ASBESTOS HANDLING IN F-UNIT COMPRESSOR BUILDING
Asbestos samples were taken July 8-11 in the F-unit compressor building (B-553). The transite roof on the building was cut on July 9-11 to install a catwalk on the roof. Three areas of the building were sampled: <?3 Hyper, //4 Spindle, //I Purge compressor. Samples were taken on July 8 to obtain a normal background concentration.
The samples were taken for 6 to 8 hours using Du Pont P4000 pumps calibrated at approximately 3 Lpm with Millipore AAWP
mixed cellulose ester filters (open face). Analysis of the samples was done by Clayton Environmental Consultants using NIOSH F& CAM 239.
The results, seen in Table I, indicate that a detectable level of fibers normally exists in the building. The cutting operation did not raise this level significantly above normal. All concentrations are well below the OSHA PEL of 2 fibers (>5/0/cc. Analysis of the transite roof by X-ray diffraction shows a 2Z chrysotile content.