Lead Plumbing Selected for School Laboratories
LUMBING in the chemi
Pcal laboratory and physi cal preparation room of the
damage that may result from embedding pipes directly in concrete or masonry. The
large new Mount Pleasant
horizontal runs are supported
Regional Senior High School,
continuously on 2 x 2 in.
Providence. R. I., was done
angle irons with hangers
with lead to solve the vexing
shaped to fit the angles.
problem of handling corro
Attention should be given
sive chemical wastes. About
to the heavy weight of lead
1500 ft. of lead pipe, of which
pipe used in this installation.
some 75 per cent is 2 in. pipe
For chemical wastes greater
weighing 12 lb. per ft., has been used in this installation. There are 86 lead stubs and 7 lead stacks; lead bag traps
ADVERTISERS STUDIOS
Mount Pleasant Regional Senior High School, Providence. R. /.. where lend is used in the
laboratory pi,umtiing.
wall thickness is naturally required than for ordinary wastes since conditions are more rigorous. Minimum
are also being used.
weight of lead pipe for this purpose should he Lead
Lead serves admirably for chemical wastes, not alone
Industries Association Standard B or M weight, which
because it resists corrosion by such a variety of modern
may be identified by the Lead Industries' "Seal of
chemicals, but because it also has flexibility that is abso
Approval'', the letters B or M. the diameter and the
lutely essential in any piping system if it is to endure.
manufacturer s name or trade mark stamped on it.
Building movement and settlement are taken up by lead
This pipe weighs:
pipe without damage or strain, an unusual feature in corrosion resistant materials. Furthermore, since joints in lead chemical wastes can be made by lead ''burning", making continuous homogeneous runs of lead pipe, joint troubles may be eliminated.
Inside Diameter
if eight per Runnitig Foot
Inches
Pountls Ounces
1 34
11V'/,i
3 12 3
27
Since solder is corroded by many chemicals that do
Horizontal runs of lead pipe in the
not affect lead all joints in chemical
Providence school were hung in drop
work should be made by lead ''burn
ceilings and vertical runs in brick
ing . In this wav nothing hut durable
chases. Lead stubs coming through
lead is presented to the attack of cor
tire concrete floors were encased in
rosives.
sheet iron sleeves. These are excellent
The architect for Mount Pleasant
practices that should be followed in
High School is Irvin Gorman, of
all piping installations wherever pos
Providence. Plumbing was done bv
sible. as it removes the danger of
C. H. Cronin. Inc., of Boston.
sSSiS
T- . cMLIlvfeSiSFgStsk
Lend laboratory waste pipes sup ported continuously on 2x2 in. angle irttrts. suspended on hangers shaped
to /it the angles.
PHOTOS I1V AIIVKMTSERS STCDIOS
Lead pipe installed in chase in brick trail oi the Mount Pleasant Schmil.
[2]
View showing some of the many lead stubs used to resist corrosice chemi cals and provide flexibility in the
school laboratory plumbing.