LOSS PREVENTION PRINCIPLES Page 13-1
Corporate Loss Prevention Review/Revision
The Dow Chemical Company
Midland, Michigan
October 1993
Restricted For Use Within Dow and Subsidiaries
13. FIRED EQUIPMENT
13.1 SAFETY AND CONTROL OF FIRED EQUIPMENT
13.1.1 Scope
Fired equipment is used within Dow to produce steam, crack or
heat liquid and gaseous feedstocks, heat DOWTHERM treat
gaseous, liquid and solid by-products, gasify coal, and
perform other functions. When fired equipment is used in
this Loss Prevention Principle, it is refers to this type of
fired process equipment.
This LPP is not intended for
commercial fired equipment used for space heating, potable
water heating, and other non-process applications.
There are significant differences in size, configuration, fuels, number and type of burners, and draft systems among the equipment used in the different appli cations. The general principles for safety and control are common to most installations, but there are significant differences in specific requirements. Technology Center Design Guidelines and consultation should be used to determine specific requirements and special means of achieving the requirements of this LPP.
This LPP was developed for fired process equipment listed in
Appendix A.
Owners of other fired equipment may find this
LPP
to be a useful guide, but should consult their Technology
Center, local safety and loss prevention representative, and
industry standards such as NFPA, ASME, Factory Mutual, and
others.
These principles are to be used in conjunction with applicable codes, standards and regulations and applied with good engineering judgment. Where governmental requirements are more stringent, those regulations take precedence.
Appendix B is a list of references rel ating to the design,
manufacture, installation, operation and maintenance of fired equipment and controls. A brief description of the subject matter of each reference is included. The list is not all inclusive and designers should familiarize themselves with
codes, standards and governmental regulations that might apply to the particular installation.
13.1.2 General Requirements
A. All fired equipment shall be provided with a safety
system and a control system.
These systems
sometimes separate and independent systems,
be one integrated system.
are but
may
DO A 117489 CONFIDENTIAL
The Safety system performs sequencing and interlocking
functions.
It performs start-up and other automatic
sequenced operations.
The safety system
also
provides the monitoring function to ensure that all
parameters
are maintained within pre-set,
safe
boundaries, and it provides alarms, event logs, overrides, partial trips and total trips of the fired equipment.
The safety system is broader in scope than what has historically been called Burner Management.
intains
The control system is for dynamic control.
It
provides control of firing rate, combustion air flow,
air-to-fuel ratio and other applicable controls.
The
control system ma
safe conditions and optimum
relationships among the controlled parameters. The
control system includes all dynamic controls as well
as what has historically been called "combustion
control".
ronment
B. The
safety
system,
control
system,
field
instrumentation,
equipment and sub-systems shall
comprise a total system (the system) that protects
personnel, equipment and the envi
from harm
and provides stable and reliable control.
C. Designers shall be qualified to design the system for
the particular type and application of the equipment,
its fuels and process streams.
This requires a
working knowledge of:
1. The specific fired equipment purpose, type, operating characteristics and the potential hazards associated with the process and fuels.
2. The loss prevention principles, codes, standards and regulations applicable to the specific fired equipment.
3. The technology available to provide the measurement and control capability to perform the functions and meet the requirements specified in this LPP.
D. installation and testing of the safety system, control
system,
field instrumentation,
equipment
and
sub-systems shall be supervised by Dow personnel are responsible to ensure that all of requirements of this LPP are met.
who the
E. All new systems shall be reviewed during the design
stage and again after construction
(prior to
start-up) by the appropriate Technology Center for
compliance with this LPP.
F. A documentation package for each installation of fired
equipmen
t shall be maintained and available for
review.
The documentation package, as described and
specified within this LPP, must contain all
documentation of the system as it is currently used.
D0 A 117490 CONFIDENTIAL
G. All significant system modifications shall be reviewed
by the appropriate Technology Center prior to
implementing the change. The owner of the equipment
will determine whether a change represent
sa
significant system modification.
In those cases
where the owner is not certain, the Technology Center
should be consulted to determine whether a reviewt is
warranted. A log of significant system modifications
shall be maintained in the Documentation Package.
nager
H. Any deviations from this LPP shall be documented with the reviewing Technology Center and approved in writing by the major ma
responsible for the equipment, or by the site manager. These written approvals shall be maintained in the Documentation Package.
I. changes.
Each operating unit that has fired equipment shall
have a written security policy that prevents unwanted
changes to the system for the equipment.
The
security policy and procedures should require
superintendent or higher level approval of
This policy shall be maintained in the documentation package.
J. All installations of fired equipment shall be reviewed periodically by a review team consisting of persons from outside the operating unit who are familiar with fired equipment and this LPP, to ensure that the system meets all requirements of this LPP. The equipment owner shall set up the review frequency for
each
installation of fired equipment and include the record of review dates and report of the latest review in the documentation package.
K. Operations and maintenance of all fired equipment shall be performed only by trained personnel competent to perform such operations and maintenance.
13.1.3 Fired Equipment Operations
To obtain Technology Center support for construction or
operation of fired
equipment within The Dow Chemical Company,
the system must be designed according to the guidelines in
this LPP and be used in conjunction with sound operating
discipline
to accomplish the following
operational
requirements:
A. Pre-Lightoff Purge (Prior to Introducing First Ignition Source)
A continuous, uninterrupted purge at a pre-defined flow rate is required prior to trial for ignition. This purge must continue for a time period sufficient
to displace a minimum of five fire box and combustion-product-path volumes. These calculations for purge flow and time requirement calculations should be maintained in the documentation package. At all times during the purge the following mandatory
DO A 117491 CONFIDFNTIAL
prerequisites must be met or a repurge is required:
1. All safety shutoff valves must be proved
closed
on all fuels and process feeds to be burned in the
combustion zone.
2. All combustion-air and combustion-product
passages must be proved open.
3. All burner air registers must be set at the purge
position.
For multiple-burner fired equipment/
purge air flow should be as evenly distributed as
possible through all burners during the purge step
to prevent
pockets of combustible gas from forming.
4. Purge air flow must be at or above 25 percent of
design maximum air flow unless otherwise specified
in the Technology Center Design Guideline for the
specific equipment.
Redundant determinations of purge flow must be
utilized.
Purge air flow is not always measured.
Although direct measurement is preferred,
the
proper flow may
be inferred from pre-determined
damper settings, blower motor amps, flow switches,
pressure switches and by other methods.
For natural draft systems, a means of inducing draft to obtain adequate purge flow must be provided.
Steam or inert gas such as nitrogen or carbon dioxide can be used, or a special purge blower or jet eductor can be installed. In no case shall an expl osimeter be used as the only purge check prior to introducing the first ignition source. 5. All electric-arc ignitors must be de-energized. 6. It must be proved there is no flame in the fired equipment. NOTE: For solid waste incinerators, see Technology Center Design Guidelines.
B. Lighting the First Burner
that
The first burner may be a pilot burner or a main
burner.
For multiple pilots
are ignited
simultaneously, refer to Technology Center Design
Guidelines for the specific equipment.
Light-off of the first burner must be sequenced by the safety system and following safeguards must be met:
automatically all of the
1. Re-purge is required if a trial for ignition of the first burner is not started within 15 minutes after commencing to establish light-off
conditions. 2. Combustion air flow controls must be set to ensure air at a pre-determined safe flow rate specified for light-off.
Air flow must be at or above 25 percent of design maximum air flow unless otherwise specified in the Technology Center Design Guideline for the specific equipment.
Redundant determinations of combustion air flow must be utilized.
DO A U7492 CONFIDENTIAL
Combustion air flow is not always
measured.
Although direct
measurement
is
preferred, the proper flow may be inferred from
pre-determined damper settings, blower motor amps,
flow switches, pressure switches and by other
methods.
3. All burner air registers must be set at the
light-off position. For multiple burner fired
equipment, combustion air flow should be as evenly
distributed as possible through all burners during
the light-off step to prevent pockets of
combustible gas from forming.
4. Combustion zone pressure (furnace pressure) must
be stable at the designated set point for
light-off.
5. If the fired equipment has a steam drum, water
level in the steam drum must be at the level
des
ignated for light-off, usually lower than the
normal control set point to allow for swelling when
the fired equipment warms up after light-off.
6. Safety shutoff valves must be proved closed on
all fuel and process feeds burned in the combustion
zone, except when appropriately opened for the
burner being ignited.
7. Fuel controls must be set to ensure fuel at the
predetermined
pressure and flow rate specified for
light-off.
If the fuel is oil or other liquid
requiring atomization and temperature control,
these controls must also be in service.
8. A designated commercial grade fuel must be used
for light-off.
9. No flame must be detected prior to trial for
ignition.
10. The ignition source for the first flame must be
present before fuel is admitte
d to the burner.
11. There must be a limited time that fuel may be
admitted before the first flame is established.
If
the flame is not established during that time
window, the fuel safety shutoff valve must be
automatically closed.
The time limit must be as short as feasible for the
particular fuel and equipment type.
For gaseous
fuels and light oils, the time shall n ot be greater
than 10 seconds after opening the safety shut-off valves, and for heavy liquid fuel the time shall
not be greater than 15 seconds after opening the
safety shut-off valves.
12. Only one attempt is allowed to establish the
first flame. If the first trial for ignition is
e of the
unsuccessful, the fired equipment must be repurged. If the burner will not ignite, the caus
problem must be determined and corrected.
NOTE: There are special hazards associated with
lighting off
liquid fuel.
Liquid
fuel
can
accumulate on the floor of the combustion chamber
from unsuccessful light-off attempts. Vapors from
this accumulation can be an explosion hazard.
Uncontrolled burning of the liquid inside the
furnace or leakage of the o
0 A 117493
confidential
r
il to the outside of the
furnace can occur.
A procedure
must be
established to guide operations personnel in
handling these situations if liquid fuel is used.
13. Proof that the first burner has successfully
ignited must be provided by one or more flame
detectors, otherwise the burner fuel must be
automatically tripped.
14. All personnel must be at sa
fe location remote
from the fired equipment during trial for ignition
of the first burner for routine light-offs.
Written procedures must be established that specify protective measures and clothing to be used when personnel must be near the furnace for non-routine light-offs.
C. Warm-up Procedure
Warm-up schedules and procedures must be established for each piece of fir ed equipment. These procedures should be programmed into the safety system to the greatest extent practical.
1. Procedures must cover the various modes and
conditions that may be encountered such as cold
light-off,
warm light-off, hot light-off and
refractory drying.
2. The procedures must specify the rate that the
equipment is brought from its condition at
light-off to its on-line status or to its fully automatic controlled status.
3. The procedures must specify the timing and order in which successive burners may be lit.
4. The procedures for lighting subsequent burners must specify permissives to be in effect, time limits for trial for ignition and conditions under which a repurge is required.
5. The procedures mus t specify when and under what
conditions secondary fuels or process feeds may be introduced.
D. Automatic Control Capability
All fired equipment must be provided with automatic (modulating) controls to minimize manual operation of important control loops. These controls must be maintained in good working order, and they must be used in the day-to-day operation of the fired
equipment.
The following control loops are typical for a large
number of installations and should be designed for
automatic control where applicable.
Any other
control loops recommended for automatic control in
Technology Center design guidelines should also be
included.
1. Firing rate (fuel control) 2. Combustion air flow 3. Combustion zone pressure (furnace p
DO A 117494 CONFTDFNTIAL
ressure)
4. Drum level or heat transfer media level 5. Hot gas quench 6. Heat transfer fluid temperature
E. Continuous Indications and Trends
In addition to the normal operator interface with the
?rocess provided by the system, specific continuous ndications or trends are sometimes required by governmental regulatory bodies or by the Tech Center.
to analog
Continuous indications refers or digital gauges and meters that may be viewed at any time without calling it up via video terminal, selector
button panel, or switch.
Continuous trends means a record-over-time of any measured or calculated parameter that may be viewed at any time without "calling it up" or configuring it via a computer or selector.
F. Alarms and Event Logs
The following condition s must be alarmed (an automatic
log of these alarms is strongly recommended):
1. Disagreement among measurements 2. All trips or runbacks (Runbacks are defined in
13.1.4) 3. All conditions that lead to a trip or runback 4. Any trip that is disabled or by-passed
G. Automatic Trip, Runback, or Step-to-Safest-Status
e safety
An automatic trip, runback, or step-to-safest status must be provided by th system to protect personnel and equipment. The appropriate action must be predetermined and executed by the safety system for each of the applicable conditions below.
nt.
Other specific requirements and methods
for
determining the existence of these conditions and
proper location of instrumentation are discussed in
the Tech Center Design Guidelines for the specific
equipme
1. Incomplete or improper light-off sequence
2. Loss of flame
3. Low fuel pressure
4. High fuel pressure
5. Low combustion air flow
6. Low air to fuel ratio
7. Trip of any draft fan
8. Loss of quench flow
9. Complete closure of any combustion-air flow
control damper
10.
Improper combustion zone pressure
(furnace
pressure)
11. Loss of heat transfer medium flow
12.
Low drum level or low heat transfer fluid level
13. Loss of indication of process variables to the
DO A 117495 CONFTDFNTT Al.
ted trip
extent that it is imprudent to continue operation
14. Low atomizing fluid flow or pressure for liquid
fuel - must trip liquid fuel as minimum
15.
High combustion or product temperatures at
critical locations in the flow path
16.
Operator initia
H. Post-Trip Purge
Post-trip purge or immediate initiation of a
pre-light-off purge after a trip can cause a
hazardous condition under some circumstances.
The
consequences of a purge initiated immediately after a
trip should be considered for all possible fuels and
conditions.
The Technology Center Design Guidelines
for the specific fired equipment should be consulted.
I. Flame Snuffing
Flame snuffing using steam or other non-flammable
vapor may be considered as a method of extinguishing
a fire resulting from flammables escaping from a tube
rupture.
Snuffing is especially applicable for
process heaters used for heating flammable liquids.
These are important points when considering the use of
snuffing steam:
1. The snuffing medium flow must be greate
r than the
total air input capacity to the fired equipment.
2. If steam is used, condensate must not be allowed
to collect in the supply piping. A very reliable
condensate removal system must be used.
3. Consequences of the rapid temperature drop
associated with the introduction of the snuffing
medium into the combustion chamber must be known.
4. The supply of the snuffing medi
urn must be very
reliable.
Once snuffing has started, loss of
snuffing medium flow before the temperature has
been sufficiently reduced may cause an explosion as
air displaces the snuffing medium.
5. All fuels and process feeds burned in the
equipment should be tripped before the snuffing
medium is added, but snuffing must commence
immediately before the leaki
ng flammable can cause
an explosive mixture.
6. Tripping followed by snuffing can also be used to
prevent
fired equipment from igniting
an
approaching flammable vapor cloud.
7. A snuffing system will require maintenance and
inspections.
13.1.4 The Safety System - Functional Design
The safety system must be designed to protect personnel and
equipment from the hazards of explosion, implosion
, fire,
overpressure and overtemperature during all phases of
operation and under all operating conditions.
The safety
system should provide for a completely automated light-off of
the
first burner.
The following functions should be
performed by the safety system.
DO A 117496 CONFIDFNTIAL.
A. Sequencing
Safe design of the sequencing system and procedures is of paramount importance. Safety and loss records compiled by insurance companies show that most serious incidents involving fired equipment occur during the initial light-off sequence.
In order for the safety system to start and proceed to
a
successful completion of a sequence,
all
permissives for each step in that sequence must be
satisfied.
A permissive is a required state of the equipment
and process that must exist and be proven to exist
by
the instrumentation. A permissive is satisfied if it
is within the specified limits for the required time
period.
A permissive may be a constant value, a
function of other variables, a function of the step
in the seguence, a function of the mode of operation
or any combination of these.
1. Startup Sequencing
A sequencing capability which provides, as minimum, automat ed pre-light-off purge and remote light-off of the first burner shall be provided.
a
A typical startup sequence involves purging the combustion zone and combustion-product passes of the fired equipment to sweep out any possible accumulation of combustible gases, energizing an electric ignitor to ignite the first burner, operating valves to admit fuel to the burner.
controlling the combustion air and fuel flows to
the burner,
and verifying that a
successful
light-off has occurred. Guidelines for designing
the sequence and specific prerequisites for the
startup of specific fired equipment are found in
the Technology Center Design Guidelines for that
equipment.
2. Automatic Sequencing of Other Operations
Seguencing of oth
er operations similar to startup
should be provided.
One example is a normal
shutdown where load is ramped down and then
burners are sequentially removed from service.
Refer to the Technology Center Design Guidelines.
B. Alarming and Event Logging
An alarm scheme with appropriate annunciation, seal-in, display, acknowledge and reset capability shall be provided. An alarm setting can be a constant value, a function of other variables, or a function of the step of the operational sequence.
The system should be capable of logging time of
occurrence of alarms and events. In the event of a
trip or misoperation, the log provides a record for
post-event analysis.
Any specific guidelines for
alarms and event logging for each type of fired
DO A 117497 OONFTDE'NTTAl
equipment are in the Technology Center Guidelines for that equipment.
Design
Individual alarms for each alarmed event or parameter should be provided. If some alarms are combined, the system should provide sufficient information to determine the initiating cause of the alarm.
C. Safety System Intervention (Overriding)
lity.
The safety system must have ultimate overriding control capabi
This overriding capability must be designed and installed such that it has priority control over all other controls including control loops in manual mode.
Safety systems intervention may take the form of
blocking actions which prevent erroneous control
signals or commands from being executed,
and
runback actions which ramp down variables when a
change creates a po
tential hazard. The safety system
must be designed such that control system actions and
manual intervention within the predetermined safety
limits are not impeded.
Manual intervention that overrides the safety system in the safe direction only is allowed. For example, the safety system can permit manual tripping of a safety shutoff valve while the equipment is running, but will not allow th e safety shutoff valve to be manually opened when the safety system requires it to
be closed.
D. Tripping and Manual Reset
An automatic trip capability shall be provided for all fuel and process feeds to the combustion zone.
Other process inputs and outputs to the fired equipment must be examined to determine the necessity for automatic trips.
At least one manual trip, located a t a safe distance
from the fired equipment, must also be provided.
These trips shall be designed such that once tripped, reintroduction of the tripped energy input is prevented until the trip sequence is completed and is manually reset.
Manual reset means that plant operations personnel must take a deliberate action to rearm the trip after determination that it is safe to do so.
Trip
devices such as safety shutoff valves may be reset or relatched through electrical means via the safety system or by an operator from a location remote from the trip device, or they may be reset at the trip device itself if allowed by the safety system.
D0 A U7498 CONFIDENTIAL
E. Partial Trips, Sub-system Trips and Step-to-Safest Status
nit,
In addition to the ability to completely trip the u each installation should be reviewed carefully to determine whether any of the following capabilities could improve the safety or reliability of the unit:
1. Partial Trips
An example of a partial trip is an automatic trip of
one
or more
burners
in a multiple-burner
installation on load injection to prevent the fuel
header pressure from going low and causing
a
complete unit trip on low burner pressure.
2. Sub-section Trips
An example of a sub-system trip is a complete trip
of
one fuel system
of a multiple-fueled
installation allowing continued operation of the
unit or units on other fuels.
3. Step-to-Safest Status
For certain fired equipment, tripping the fuel under
some circumstances can create a condition that
is
more hazardous than the condition with continued
fuel input. One example where it is safer to not
trip the fuelimmediately is
a furnace with a
flammable process fluid being heated that has a
tube leak because it is better to incinerate the
fluid than to allow the formation of an explosive
vapor.
A thorough review of possible circumstances where
tripping
the fuel could be unsafe must be conducted for each installation of fired equipment. the Technology Center Design Guidelines specific fired equipment.
Consult for the
13.1.5 The Control System - Functional Design
The control system for each installation of fired equipment
shall be designed and installed to provide automatic control
of all functions necessary to ensure a safe and optimum
operation of the equi
pment throughout its entire range of
operations and operating conditions.
The following are
Minimum Requirements:
A. Stable dynamic control of all automatic control loops shall be provided.
B. An evaluation of each automatic control loop should be made to determine whether it should be provided with capability of being switched to manual control by plant operating personnel.
Sufficient indication of the status of the equipment,
the process and the controls must be provided to permit safe manual control.
NOTE: The safety system has safe-direction priority
DO A 117499 CONFTDFNTTAl
control over all other control including loops
switched to manual control. Attempts to manually
adjust the equipment that would increase the risk of
a safety or loss incident must be prevented.
These
protective blocks must b
e pre-defined in the system
design.
C. All transfer capability between automatic control and manual control shall be designed such that unsafe transfer of control from one mode to the other is prevented.
D. Indications, Trends and Displays
The system must provide the operator of the fired equipment sufficient indication of key variables such that the status of the equipment and c ontrols can be determined at a glance. Trends and displays supplement indication and may be displayed on screens upon operator demand. It Is advised that trending
capability be sufficient to allow trending of all analog inputs and all digital inputs.
Specific requirements are included in the Technology Center Design Guidelines for the specific equipment. 13.1.6 The Control System - Design of Common Control Loops
The following control loops are typical for a large number of fired equipment installations and where used should be designed and installed according to the following principles:
A. Firing Rate (or Load Control)
Firing rate is the rate that fuel is burned in the fired equipment, usually to provide useful energy output. Firing rate is to be varied automatically in response to changing demand
Firing rate shall be controlled by the control system
to ensure that the total fuel input does not exceed
the maximum capability of the fired equipment.
Fuel
input to any individual burner should not exceed the
capacity of the burner.
The measured variables (flow, header pressure, process temperature, etc.) that determine the appropriate fuel input to the fired equipment depends on the
application.
The safety system has priority over the control system to ensure safety in the event of control system failure and can be used to block control signals, constrain valve and damper actuators( or run back actuators to a predetermined, safe position, or close safety shutoff valves for any given condition.
These safety system interventions or constraint control s should be considered and utilized where applicable to prevent fuel flow increases when:
DO A 117500 CONFIDENTIAL
burner(s) high
fuel flow is at or above the capacity of the
air to fuel ratio is low combustion product oxygen is low combustion product CO or combustibles process fluid overpressure exists process fluid overtemperature exists combustion zone, quench zone or stack
are high temperature
is
drum level is low or heat transfer fluid flow is low equipment is at or above maximum output high combustion zone pressure (furnace pressure)
Consideration should be given to safety system interventions (overrides) to prevent manual increase of fuel flow for the above conditions.
B. Combustion Air Flow
The combustion air flow shall be controlled by the control system to ensure a safe level of combustion air.
d be
The safety system has priority over the control system
to ensure safety and loss prevention in the event of
control system failure and can be used to block
control signals, constrain valve and damper actuators
or run back actuators to a pre-determined, safe
position for any given condition. These
safety
system interventions or constraint controls shoul
considered and utilized where applicable to prevent air flow decrease when:
air-to-fuel ratio is low combustion-product oxygen is low combustion-product CO or combustibles are high
air flow is at or below the minimum specified burner manufacturer
by
Consideration should be given to safety system intervention (override) to prevent manual decrease of air flow f or the above conditions.
C. Air-to-Fuel Ratio
1. Air-to-fuel ratio control provides the ability to optimize fuel efficiency while ensuring sufficient air for safe combustion.
2. When air-to-fuel ratio control is used, the controller must directly proportion combustion air and fuel flow to the burners by using feedback from flow measurements or by moving the respective flow
positioners proportionately.
In no case should
feedback from flue gas analysis such as oxygen or
carbon monoxide be used to directly control the
ratio of air to fuel. Feedback from oxygen or
carbon monoxide in the flue gas may be used to bias
or fine tune the air-to-fuel ratio controller
output within a narrowly limited range.
3. For fired equipment with multiple burners, t
he
C>0 A 117501
CONFIDENTIAL
effect of a burner or burners being out of service
must be taken into consideration. If the air flow through the out-of-service burner(s) is not shut
off when the fuel is shut off, the design air and
fuel flows to achieve the desired ratio will not be
correct for the burners remaining in service.
The
air flow through the out-of-service burner(s)
should be shut off when
the fuel flow is shut off
if possible.
If this is not possible,
the
air-to-fuel ratio controller must be properly
compensated for to account for this condition.
4. When utilized, air-to-fuel ratio control must be
designed to prevent an unsafe condition when
variations in fuel composition cause an increase in
combustion air requirement.
5. It is recommended that ai r-to-fuel ratio control
be one of two types: lead/lag or pacing, a) Lead/Lag
Where practical, fired equipment should use a
metered air-to-fuel ratio control.
Metered
means that the combustion air flow and all the fuel flows are measured. The system must be configured using Select logic to accomplish the following: 1)Combustion ai
r flow requirements shall be
determined but the higher of:
fuel setpoint from the firing rate
controller, or
the actual measured fuel flow.
of:
2) Fuel flow shall be determined by the lower
air flow set point from the firing rate controller, or
the actual measured air flow.
With this design, an air flow increase alway s
leads a fuel flow increase when picking up
load, and always lags a fuel flow decrease
when dropping load to ensure that an adequate
volume of combustion air is available to
completely burn the fuel,
b) Pacing
Many smaller installations with one or two
burners
are supplied with pacing
type
control
air-to-fuel
ratio
systems.
The
positions of the fuel flow control valve and the
air
flow control device or
devices are
correlated to provide the correct air-to-fuel
ratio throughout the operating range. The fuel
control valve and air flow control device are
either physically linked, or the position of one
is set by position feedback from the other.
In most such systems the fuel flow is measured,
but the combustion air flow is not measured.
Failure or misadjustment of the mechanical or
electrical linkages can cause a hazardous
air-to-fuel
ratio.
Each
installation with
pacing control must have safeguards to prevent
explosions in the event of a linkage failure.
DO A 117502 CONFIDENTIAL.
iginally
Special Precautions -- Fired equipment or
supplied with pacing control can be converted to control where the air and fuel flow positioners are not linked, but in such conversions it is mandatory that the combustion air flow be measured and that a lead/lag system as described above be used.
D. Drum Level Control (or Feedwater Flow Control)
For most boilers and other fired equipment that
produces steam, drum level control is one of the most critical control loops. The control design that gives the best control in most of these installations is called three-element control.
For three-element control the steam flow, feedwater flow and drum level are all measured. One method of three element control is for the feedwater flow controller to use the measured steam flow as th e feedwater flow set point. That set point, however, is biased upward by low drum level and downward by high drum level.
13.1.7 System Design and Installation Requirements
The energy conversion process in any fired equipment can be quickly driven to a condition where property loss, safety or ecological consequences are severe. At the same time there is an economic incentive to operate the equipment at high capacity, the rmal efficiency and unit availability.
The system must, therefore, be designed and installed to perform with a high degree of dependability. The design and installation considerations discussed in this section can be used to help provide the level of dependability needed for safety and control of fired equipment.
A. General
lame
1. Technology
The technology available to meet the requirements of
each process such as f
detection, air flow
measuring, valve positioning, etc.
should be
evaluated
and the best proven technology
implemented.
chnology"
Modern technology should be used where it has a proven performance record, but consideration should be given to the compatibility of the new system with the existing plant control scheme. Piecemeal additions of the current "latest te that
result in a confusing array of different control schemes should be avoided.
Designers are urged to talk with appropriate experts
and operators of similar equipment to learn the
performance record of an
instrument,
valve,
operator, etc. in actual service before specifying
new equipment.
2. Speed
Natural time lags throughout each control loop mu St
be known and taken into account in designing and installing the system. The overall time required for measuring, scanning, processing, outputting and changing actuator positions must be designed such that safety and control stability is assured for all process changes encountered.
The safety system must be designed to safely shut
of five
down the fired equipment within a maximum
seconds from the time the initiating device is
activated until the safety shut-off valves are
fully closed. In the case of flame detectors, the
time delay inherent in detection must be included
in the five seconds. If the loss-of-flame contact
operates three seconds after the flame is actually
out, then the safety shutoff valves must be closed
within two seco
nds after the initiating device is
activated.
3. Time Delays
Time delays programmed into the safety system or
field instruments to eliminate false trips must be
kept to an absolute minimum and in no case shall
jeopardize personnel and equipment.
4. Redundancy
The system must incorporate appropriate levels of
redundancy from the point of measurement through
the input path, processing path and output
including
actuators
to
ensure
controllability and reliability.
path safety,
For this LPP, redundant means more than one, and
applies to any component, data path or power path
of the system. It is important that any redundancy
in the system be monitored and alarmed when a fault
is detected or when redundant process measuremen ts
do not agree.
a) Components
means individual
transmitters,
switches,
input
cards,
output
cards,
micro-processors, trip relays, etc. It must be
assumed that any one component will fail.
The
consequences of failure must be assessed and
redundancy of the components designed to meet
the reliability objectives.
b) Data Paths
The data input signal paths and control signal output paths must be considered in designing the redundancy of the system.
The design and installation of cable tray routing is important. All cable trays converging at a single entry point through a control room wall,
for example, creates a single point where fire or mechanical damage can shut down several
pieces of fired equipment possibly for a long duration.
simultaneously,
Separation of paths for redundant inputs and
outputs is critical to realizing the benefits of the redundancy.
This separation includes I/O cards, cable trays
and field junction boxes.
c) Power Paths
The instrument power path for the safety system
an
d the control system from the power source
through various power conditioners, must also be
designed with the appropriate level
of
redundancy.
Uninterruptible power supplies or
appropriate battery backup should be provided
for these power paths.
The power path for pump and fan motors and other
powered equipment should also be designed with
t
he appropriate level of redundancy.
For
critical applications,
automatic switchover
schemes for power sources should be used,
d) Auxiliary Systems
Reliability of the auxiliary systems can affect
the reliability of the fired equipment and its
safety system and control system.
Consequences
of failure of each of the following auxiliary
systems should
be assessed and each system
designed accordingly:
instrument air fuel atomizing cooling water lubrication
fluid
fuel supply air conditioning
nitrogen
5. Systems
Logic Applied to Redundant and Non-redundant
The decision to use one, two with OR logic,
two with AND logic or three with VOTING logic
is dependent upon the application.
Specific
recommended logic selections are discussed in
Technology Center Design Guidelines,
a) Single Component
When only one (flame detector, air flow
transmitter, microprocessor, etc.) is used in
the system, the process must be tripped or
driven to its safest status if the "one"
indicat
es that a trip condition exists, whether
the indication is real or due to an instrument
failure.
Any instrument failure which disables a shutdown must be alarmed and appropriate action must be taken. b) Two With OR Logic When redundancy consisting of two with OR logic is used, indication of a trip condition by either must cause a trip or drive the process to its safest status.
It is used when safety, loss or environmental
considerations
are
very
important
and
reliability
considerations are
relatively
DO A 117S0S CONFIDENTIAL
unimportant.
c) Two With AND Logic
When redundancy consisting of two with AND
logic is used, both must agree before an
action is taken. It is used
when reliability is
very important and there are no safety, property
loss or environmental consequences.
d) Three With VOTING Logic
When redundancy consisting of three with voting
logic is used, action will be taken when any
two of the three agree that an action is
required.
It is used when high reliability is
needed and safety, loss or environ
mental
consequences are severe. It is also used where
instrument reliability is questionable.
6. Signal Selection in Redundant Systems
The system must be designed and installed to ensure
that when two or more inputs are used to determine
a control output, the signal that causes the
control system or safety system to drive the
process in the safe direction is selec
ted.
For
example, the lower of two combustion air flow
signals and the higher of two fuel flow signals
should be used for combustion control.
A small allowable difference in the measurements should be predefined and alarmed when exceeded.
It is permissible to use a computed average of two or more signals if: a) the allowable difference in the measurements is small, b) a difference greater than allowable is alarmed, and c) the control falls back to safe direction control when the difference is exceeded. 7. Self-Diagnosis Self-diagnosis is the ability of the system to
determine that a fault or failure has occurred anywhere within the system that reduces the level of protection or controllability that was intended.
S elf-diagnosis capability is advertised by most
system vendors today; however, a thorough analysis must be made to determine whether the specific capabilities provided are adequate to secure the level of protection needed and to evaluate which is the best system for the application.
Self-diagnosis includes the capability to verify that control and safety outputs are executed
properly and within a predefined time limit.
This
requires that appropriate feedback from the
equipment and process be provided by the system
designers.
flame
Individual components and sub-systems should also
have self-diagnosis or self-checking capabilities.
For example, uninterruptible power supplies must
switch over when self checking reveals a problem,
and
detectors should be one of the self
DO A
117506
CONFIDENTIAL
checking type.
The system must be designed and installed such that operations personnel are alerted to system faults and all components of the system automatically fail to their safest status. 8. Failure Modes The system must be designed and installed such that failure of any single component will not jeopardize the safet y, environmental or loss prevention functions of the system. Some equipment such as valves and dampers can be designed to fail open, fail closed, or fail last.
The appropriate failure mode for each of these components must be determined to ensure safety. The failure positions can be a function of the operating status of the equipment.
The reasons used in d etermining the failure mode of
each output field device (control valve, safety
shutoff valve, etc.) should be maintained by the operating facility in the documentation package.
Where computers, programmable logic controllers (PLCs), or other electronic circuits are used, it must be recognized that certain electronic components can fail either conducting or
non-conducting.
The full consequences of both
types of failure for each loop must be assessed and
understood. Redundancy, self diagnosis and correct
failure modes are the tools to ensure reliability
of the safety and prevention functions of the
system.
9. Shielding, Connecting and Grounding
Poor wiring connections, poor circuit board
connections and improper gro
unding and shielding
are potential causes of unreliable performance of
the system.
Both the design and installation of
all components require attention to detail to avoid
future problems.
B. Field Instrumentation Principles
to make
1. Direct Measurement
It is better to measure a variable directly than to
infer the measurement.
Though it is sometimes
virtually impossible
all of the direct
measurements desired, it should be kept in mind
that serious consequences can result from relying
solely upon inferred data. For example, the use of
a duct pressure switch at the discharge of a forced
draft fan to infer purge air flow illustrates the
point.
A burner air register (and/or an air flow
control damper or stack damper) that can be closed
is sometimes located downstream of the pressure tap.
Undetected closure of any of these could cause the switch to satisfy the purge air flow permissive
D0 A 117507
confidential
when in actuality there is inadequate air flow.
The cost of providing safeguards that reduce risk to the same level as the direct measurement approach is often as high as providing the direct measurement.
2. edundancy
Analog Transmitters Versus Switches
Analog transmitters should be used in preference to
switches.
This includes pressure transmitters
rather than pressure switches and position
transmitters in preference to limit switches to
indicate the position of modulated dampers and
valves.
3. Redundancy of Field Instrumentation
It is recommended that some level of r be
installed for all measurements which can cause
process trip.
For true redundancy of a field mounted instrument, each sensor must be mounted on a different tap so that plugging or breaking off of the tap does not affect more than one measurement.
Redundancy can be obtained with two or more instruments that have the same measuring principle
or with two or more instruments that use different
measuring
principles.
An example of two
measurements of different principle is a pressure
transmitter on a boiler steam drum and a
temperature measurement of the steam in the vapor
space.
Saturated steam temperature can be used to
infer pressure.
The same measurement can be used for pre-trip alarm in addition to tripping the process.
control
and
C. Controlled Equipment and Sub-systems
1. The Combustion Air and Draft System
a) Fans shall have sufficient capacity to supply all
air required for safe operation plus 15 percent
volume flow as established by the boiler
operating at maximum load and at a specified
maximum inlet air or gas temperature to the fan.
b) Fans and d
ucts must be designed to withstand the
static pressure associated with the excess flow
capacity requirement above.
c) The arrangement of air inlets, duct work and air
pre-heaters shall minimize contamination of the
air supply by such materials as flue gas, water
and fuel or other combustible materials.
Appropriate drain and access openings shall be
provid
ed.
d) The air supply equipment shall be capable of
continuing
the proper air flow
during
. anticipated furnace pressure pulsations.
2 Fuel System and Process Feeds Burned in the Fired
Equipment
Schematic diagrams of typical fuel systems for installations of fired equipment can be found in
DO A 117508 CONFIDFNTIAL
the Technology Center Design Guidelines.
a) All fired equipment sha 11 be provided with means
of ensuring that the fuel at each burner tip is maintained at the correct flow rate, pressure, temperature, composition, viscosity and purity. b) All fired equipment shall be provided with means to positively isolate all fuel and process feeds
from the fired equipment, the fuel handling equipment, and other devices while maintenance
is being performed. c) The fuel system shall comply with the latest LPPs for Emergency Block Valves and Relief Systems. d) All fired equipment shall be provided with safety shutoff valves. Safety shutoff valves must stop all liquid and gaseous fuel input and process feeds to individual installations of fired equipment automatically and rapidly.
Safety shutoff v
alves must have the following
characteristics:
Be quick closing. The safety system must be
designed to safely shut down the fired
equipment within a maximum of five seconds
from
the time the initiating device is
activated until the safety shut-off valves are
fully closed. In the case of flame detectors,
the time delay inherent in detec
tion must be
included in the five seconds.
If the
loss-of-flame contact operates three seconds
after the flame is actually out, then the
safety shutoff valves must be closed within
two seconds after the initiating device is
activated.
Be for on/off service only. Cannot be used for
control or any other service other than
for
isolation.
Be of a design that provides positive shutoff.
Be provided with position switches supplied as
needed to prove the valve position.
Consist of automatic double blocks on all
gaseous and liquid fuels and process feeds
that are burned in the combustion zone.
A
vent, drain, purge or bleed must be installed
between the two automatic valves and the material discharged must be disposed of in a safe and environmentally responsible manner. The vent, drain, purge or bleed valves need not necessarily be automatically operated. Be located as close to the burners as practical to minimize entrained energy downstream of the safety shutoff valves. Be
close coupled. The distance between the upstream and downstream safety shutoff valves must be no greater than three pipe diameters or 12 in (30.5 cm), whichever is greater.
e) Pipe, valves, flanges, and fittings shall conform to piping specifications for the fuel and process feed conditions.
f) Piping for fuel and process feeds burned in the
DO A 117509 CONFIDENTIAL
fired eq
uipment shall be routed carefully with
respect to roadways and railroads to reduce the
possibility of components such as valves from
being struck by heavy maintenance equipment,
automobiles or derailed train cars,
g) Where fuel or process feed piping must be routed
through
buildings
or tunnels,
adequate
ventilation and leak detection must be provided,
h
) All piping carrying fuel and process feeds to be
burned in the combustion zone shall be designed
and
installed
with appropriate
purging
connections for maintenance.
3. Ignition and Combustion System
a) An ignitor is the device that first introduces an
ignition source into the fired equipment.
The
ignitor must be designed with the following
features:
Commercially manufactured or of proven design for the application. Remotely operated. Properly sized and aligned to provide sufficient energy to ignite the associated pilot or main burner. Used on a burner that is provided with flame
detection. b) A pilot is a burner that lights another burner. All pilots must incorporate
the following design
features: Commercially manufactured or of proven design for the application. Properly sized and aligned to provide sufficient energy to ignite the associated burner. Must be proved stable for a minimum of five seconds before permitting fuel to be admitted to the associated main burner.
If a continuous pilot, must be minimum of 10 percent of design maximum input of associated main burner unless otherwise specified in the Technology Center Design Guidelines. If a continuous pilot, must be continuously proved independently of the associated main flame unless equal protection is provided and documented in the documentation package.
of proven
If an interrupted pilot, the pilot must shut
down within 10 seconds after opening safety
shutoff valves for gas and light oil fuels, or
within 15 seconds after opening safety shutoff
valves for heavy oil fuels.
Safety shutoff valves must be provided for
pilots regardless of pilot size.
c) Main Burner
Commercially manufactured or
design
for the application.
Stable and self-supporting at all times if not
supplied with a continuous pilot.
Supplied with proper atomization if required.
Designed as an integral part of the overall
emission control system.
D0 A 117510
CONFIDENTIAL.
Designed for temperature of combustion air.
d) Flame Detection
Commercially manufactured detectors o
r of
proven design for the application.
UV or IR flame detector best suited to fuel and
furnace design. Flame ionization detector can
be used with approval of Technology Center.
Self-checking detectors.
Mechanical type
self-checking detectors are preferred.
If two detectors are used, must use both, or
one designated for proving flame for lig
ht-off
of first burner.
Aligned and focused to detect only the flame or
flames intended.
The total time from actual flame out until the
safety shutoff valves are closed must be five
seconds or less.
Detector response to loss of flame must be
under four seconds.
Detector installed such that it will detect
flame lift-off if possible. Flame lif
t-off is
a condition where the flame front moves away
form the burner tip further than is designed
for the Btu input rate of the burner.
Purge medium for detector must be clean, dry
and oil-free.
4. Furnace Conditions (Television)
Properly designed and installed furnace television
may be of significant value as a supplementary
indication of flame and othe
r conditions in some
furnace designs. It is of particular value during
start-up in viewing igniters, pilots and individual
burners for proper ignition. This is an aid, but
not a substitute for flame detectors and other
condition monitoring.
13.1.8 Maintenance, Inspection and Testing of the System
A. Critical Instruments
Critical instruments associated with the system be defined and tested according to the latest edition of the LPP for critical instruments.
shall
B. Documentation Package
A documentation package is required for each
installation.
It should be up-to-date, available,
and must contain the following:
1. Dow piping and instrument diagrams (P&lDs) 2. Critical instrument list, testing procedure for
each instrument, and record of tests 3.
Listing of trips and trip set points
4. Logic diagram for safety system 5. Control logic block diagrams
6. Source code for the safety system and the control system and wiring diagrams for relay systems
7. The security policy 8. Calculations for purge rate and purge time
requirements
DO A 117511
CONFIDENTIAL
F
safety
9. The reasons used in determining the failure mode of each output field device (control valve,
shutoff valve, etc.)*
10.
Applicable Technology Center Design
for the fired equipment
Guidelines
11. equipment
Operating procedures associated with the fired
12.
Written approvals of deviations from this LPP
13. Log of significant system modifications
C. Inspections and Reports Required by Governmental Agencies
Inspection schedules and other requirements, along
with
their proper reports and documentation, shall strictly adhere to authorized governmental requirements for fired equipment and systems. APPENDIX A LIST OF FIRED EQUIPMENT
agencies
Power and Utilities Technology Center Field-erected boilers (power boilers) Package boilers - single burner Package boilers - multiple burner Heat recovery steam generators - auxiliary fired
Hydr ocarbons Technology Center
Radiant-wall cracking furnaces (gas feed) Radiant-wall cracking furnaces (liquid feed) Fired steam superheaters
Multiple-burner process heaters - not radiant wall
CEP Technology Center Radiant-wall cracking furnaces (liquid feed) Multiple-burner process heaters - not radiant wall
Environmental Technology Center
Thermal oxidizers (TOX)
Thermal heat recovery oxidizers (THROX)
Halogen acid fu rnaces (HAF) Appendix A (continued)
The following fired equipment when involved in disposal of solid, liquid, and gaseous materials:
treatment
and
DO A 117512 CONFIDENTIAL
l
ovens rotary kilns Multiple-chambered incinerators
APPENDIX B LIST OF REFERENCES RELATING TO THE DESIGN, MANUFACTURE, INSTALLATION, OPERATION AND MAINTENANCE OF FIRED EQUIPMENT
ASME CSD-1 Controls and Safety Devices for Automatically Fired Boilers
The rules of this cod e cover requirements for the assembly, maintenance and operation of controls and safety devices installed on automatically operated boilers directly fired with gas, oil, gas-oil or electricity, and are applicable to the following service:
All automatically fired boilers regardless of fuel ratings; b) burners field-installed in automatically boilers.
input fired
Boilers with fuel input ratings of 400,000 Btuh (117 228 W) or below are covere d in this code under Part CR. Boilers with fuel input ratings of 12,500 Btuh or above, falling within the scope of NFPA 85A, NFPA 85B, FRPA 85D, NFPA 85E and water heaters, are excluded from this code.
NFPA 85A
Prevention of Furnace Explosions in Fuel-Oil and
Natural Gas-Fired Single Burner Boiler-Furnaces
This bulletin applies to boilers with fuel input greater than 12,500,000 Btuh (3663 KW) that use single burners firing natural gas, fuel oil, or both. It includes information on design, installation, operation and maintenance. This standard applies only to boiler-furnaces using single burners firing:
natural gas only, other gas with a Btuh value and characteristics similar to natural gas, fuel oil (only No. 2, 4, 5, or 6 grade), simultaneous firing of gas and oil for fuel transfer, simultaneous firing of gas and oil continuously.
NFPA 85B
Prevention of Furnace Explosions in Natural Gas-F
ired
Multiple Burner Boiler-Furnaces
This bulletin presents requirements for the design, installation,
operation and maintenance of specified boiler furnaces, their
fuel-burning systems and related control equipment.
This
standard applies to boilers with fuel input greater than
12,500,000 Btuh (3663 KW) and applies only to boiler-furnaces
using multiple burners firing natural gas and other similar
gaseous fuels.
NFPA 85D
Prevention of Furnace Explo
sions in Fuel Oil-Fired
Multiple Burner Boiler-Furnaces
DO A 117513 CONFIDENTIAL
This bulletin outlines equipment requirements, sequencing of
operations and interlock and alarm requirements for specified
boiler-furnaces.
This standard applies to boilers with fuel
input greater than 12,500,000 Btuh (3663 KW) and applies to
boiler-furnaces using multiple burners firing fuel oil only. NFPA 85G Prevention of Furnace Implosions in Multiple Burner
Boiler-Furnaces
The scope o f this standard is to establish minimum standards for the design, installation and operation of boiler-furnaces, their fuel burning, air supply and combustion products removal systems which include induced draft fans, related control equipment and the stack, to prevent furnace implosions and to contribute to operating safety.
NFPA 86 Ovens and Furnaces
This bulletin applies to Class A/B ovens or furnaces - heat
utilization equipment operating at atmospheric pressures and used
by industry for the processing of materials.
This standard
provides requirements for location, construction, operation,
heating system, ventilation, safety control equipment and fire
protection.
NOTE:
Current revisions and amendments of the above NFPA
guidelines take precedence over those listed.
North American Guidelines for Applications of MOD V to Burner Management
The purpose of this guideline is to assist MOD V application personnel in both the c entral group and manufacturing in the application of MOD V to fired equipment installed in the U.S.A. The basis of this document is the Dow Corporate Loss Prevention Principles. The intent is to provide a standardized method for enforcement of the burner management principles stated in the Loss Prevention Principles.
Europe Guidelines for Applications of MOD V to Burner Management
The purpose of this guideline is to assist MOD V application
personnel in both the central gr oup and manufacturing in the application of MOD V to fired equipment installed in Europe. The basis of this document is the Dow Corporate Loss Prevention Principles. The intent is to provide a standardized method for enforcement of the burner management principles stated in the Loss Prevention Principles.
APPENDIX C BURNER MANAGEMENT AUDIT FORM FOR FIRED EQUIPMENT
Location of Equipment (Plant/Block):
Date Form:
Name of Person Filling Out
THE FOLLOWING DOES NOT APPLY TO SPACE HEATERS, POTABLE WATER HEATING AND CERTAIN OTHER NON-PROCESS APPLICATIONS.
A. General
1. Have you read and understood LPP 13.1? No ( )
Yes (
)
2. Have all deviation from LPP 13.1 been documented and approved by either your major manager or site manager? Yes (
DO A 117514 CONFIDENTIAL
) No ( )
3. Have you developed installation?
13.1.8B) Yes ( ) No ( )
a documentation (LPP
package
for
this
4. Have you worked with your Tech Center regarding specific burner management guidelines related to your equipment? Yes ( ) No ( )
5. Have you written
changes
to
Yes ( ) No ( )
a security policy
the
system
preventing unwanted or equipment?
6. Do you have a written warm-up procedure for this equipment? Yes ( ) No ( )
7. Does your installation utilize flame snuffing?
Yes (
) No ( ) B. Pre-Lightoff Requirements
1. Do you have a continuous, uninterrupted purge sufficient to displace a minimum of five fire box and combustion-product-path volumes prior to trial for ignition?
2. Is your purge flow rate at or above 25% of design maximum? Yes ( ) No ( )
Are redundant determinations of purge flow utilized? Yes ( ) No ( )
3. If your fire d equipment is natural draft, what means do you
use to obtain adequate flow for purging?
C. Lighting First Burner
1. Is it possible to have a flame detected prior to trial for
ignition? Yes ( )
No ( )
2. If the initial attempt to light the burner is unsuccessful, is it possible to try again before repurging the system? Yes ( ) No ( )
3. How many flame detectors do you have monitoring your first burner?
D. Safety Sys tem
1. Is your pre-lightoff burner automated?
No ( )
purge
and
remote
lightoff
of the Yes
first ()
2. Does capability?
No ( )
your
safety
system
have
ultimate
overriding control Yes ( )
00 A 11751s
confidential
3. Do you have an automatic to the combustion zone?
No ( )
trip
for
all
fuel
and
process Yes
feeds
()
4. Do y
ou have a manual trip for the equipment located at a safe distance?
Yes No ( )
(
)
5. Does the system have the safety shutoff valves fully closed
within five (5) seconds from the time the initiating device
is activated?
Yes ( )
No (
E. Control System
1. Is your system automatic
ntrol? Yes ( ) No ( )
set up and
for bumpless transfer manual
between co
2. Do you use feedback from flue gas analysis control the ratio of air to fuel?
No ( )
to directly
Yes (
)
3. Does your installation have pacing? (See LPP 13.1.6 C5.2)Yes ( If yes, what safeguards do you have to prevent explosions
from linkage failure?
)
) No
F. Controlled Equipment and Sub-Systems
1. Do your combustion air fans have req
uired for safe operation plus 15%? No ( )
capacity to Yes
supply ()
all
air
2. Is your equipment set up to ensure that the fuel at each burner tip is maintained at the correct flow rate, pressure, temperature, composition, viscosity and purity?
3. Complete trip, partial trip, runback or step-to-safest status are required as part of the safety system. Which are applicable to your instal
lation? (See next page)
PLEASE SELECT THE APPROPRIATE PROGRAMMED RESPONSE AS IT PERTAINS TO YOUR FIRED EQUIPMENT
RIP
TRIP
BACK
COMPLETE
T SAFEST N.A
PARTIA L
RUN
STEP-TO-
1. Incomplete/improper light-off sequence
2. Loss of flame
DO A 117516 CONFIDENTIAL
3. Low fuel pressure
4. High fuel pressure
5. Low combustion air flow
6. Low air to fuel ratio
7. Trip of any draft fan
8. Loss of quench flow
9. Closure combustion/air flow control damage 10. Unstable combustion zone pressure
11. Loss of heat transfer medium flow 12. Low drum level/low heat transfer fluid level 13. Loss indication of process variables 14. Low atomizing fluid flow/liquid fuel pressure 15. High combustion/product temperature
16. Operator initiated trip
UNIT LOSS PREVENTION INSURANCE REPORT
1. Summary of Unit Features and Status
Area/Country
North America / USA
Site
Louisiana Divison
Unit Superintendent
Ken Fox
Division
Louisiana Division
Unit
Power 1
Location
Plaquemine, La.
Date
5/19/94
Building Number/s
Bldg.2801
Date of Previous Inspection
3/10/92
Type of Operation
Power Plant and Water Treating
Inspected By (from Safety & Loss Prevention)
Buck Bailey
Inspected by (from Plant)
Marty Morrison
Give a written summary including overall evaluation comments, comparison to previous inspection, and
summary of recommendations:
Consolidated Audit summary is attached as a separate report.
Form C-91870A
IS-0850
Page 1 of 6
DO A 117518 CONFIDENTIAL
1/93
UNIT LOSS PREVENTION INSURANCE REPORT
2. Summary of Ratings and Recommendations for Unit
UNIT RISK FEATURES
3. Plant Condition and Appearance
4. Unit Risk Analysis Package
5. Changes Since Last Inspection
6. Features for Areas in Unit
7. Drainage and Containment
8. Tank Storage
9. Electrical & Instrument Conditions
10. Chemical Inventory & Isolation
11. Management Considerations
12. Plant Reliability
R = Recommend Upgrading
G = Good
F = Fair
E = Excellent
RECOMMENDATION R F G E NA NUMBER/S
X
X X X
X X X
NA = Not Applicable
Refer to Guideline for definitions of ratings. For recommendations, see Pages.
Give a brief narrative background summary including history of unit with details on age, construction phases, original plant, etc.
h Ale*.
j ^ *1 i *2--
i< r-
fS, j ^ ~ u* ts
j fii /la.'ii'- ^ J
^ ct^j + >a ^
1r ^^ a *s-t at
^> j
j life 3
zllV Tri>i
A `'1 / ^
'***
Form C-91870A
IS-0850
Page 2 of 6
DO A 117519 CONFTDFNTTAl
1/93
UNIT LOSS PREVENTION INSURANCE REPORT
3. General Unit Information
Plant Unit
, f U h)>h t-S
Unit Products
Raw Materials /l>e/
A^iv'ir U/a/cs'
Operating Davs/Week?
.
Operating Hours/Day? 2V
Plant Condition & Appearance - Description
No. of Shifts? e
Date Hours per Shift?
4. Unit Risk Analysis Package
Items which must be attached as part of Risk Analysis Package (Check if attached/Give any explanations)
Block Flow Sheets
Yes
F&EI Calc. Sheets for Highest MPPD and Highest MPDO & Bl
Yes
Process Description
Yes
CEI Summary Sheets
Yes
Plot Plan with Areas of Exposure and Protection Features
Yes
Business Interruption Data
Yes
F&EI Risk Analysis Summary
Yes
Replacement Value
^ 3 ft rw.iv'>-
Interdependencies with Other Dow Facilities & Which Facilities?
Power and steam generated by the Power 1 plant is supplied through a distribution network to all other plants at the site. Power 2 is a co-generator of power and steam. Condensate returned from the other plants is used to feed the steam boilers.
Interdependencies with Non-Dow Facilities Raw Material supplier, Utility Supplier, Final Processing, Sole Supplier, etc.
Fuel gas is received into the site from a south Louisiana supply network. Oxygen and mitrogen is received by pipeline from a local company and distributed by the Power plant. An electrical tie in place to send and receive power from the local utility company.
Spare Parts Available ror Critical Equipment? Which Critical Equipment?
Yes, inventory is maintained locally.
List Top 3 Critical Items 1. Boilers 2. Turbines 3. Generators
Spares Available?
Yes
5. Changes Since Last Loss Prevention Inspection
Significant Changes to Plant Since Last Loss Prevention Inspection? Any Incidents Since Last Inspection?
1. Boiler NOX Reduction Project 2. Cathodic protection project
3. i31-1 Car' f" 1 f '"0t> 1*- -- u t 1 >.
Management of Change Program Established?
Yes participation follows the U.S.Safety Standard
Significant Capital Projects in Progress or Planned? Give Title and Amount of Capital.
1. Boiler NOX reduction project (completion)
f H (ar-"-1
" i1 Ur/ 1' V, i )
UP Review Done/Planned? Yes
Date?
Form C-91870A
IS-0850
Page 3 of 6
DO A 117520 CONFIDENTIAL
1/93
UNIT LOSS PREVENTION INSURANCE REPORT
6. Features for Areas in Unit
REFER TO PLOT PLAN WHICH IS TO BE ATTACHED. (CHANGE TOP HEADING NAME IF NEEDED.)
FEATURE AREA
*
SEPARATION PER LPP 2.2?
m
6.?L'
FIRE WALLS FOR SEPARATION? HOUR RATINGS?
PERCENT OF PLANT VALUE?
STRUCTURE AREA?
STRUCTURE HEIGHT?
NUMBER OF OPERATING LEVELS?
TYPE OF CONSTRUC TION? (COMBUSTIBLE OR NOT?)
OPEN OR CLOSED CONSTRUCTION? (PERCENT OPEN?) FIREPROOFING USED? (TYPE?)
DELUGE & DRAINAGE IN LIEU OF FIRE PROOFING?
SPRINKLER SYSTEMS?
DELUGE SYSTEMS?
FOAM SYSTEMS?
AUTOMATIC OR MANUAL TRIGGERING OF SYSTEMS?
HYDRANTS IN AREA?
FIRE WATER MONITORS?
INERTING SYSTEMS?
FIRE EXTINGUISHING SYSTEMS? (CO.HALON, ETC.) OTHER FIRE PROTECTION SYSTEMS? OTHER SYSTEMS? SPECIFY.
JftNK PARM
*n.*re~*
REAOtlpN/
JjBr
fit
-
OTHER (SPECIFY)
WARE HOUSE
OFFICE/
CONTROL ROOM
Form C-91870A
IS-0850
Page 4 of 6
DO A 117521 CONFTDENTTAI.
1/93
UNIT LOSS PREVENTION INSUhiANUb RbPURI
7. Drainage and Containment
Type of Impoundment - Remote Pit vs Dike
Volume per LPP 7.6.2.G?
Testing of Drainage System?
Firewater Containment Considered?
Open Trenches or Closed Drains?
Drainage Away from Tanks & Equipment?
Plans/Equipment for emptying Pits/Dikes?
Vapor Suppression of Pit/Dike using Foam?
Tank separation distances per LPP 7.6.6? Worst Rainfall Considered? Impervious Containment Surfaces? Operating Discipline to Keep Pits/Dikes Empty?
8. Tank Storage
Types of Tanks (Pressure Vessels, Atmospheric Tanks, etc.)
Redundant High Level Alarms?
Pressure Relief?
Vessel Registration Program?
With Inspection & Testing?
Codes Observed(A.P.I., A.S.M.E. U.L., T.U.V., etc.)
Interlock Between High Level Alarms & Pumping?
Vacuum Relief?
Pressure Vessel Relief Registration?
With Inspection & Testing?
9. Electrical and Instrument Conditions
Electrical Classifications Areas Well Defined?(See LPP 3.1)
Non-classified Plant
El. Classification Drawing Up- To Date? Last Revision Date?
Redundant Electrical Feeds?
Yes
Backup Generators?
Yes
Grounding with Inspection Program?
Oil Filled Electrical Equipment? Yes
Oil Filled Equip. Indoors or Outdoors? Outdoors
Cable Penetrations Sealed? Yes
Cable Trays Exposed to Potential Fires?
Cable Trays Sprinkler Protected? Yes
-Type of Process Control - MOD Control?
- Process Information Systems?
Periodic Review of MOD Program?
- Audits of MOD Program and Alarms?
10. Chemical Inventory & Isolation
Handling Flammable, Toxic or Corrosive Liquids and/or Gases
Are There Flammable Liquids/Gases? Flammable gas
Is There Flammable Gas Detection? No
What are they? Methane, Hydrogen, Syn-Gas
Frequency of Testing Gas Detectors?
^ '
Hazard Ratings Shown on Tanks? (LPP 1,5) Not used in LAD NFPA Ratings or Other Shown? Not used in LAD
Emergency Block Valves
Other Special Hazards
Are there Toxic Liquids/Gases? Yes
What are they? Chlorine cylinder
Are there Corrosive Liquids/Gases? Yes
What are they?
Caustic
-,
Are EBVs Identified in Drawings? Yes
Are EBVs Identified in Field?
Frequency of Testing of EBVs? 8*.-L. JiwVj /f.* Kl*. S
Are EBVs Fire Rated in Flammable Service? No
Any Other Special Hazards which Increase Risk of Operation?
Form C-91870A
IS-0850
Page 5 of 6
DO A 117522 CONFIDENT! Al
1/93
UNIT LOSS PREVENTION INSURANCE REPORT
11. Management Considerations
Last Loss Prevention Inspection?
March 1992
Last Consolidated Audit?
March 1992
Other Audits or Reviews of Plant? (e.g. T/C) Tech Center
Implementation of Minimum Requirements? Yes
Operator Training Procedures Written & Current? Yes
Operating Procedures Written & Current? Yes
Emergency Plans Written for Unit? Yes
Written Plans for Fire Protection Impairment?
Yes,LAD S&LP Standards
Date of Last Hypothetical Emergency?
shi
Critical Instrument Program Established?
Yes
Emergency Plans Shared with Other Units & Oil .Site?
No
Testing of Critical Instruments? Yes
Preventative Maintenance Program in Place?
Yes
Reactive Chemicals Program?
Yes
Date of Last Reactive Chemicals Review? March 1992
Plant Contact Person for Loss Prevention?
Ken Fox, Marty Morrison
Contractor Safety Program Established? Yes
Smoking Regulations & Enforcement? Yes. LAD policy
Other Management Programs in Place Affecting Loss Prevention? List e.g., Fire Protection Inspections, Insurance Inspections
12. Plant Reliability r"
Production Capacity
Per Cent of Capacity for Year
Theoretical Hours/Year for Production Capacity?
Hours/Year Loss Due to Outages or Percent
Reduced Rates
Reliability
(Hours. Operation at Theoretical Rate) (Total Hours Available)
Form C-91870A
IS-0850
Page 6 of 6
DO A 117523 CONFIDENTIAL
1/93
I
FIRE & EXPLOSION INDEX
AREA/COUNTRY
DIVISION
LOCATION
-*!
DATE
North America / USA SITE
Louisiana Division MANUFACTURING UNIT
Plaquemine.Lae PROCESS UNIT
5/26/94
Loouisrana Division PREPARED BY;
Power 1
Boiler 4
APPROVED BY: (Sup*rmt*ndnt)
BUILDING
Marty Morrison REVIEWED BY: <Mang*in*nt)
Ken Fox REVIEWED BY; (Technology Center)
B-2801 REVIEWED BY: (Safety 4 Lott Prevention)
? MATERIALS IN PROCESS UNIT
?
Buck Bailey
Methane STATE OF OPERATION
BASIC MATERIAL^) FOR MATERIAL FACTOR
__ DESIGN __ STARTUP JC.NORMALOPERATION __ SHUTDOWN Methane
MATERIAL FACTOR (See Table 1 or Appendices A or B) Note requirements when unit temperatures over 140 *F (6
21
1. General Process Hazards
Penalty Fac Penalty Fac tor Range tor Used (1)
Base Factor..........................................................................................................
1.00
1.00
A. Exothermic Chemical Reactions B. Endothermic Processes
0.30 to 1.25 0.20 to 0.40
0.00 0.00
C. Material Handling and Transfer D. Enclosed or Indoor Process Units
0.25 to 1.05 0.25 to 0.90
0.00 0.00
E. Access
0.20 to 0.35
0.00
F. Drainage and Spill Control
Oaallons 0.25 to 0.50
0.00
General Process Hazards F actor(FI)..................................................................................
1.00
2. Special Process Hazards Base Factor..........................................................................................................
1.00
A. Toxic Material(s)
0.20 to 0.80
B. Sub-Atmospheric Pressure (< 500 mm Hg) C. Operation In or Near Flammable Range ___ INERTED _X_ NOT INERTED
0.50
1. Tank Farms Storage Flammable Liquids
0.50
2. Process Upset or Purge Failure
0.30
3. Always in Flammable Range D. Dust Explosion (See Table 3)
0.80 _ 0.25 to 2.00
E. Pressure (See Fiaure 2)
Ooeratina Pressure 45 Dsia
Relief Settina 55 Dsia
F. Low Temperature G. Quantity of Flammable/Unstable Material
___ 0.20 to 0.30 Quantity-100 lb
He = 21.500 BTU/lb
1. Liquids or Gases in Process (See Figure 3)
2. Liquids or Gases in Storage (See Figure 4)
1.00 0.20 0.00
0.00 0.30 0.00 0,00
0.22 0.00
0.00 0.00
3. Combustible Solids in Storage, Dust in Process (See Figure 5) H. Corrosion and Erosion 1. Leakage - Joints and Packing
0.10 to 0.75 0.10 to 1.50
0.00 0.00 0.00
J. Use of Fired Equipment (See Figure 6)
1.00
K. Hot Oil Heat Exchange System (See Table 5)
0.15to 1.15
0.00
L. Rotating Equipment
0.50
0.00
Special Process Hazards Factor (F2)..................................................................................
2.72
Process Unit Hazards Factor (FI x F2) * F3................................................................... Fire and Explosion Index (F3 x MF * F&EI)........................................................................
2.72
57
(1) For no penalty use 0.00.
DO A 117524 CONFIDENTIAL
Print Date: 5/26/94
r
LOSS CONTROL CREDIT FACTORS r '
1. Process Control Credit Factor (Cl)
Feature
a. Emergency Power b. Cooling c. Explosion Control d. Emergency Shutdown e. Computer Control
Credit Factor Range
0.98 0.97 to 0,99 0.84 to 0.88 0.96 to 0.99 0.93 to 0.99
Credit Factor Used (2)
0.98 1.00 1.00 0.98 0.93
Feature
f. Inert Gas ? Operating Instructions/Procedures h. Reactive Chemical Review
1. Other Process Hazard Analysis
Credit Factor Range 0.94 to 0.96 0.91 to 0.99 0.91 to 0.98 0.91 to 0.98
Credit Factor Used (2)
1.00 0.92 0.91 0.96
Cl Value (3) 1 0.715 |
2. Material Isolation Credit Factor (C2)
Feature
Credit Factor Range
Credit Factor Used (2)
Feature
a. Remote Control Valves 0.96 to 0.98
! b. Dump/Blowdown
0.96 to 0.98
0.96 1.00
c. Drainage d. Interlock
u/Ji iAe-t 'lie"
C2 Value (3) | 0,874 j
Credit Factor Range 0.91 to 0.97
0.98
Credit Factor Used (2)
0.91 1.00
3 Fire Protection Credit Factor (C3)
Feature
a. Leak Detection
b. Structural Steel
rt > tut
c. Fire Water Supply
d. Special Systems
e. Sprinkler Systems
Credit Factor Range 0.94 to 0.98 0.95 to 0.98 0.94 to 0.97
0.91 0.74 to 0.97
Credit Factor Used (2)
1.00 1.00 0.97
Feature
f. Water Curtains g. Foam h. Hand Extinguishers/Monitors i. Cable Protection
Credit
Credit
Factor
Factor
Range Used (2)
0.97 to 0.98 1.00
0.92 to 0.97 1.00
0.93 to 0.98 1.00 0.94 to 0.98 '"i-oqj.
dt Yaa.,dL\~
K> d
C3 Value (3) | 0.970 |
Loss Control Credit Factor * Cl x C2 x C3 (3) *
[ 0.606
PROCESS UNIT RISK ANALYSIS SUMMARY
1. Fire and Explosion Index (F&EI)..........
(See Front)
57
2. Radius of Exposure...................................
<ngm7>
48
ft
3. Area of Exposure................................................................
7218
sq.ft.
4. Value of Area of Exposure (1994 Dollars).................................................................... ....... $MM
5. Damage Factor....................................................... 0.56
6. Base Maximum Probable Property Damage (Base MPPD) [4 x 5]...................
7. Loss Control Credit Factor ........................(See Above)|
0.61
$MM
8. Actual Maximum Probable Property Damage (Actual MPPD) [6x7]....
................ $MM
9. Maximum Probable Days Outage - (MPDO)
(ngm|
64
days
10. Business Interruption - (Bl)................................................................................................. SMM
18.98 10.60
6.42 1.48
| I
| |
(2) For no credit factor enter 1.00
(3) Product of all factors used
Refer to "Fire & Explosion Index Hazard Classification Guide" (Form #471-00001) for details
Print Date: 5/26/94