normal Water Pressures
Fixtures
Cold Water (Gallons per
Minute)
45 10 30=* 10
1
10 3 3 6 30 1 2 114 5 4 2 6 6 3 6 JO
Hot Water (Gallons per
Mintjtb)
0 0 0 0 0 0 3 3 6 30 1 2 1J4 5 4 2 6
3 6 0
^Actual tests on water-closet flush valves indicate 40 gpm as the maximum rate of flow with 30 lb pres sure at the valve; this would increase to 60 gpm (about 50 per cent) at 90 lb pressure. The 45 gpm has been, taken as an average flow; possibly, with very low pressures just sufficient to operate the flush valve, 30 gpm. could be allowed with safety. Urinal flush valves would vary proportionately in the same manner.
type of occupancy and with the number of fixtures in the installation. With only two fixtures it is possible that both will at some time be inoperation simultaneously. With 200 fixtures, however, it is unlikely that the entire 200 would ever operate at the same time. Consequently, the factor of usage becomes smaller as the number of fixtures becomes, greater, all other things being equal.
The maximum flow per fixture for cold water should be totaled inde pendently of that for hot water, and the sum of the two may be used in computing the probable flow through the incoming cold water supply main.
FACTOR OF USAGE
The principal fixture subject to wide variation in water demand is a flush valve closet, though special consideration should also be given to.
814
CHAPTER 46. WATER SUPPLY PIPING AND WATER HEATINC
the demand of shower baths, especially in athletic clubs and in manu facturing plants where the outgoing shifts create a heavy peak.
The curves of Fig. 1 suggest a method of selecting a factor of usage. The curve at the left should be followed for hot water piping and for cold water if the system has gravity tank closets, while the curve to the right allows amply for the influence of flush valve closets.
If the product of the number of fixtures in a building multiplied by the proper values in Table 1 totals 620 gal of water as the maximum flow, using flush tank closets, the factor of usage from Fig. 1 will be about 23 per cent, and the probable flow will be 620 X 0.23 = 143 gpm. This is the first item to be determined in the design of a water supply system. In a building using 143 gpm no serious difference in the size of the main supply pipe would be occasioned by use of flush valves, since the factor of usage with the latter would be increased only to about 25 per cent or 155 gpm.
The curves of Fig. 1 are believed conservative for toilet rooms in large office buildings which have early business hour peaks, especially in the men's toilets, but may not be conservative enough for plants such as were mentioned previously where heavy peak demands occur during certain bathing hours. The proper usage percentage for such cases must be a matter of judgment and might properly approach 100 per cent. The average flow will usually be considerably smaller.
Example 1. Assume that in a normal building, such as a residential hotel or an apart ment house, there are 50 flush valve water-closets, 50 lavatories, 50 sinks and 50 baths, and that it is desired to determine the probable flow in. a line supplying all of these fixtures with both hot and cold wa ter.
-CoW Water 50 W. C. x 45 gpm____________2250gpm 50 Lavs, x 3 gpm____________ 150gpm 50 Sinks x 4 gpm____________ 200gpm 50 Baths x 5 gpm_______ 250 gpm
Maximum flow...
..2850 gpm
Fig. 1 shows a factor of usage of 9 per cent.
[Probable flow of cold water is .2850 X 0.09.........................
257 gpm
Hot Water 50 Lavs, x 3 gpm_.._____ 150 gpm 50 Sinks x 4 gpm 200 gpm 50 Baths x 5 gpm_____ ___ 250 gpm
'
Maximum flow................ ... 600 gpm
Fig. 1 shows a factor of usage of 23 per cent.
Probable flow of hot water is 600 X 0.23__133 gpm Total for main supplying cold
and hot water (2850 + 600) X 0.08---------------------------------- 276 gpm It should be noted that this is a rate of flaw or an instantaneous demand.
.
WATER PRESSURE
The usual practice in buildings of moderate height is to place the water supply mains near the basement ceiling, with up-feed risers feeding the various fixtures on the superimposed stories. In tall buildings the pressure due to the weight of the water becomes so great as to limit.the service to vertical sections not exceeding about 20 stories in height. Beyond this approximate limit the valves on the lower stories will be noisy and the piping should be extra strong.
For these reasons, the considerations of this chapter are limited to horizontal mains and to risers which serve not more than 20 stories. In taller buildings it is usual to install separate horizontal mains for each superimposed zone, served by extra strong main risers.
815