Document dYZ4eyNO9REKL23Mr65JV9185
*
RESULTS
Preliminary tests proved techniques customarily employed in anti-biotic sensitivity testing, not applicable in the quantitation of the inhibitory response of niirex, heptachlor, and the PCBs. These toxicants are insoluble in water and the diffusion rates through the
- agar were variable, yielding non-quantitative zones of inhibition. A relative inhibitory effect, however, could be distinguished between the bacterial strains and toxicant levels tested by using the method
described in Table 1.
Of the 85 bacteria tested, 26 demonstrated zones of inhibition to at least one of the test compounds (Table 1). The PCBs were markedly more inhibitory than the organochlorine pesticides. Only 3% of the strains screened showed inhibition at 0.5aig of mirex and heptachlor. This concentration of A r o e l o ^ 1016 and 1242, however, inhibited 31% of'the bacterial strains. Further, o.lmg of Aroclor^ 1016 inhibited 69% of these strains and Aroclox 1242 inhibited 62%.
We attempted to correlate PCS-sensitivity response with biochemical activity or cell composition (Table 2)* PCD-sencitive bac-
i teria were both Gram positive and negative and no morphological correlation was noted. However, a comparison of biochemical activities of sensitive and non-sensitive bacteria tested showed two distinctly different groupings. Amylase and gelatinusc pi*-F-4wet:-So was .s-iiow*. Hy 76% and 86% respectively, of the sensitive strains; hov:evcr, of the total bacterial strains screened, only 33% and 42% of the population;;
v* showed these activities. No other biochemical activity differed
NEV 0256<t9
738904
NEV 025650
738905
Table 2. Comparison of Physiological Activities of PCft-sensitlvo and Non-sensitive Microorganisms
Bacteria
Tested
Urease
Sensitive
Non-Sensitive 13
Production of:
Amylase
Lipase
Gelatinase
76
33 '
86
33 2*3
42
5 6
Nitrate deduction
29 37
^Percentage of cultures tested showing positive reaction, 100 cultures .tested.
Citrate
Gram
Utilization Reaction
43 50
41
distinctly from the non-sensitive bacterial populations. No \
characteristic gran reaction was shown by the PCB-sensitive bacteria
DISCUSSION
S. The sensitivity disc testing procedure commonly, used in clini
cal bacteriology has been successfully applied here as a rapid
method for detecting PCB-sensitive estuarine microorganisms in pure
culture. Although the procedure is qualitative only, it can serve
to eliminate many hours of tedious experimentation involved in the
isolation of suitable test organisms for more detailed examinations.
'* This Dethod has been used previously by investigators to study the
effects of pesticides on grov?th of bacteria (Uiddus/ et al. 1971;
Trudgill^' et al. 1971).. However, no significant response has been
Bhown screening estuarine microbes and chlorinated hydrocarbon
pesticides in this study. Conversely, PCS sensitivity in estuarine
bacteria was quite dramatic (Figure 1) using this method. %
el. (1973) demonstrated no sensitivity to 0.02 tng PCB by
Keil et Coli
InfSC. using the same method on non-marine medium. C*we experiments in-
S'* dicated PCBls stimulate growth of E. coli. No explanation for
(Rot A 1-, t.his difference between stimulation in E. coli.and inhibiton in
-A-
estuarine bacteria,Ihas been determined at this time.
The implications of this inhibition, if wide spread in the
environment, are obvious. The sensitivity of a large number of
heterotrophic bacteria to PCBs nay be of considerable importance
in an estuarine environment. PCCs have been shown to pei-sist in
estuarine sediments in relatively high concentration (9 ppm).
Sediment corcl taken in close proximity to another showed markedly
different concentrations .(0.06-9 ppm) indicating the PCBs are pro-
NEV 02oobl
738906
\.
'
bably absorbed onto particulate organic natter during transport and deposition in estuarine sediments (Butler, 1974). The aforemehtioned concentrations, when considered absorbed onto distinct detrital particles, are not unlike those shown to be inhibitory to hetrotrophic growth in this study. Consequently, PCBs could in hibit the normal turnover of carbon in estuarine sediments by inhibition of specific heterotrophic bacteria attached to organic detritus.
t
v NfcV 025652
738907
Ahmed, M. and D.D. Focht. 70-72 (1973).
REFERENCES
1 Bull. Environ. Contain. Toxicoll10,
I
Bout-quin, A. W., In: The Microbial Degrad. of Oil Pollutants, Eds. Ahearn, D.G. and S.P. Meyers, 237-2A3 (1973).
Butler, P. A. Personal Communication (1974).
Keil, J. E., S. H. Sandifer, C. D. Grber, and L,, E. Priester. 6 i ? 3 7 - r y ; . <??1
Paris, Doris and. David L. Lewis. Residue Reviews 4 5 , 95-124 (1973).
Trudgill, P. W . , Widdus, and J. A. Rees, J. of Gen.. Microbiol. 69,
1-13 (1971).
Ware, G. W. and C. C. Roan, Residue Reviews 33, 15-45 (1970).
tyjLddus, R., P. W. Trudgill, and D. C. Turnell, J. of Gen. Microbiol. 69, 22-31 (1971).
I
NV 025653
738908
!
-3-
IKTRODUCTION Polychlorinated biphenyls (PCB) have been used in a wido variety of industrial and consumer applications over the past 40 years, but it was only recently that evidence began to appear that these materials had been widely dispersed throughout the environ ment, By letter dated February 1$, 1970 the Monsanto Company, sole US producer of PCB's, notified all of its customers of'the potential problem of environmental c o n tamination" by these liquids and recommended "that all possible care should be taken in the application, processing, and effluent disposal of these products to prevent them becoming environmental c o n taminants," Monsant o has begun a program to discontinue sales of PCB'a for use in paints, plasticizers, specialty inks, adhesives, paper coatings and all other open-system applications. The Monsanto Company has declared, however, that it will continue to eell PCB's for closed-systern electrical uses. This decision is a tacit .recognition of the important role that PCB's play in the. safe, reliable, and efficient delivery of electric power from the generating plant to the user. In the spate of published reports and st itements that have appeared in recent years on P C B 's there has been no meaningful exposition of this role of PCB's in electrical equipment - why, where, and how they are used; what alternatives are available; and what the consequences would be to the users of such equipment if PCB's were no longer / available. We hope that this report will provide such an It
738909
N t V 0 ^i>6 bh
-A-' BACKGROUND
PCB's pre used by the electrical industry as components of certain types of transformers ond capacitors The nature and
function of those devices are described in the separate sections of this roport devoted to them. At this point it is sufficient
to say: 1. T r a n s f o r m e r s are 'devices for c o n v e r t i n g e l e c t r i c a l power from one voltage and current level to Another, and the cond u c t i n g parts of these devices must be separated from each other by a suitable insulating 'medium* 2. Capacitors are devices for storing electrical energy through the physical separation of charged metal surfaces by an Insulating medium* Prior to 1930 the most commonly used insulating medium was
mineral oil* The early 1930's saw the commercial development of insulating liquids that were mixtures of synthetic chlorinated aro matic hydrocarbons, principally various polychlorinated biphenyls.
By controlling the composition of these mixtures, the manufacturer
could obtain desired combinations of thermal, chemical and dielectric
properties thAt resulted in Insulating liquids with mu c h greater
oxidation and fire resistance than mineral oils. During the past
AO years these liquids have become widely used in certain types
t
of transformers and capacitors and are recognized as a distinct
class of insulating materials designated by the international
term "askarel". The definition of the term "askarel", the composi
tions' of the liquid that comprise this class of materials, and the
various trademarks by which they, are known commercially are described
in the following section headed "Askarel".
NEV 025655
738910
i *5* The particular a$karel6 used in transformers end capacitors
arc different; so also are the reasons for, and the extent and
consequence* of, their use in these two types of electrical equip-'
meat* However, certain general comments can be made at this point
concerning their use in both types of equipment:
1, Askarel - i n s u l a t e d transformers and capacitors are
delivered to customers as sealed units from w h ich
there is no escape of askarel under normal operation
during their expected lifetimes of 10 to more than 30
y e a r s . H o w e v o r , certain types of equipment failures
can rupture the case and permit the loss of some
askarel to the environment* Such failures occur
at a rate of about 0*02% of the units in service
per y e a r
2* PCH's can get into the environment during the manu-
*
facture, delivery, improper use, maintenance, repair,
and disposal of transformers and capacitors. In
addition to specific control measures instituted
by individual manufacturers and recommended by
them to the equipment users, the A merican National
Standards Institute has established ANSI Committee
C107 on Use and Dispo s a l of Askarel Used in Electrical
Equipment* Its memb e r s h i p s (see Appen d i x 1) is
divided into separate working groups on transformers
end capacitors which will recommend national standards
and procedures n ecessary to prevent the loss of PCB's
to the environment at all stages from equipment
I
manufacture through ultimate disposal.
3* The record of reliable and safe performance that
.insulated transformers and capacitors have
Ntv 02t>o56
738911
I I6 compiled during the past four decades is reflected in the various codes, standards, and regulations th'at now e f f e c tively require or encourage the continued use ofaskarel-insulated equipment in many Applications
l
NEV 025657
738912
7 -7ASKAREL
D r f1n 11Ions *
.
1. A iynthetic nonflammable insulating liquid which, when
decomposed by Che electric arc, evolves only nonflammable gaseous
mixtures* (From the National Electrical Code 1971 and the
American National Standards Institute C-42 series,
"Definitions of Electrical Terms.")
2, Tho term askarel generally describes a w idely used,
broad class of nonflammable synthetic halogenated hydrocarbon
insulating liquids used as electrical insulating media.
Askarels of various compositional types are used. Under
arcing conditions the gases produced, while consisting of p r e domi
nantly non-combustible hydrogen chloride, can yield varying amountB
of combustible gases depending upon the askarel type.
Insulation systems incorporating these askarels and
cellulosic or other organic materials may, when arced, produce
gaseous mixtures which aro moderately flammable*.
(From ASTM (American Society for Testing and
Materials) Method D 2283-71, Port 29, 1971 issue;
will also appear in the 1972 issue of the IEEE
(Institute of Electronic and Electrical Engineers)
o"Guide for Acceptance and M a i ntenance of Transformer
Askarels In Equipment."; Adoption was also recommended
to the International Electrotechnical. Commission by
its Subcommittee 10B (Insulating Liquids Other than
Hydrocarbon Oils) of Committee 10 (Liquid and Caseous
Dielectrics) as reported in item number 9 of minutes m# mai e9 It+fs 1AV, U . v. 1071 \
738913
NcV 02bb3b
6-
Compositlono
'
Polychlorinated biphenyls are derivatives of the hydrocarbon,
biphenyl, which has the chemical formula
Fr o m one to ten
of the hydrogen atoms in a molecule of biphenyl can be replaced
by chlorine atoms, and the chemical identity of the resulting
chlorinated compound depends both-on the number of chlorine atoms
that have been introduced into the molecule and on the specific
sites in the molecular structure at which they are introduced.
The commercial material m a n u f actured by Monsa n t o under its
registered trademark Aroclor consists of mixtures of these specific
chlorinated compounds. They are usually identified by the weight
percent of chlorine in the total mixtures, e.g. Aroclor 1254 c o n
tains 547. chlorine. The Aroclors commonly used in the electrical
Industry are Aroclors' 1260, 1254, and 1242. ,t
Aroclor 1242, used primarily in capacitors, contains about
77. of pentachlorobiphenyls and higher. In September 1971 Monsanto
introduced a new capacitor-grade askarel, Aroclor MCS-1016, which
is essentially Aro c l o r 1242 that has been specially processed to
reduce the content of p e n t a c hlorobiphenyls and higher to less than
0.4%.
.
As a general rule, the nonflammability of liquid PCB's, their
vapors, and their arc-formed gaseous products is greater the higher
the degree of chlorination of the liquid. Studies by Monsanto
suggest that the resistance of PCB's to d e g r a d a t i o n in the environ#
ment may also Increase with Increasing chlorine content. Analytics'
methods for low levels of PCB's (reported in parts per m i l lion or
parts per billion) in marine, aquatic, and wildlife environments
do not always identify the specific compounds that are present,
but in i 1 6 letter of February 19, 1970 to its customers, Monsanto
NtV 025659
738914
-9-
V'*i beer, i jnd ir, the environment end appear to prosent no potential
iroblcv. to the r n v i r o n m e n t . "
iTradem--arks *
!i
Tho following trademarks are used by electrical manufacturers
to designate the askorelc used in their products:
Manufacturer
Trademark
*iv vox Allis-r naimers .
V>*' f.*
Hyvol Chlorextol
'
American Corp.
Abestol
Cornell Dubilier General Electric
Dykanol . Pyranol
y
Kuhlman Electric
Saf-T-Kuhl
Elemex
Sangamo Electric
Diaclor
Wagner Electric
Noflamol
Westinghouse Electric
Inerteen
Toxic and Biological Effects of PCB's
Systematic investigations of the toxic and biological effects
of PCD's have been undertaken only within the past few years, and
the d e s c r i p t i o n and evaluation of the results is beyond the scope
,/.r ' -r re;
Tome Investigators suggest that reports of certain
toxic reactions may be caused by highly poisonous compounds (c.g.
chlorinated dibencofurans) found to be contaminants in some PCB
preparations* In the United States, medical records show that
over a nearly 40~year period the only adverse health effects
experienced by US workers exposed* to P C B r6,either during the
manufacture of these liquids or of electrical equipment containing
these liquids,have been limited to occasional cases of non-chronic
chloracne or other temporary skin lesions or irritations.
* NEV 025660
738915
10 TRANSFORMERS
Defin tioti ,
A transformer is a device for transferring electrical energy from one
alternating current circuit to another by electromagnetic means. It has no
moving parts and performs Its function by linking two electric current-
carrying circuits (the colls, usually copper wire) via a common magnetic
flux carrying-circuit (the core, usually a special grade of iron). A
transformer may be designed to effect a change in voltage or current from
one circuit to the other or simply to obtain electrical energy from one
electrical circuit without making a conductive connection between it and a
second electrical circuit. The transmission of electrical energy from one point to another Is
*
essentially the transmission of a required number of kilovolt-amperes (kva).
By means of transformers the kva's may be generated at a low voltage suitable
for the windings of generators, stepped up to higher voltages and lower
currents suitable for transmission of electricity over long distance wires,
and then at the desired destination stepped down to a lower voltage and
larger current suitable for utilization by electrically powered equipment.
The almost universal use of the alternating current system for the trans
mission and distribution of electrical energy is largely due to this ability
of transformers to link up circuits of different voltages and currents. Thus
the generator, the transmission lines, the secondary distribution system, and
finally the great variety of ultimate loads can each be operated at the voi-
$
tage most suitable to its particular function. Without this unique ability
of the transformer to adapt the circuit voltage to the individual require
ments of the different part6 of the system, the enormous development and
progress in the transmission And distribution of electrical energy during
the past 60 years would not have been possible.
NEV 025661
738916
'? '
*11-
Why Askarels are Used in Transformers
The coile and core of roost transformers are enclosed in sealed metal
tanks that are filled with an Insulating liquid, usually mineral oil. Under
certain conditions of sudden power surges high-current electric arcs are
produced inside the transformer which can generate and ignite flamnable and
explosive gas mixtures formed from the mineral oil and other cellulosic in
sulating components In the transformer.
Because of the nonflammability of liquid askarels, their vapors, and
their arc-formed gaseous products, transformers filled with askarels arc
free of these fire and explosion hazards and may be used in locations where
failures of oil-insulated transformers would present a potential danger to
life and'property. This safety factor is the only advantage that askarel-
insulated transformers have over oil-insulated transformers of the 60me size
and rating. The density of askarels is about 1.7 times that of mineral oil,
so askarcl-insulated transformers are heavier than their oil-filled counter
parts. Askarels themselves are more expensive than mineral oils, and their
solvent characteristics require the use of more expensive insulation compo
nents on the internal parts of the transformer, so the complete units are
more expensive.
As a consequence, askarel-lnsulated transformers have captured only
those market applications (less than 5%, but growing) where considerations
of safety and reliability are paramount. Their use in such applications is
usually required or encouraged by the provisions of electrical codes, fire
underwriting policies, or governmental regulations.
/
Note: Prior to the mid-1950's the liquid used in askarel-lnsulated
transformers was a 50-50 weight mixture of Aroclor 1260 (607, chlorine) with
trichlorobcnzenes; then the benzene component wa6 changed to a mixture of
trl- and tetrachlorbenzcnes; and in 1971 the Aroclor component was changed
to Aroclor 1254 (547. chlorine).
NEV 025662
738917
-12Types n n d A p p lications of Askarol-Insulatod Transformers
Thcro arc two broad classifications of transformers r porrer transformers, which aro used to step up voltages; and distribution transformers, which are used to step down voltogos. The many typos of transformers that are included within these two clesslficatione are listed in Appendix 2, The applications that accompany the listing apply only to those units of a given type that arc m a n u factured with askarel as the insulating liquid. Most units ofthe types listed arc still oil-insulated.
We estimate that the total number of askare1-insulatcd units that have been put into service in the United States since 1932 is 125,000, and virtually all of these units are still in service. The l ifetime-before-failure is often longer than 30 years, and almost all units that do jfail are rebuilt and returned to service. The current production rate of new askarcl-insulated transformers units is about 5,000 per year.
Most of these transformers are located inside public, commer cial, or Industrial buildings; on the roof tops of such buildings; or in close proximity to such buildings, and require no special enclosures other than what are necessary to prevent accidental hazardous mechanical or olectrical contact of persons with the equipment. However, the National Electrical Code does specify vaults for the indoor lnrtallatlon of askarel-insulated transformers j ated more than 35,000 vclts* A s k a r e 1 - insula ted transformers arc, limited by the electrial properties of these liquids to ratings below 69,000 volts.
The amount of askarel used in various types of transformers ranges from 40 to 500 gals, (516 to 6,450 lbs,) with an average of about 235 gals. (3,032 lbs.). During 1968, the last complete "normal" year for the electrical industry, the total amount of
738918
0^5663
13-
.r c H *c used In Crmuiformers was approximately 1.3 million gallons (8,4* thousand tons).
P r o r.o >it A 1 ternatives to Askar c 1-Insu la ted T r a n s f o r m e r s If l'CB's were to be no longer avail a b l e for c l o s e d - s y s t e m
electrical uf es -- as they are no longer a v a i l a b l e from K o n s a n t > for o p e n - s y s t e m a p p l i c a t i o n s . - - vh o t a l t e r n a t i v e s to a s k a r c l - i n s u l a t c d transformers could now be supplied by the clcctricol industry, and what would be the effect upon the user should askarel-insulated
> transformers no longer be a v a i l a b l e eit h e r as new or r e p l ac e m e n t units?
The only present alternatives to a s karcl-insulatcd transformers arc o i l - i n s u l a t e d tra n s f o r m e r s or dry-t y p e tra n s f o r m e r s (either those open to the a t m o s p h e r e or those that arc g a s - f i l l e d and sealed)
A. Oil -ins u l a ted t r a n s f o rmers 1. If one d i s r e g a r d s safety c o n s i d e r a t i o n s , there are no technical reasons why oil-insulated transformers could, not be directly substituted for askarcl-insulatcd t r a n s f o r m e r s . The size of the unit*would be unchanged;
. .. the w e i g h t and cost w o u l d be less, 2, T h e r e are legal restrictions' to such a direct substitution. a. Some local r e g u l a t i o n s (e.g. Chica g o ) prohib i t the use of o i l - i n s u l a t e d units in c e r t a i n l o c a tions whore askarcl-insulated units arc allowed. b. Where o i l - i n s u l a t e d t r a nsformers would not be s p e c i f i c a l l y p r o h i b i t e d os ^on-site replacements.' for askavnl-insulated units, the National .Electrical Code imposes special restrictions upon their mode of installation. Although
738919
Ntv O^^OO^
-14-
35,000 volts must be Installed in vaults,
all oil-insulated transformers require vaults,
except that alternative fire protection arrange
ments arc permitted for units rated not over
600 volts. Assuming that space were available
inside an existing building to accommodate
these special auxiliary safety provisions,
the c o 6 1 of their construction could range
from $5,000 to $50,000 per transformer,
c. Oil-insulated units can be installed outdoors
if they are suitably isolated from flammable
structures or if these structures are suitably
safeguarded against fires originating in the
transformers. The power output must thon
be brought to the point of use inside the
building via cables or insulated buses, and
the cost of cable and bus installation could
* also range from $5,000 to $50,000 per tr&ns-
. former. The outdoor transformer would have
to be of a higher rating than the indoor one
it would replace because of voltage drop and
consequent power losses in the cable or bus
runs,
B Dry-type transformers .
,
*
In most locations, dry-type transformers (either those
open to the atmosphere or those that are gas-filled
and scaled) could not be directly substituted for
a6karel-insulatcd transformers. There are several
restrictions to such a direct substitution: / ? NEV 025665
738920
15
1, The provisions of the National Electrical Code '
arc more stringent for certain classes of dry-
type transformers than for comparable askarcl-
insulated units
2 Present technology is not available for d e s i g n
ing and manufacturing reliable dry-type trans
formers above
KVA and/or 15 KV.
3, The reliability of dry-type transformers is less
than that of comparably rated liquid-insulated
transformers Oil- and askarel-in6ulated units
show much greater resistance to switching and
lightning surges than do dry-type units An EEI survey of failures in network transformer banks
I
showed a 77 per year failure rote for dry-type
units compared to 027 for liquid-insulated
units. Furthermore, liquid-insulated transformers
have a much greater overload capability* Many
liquid-insulated units can sustain a 1007. o v e r
load for 8 hours and a 2007 overload for 2 hours I
These transformers are able to m a i n t a i n continuity
of electrical service during periods of temporary
outage of related equipment* .
A* Some dry-type transformers are larger by 10 to 30%
than comparably rated liquid-insulated units, and
t
most are more expensive.
5* Dry-type transformers are noisier by 5-10 dB than
are liquid-insulated transformers*
6. Bccauso their insides require regular cleaning,
the maintenance costs for open dry-type transformers
are higher than those f.or sealed dry-type transformers
NfcV 0^5660
738921
-16er for: liquid-insulated transformers, which arc also sealed. 7. Open dry-type transformers, which are cheaper . than sealed dry-type transformers, cannot be used in certain corrosive or hazardous atmospheres, c, g. on furnaces or on electrostatic precipitators near hot stacks. Summary 1. For t e c h n i c o l o r legal reasons it would be impossible to replace most askarel-insulated transformers now in service by oil-insulated units of equivalent / rating and reliability without major construction changes that would be required to compensate for the fire and'explosion resistance of the askarelinsulated units, 2, For certain applications and locations, dry-type transformers could replace askarel-insulated trans formers, but with a significant reduction in system reliability.
NEV 025667
738922
*17-
CAPACITORS
Definition t A capacitor is a device that stores electrical energy. It
consists of two metal surfaces or electrodes separated by an insulating m e dium such as air, paper, plastic film, or oil. W h e n a voltage is applied across the electrodes, electrostatic energy is stored in the insulating medium.
In typical industrial capacitors the electrode material is aluminum foil and the Insulating medium or dielectric is paper tissue and/or plastic film,which for m a n y applications is impregnated wi t h a liquid dielectric. A liquid inpregnant is used to fill the voids w i thin the paper or plastic film structure, to fill the voids between sheets, and to contribute to the capacitance or c h a r g e carrying ability of the composite. Voids must be eliminated within capacitors that are to be used above 200-300 volts, which exceeds the dielectric breakdown Btrength of air.
In our definition of transformers we emphasized their importance in the transmission and distribution of electrical power (kilovolt amperes) from the generating plant to the ultimate load. If the load were purely resistive (e.g. an electric heating element) no further m o d i f i c a t i o n of the power supply delivered to it would be required. Other loads (e.g. induction motors) may require that a portion of the k i l o v olt-ampere6 delivered to them be used to p r o vide a magnetizing current, which does not contribute directly to the useful power output of the load. This portion of the total kva delivered to the load is d e signated as reactive kilovolt- a m p e r e s (k/ars). It has been found more economical to produce kvars from total kva's near the point of load rather than near the point of kva generation, and capacitors provide the most efficient way of
738923
KfcV 02566
-18-
cffccting Chis transformacin at Che point of load*
Why Askarols are Used in Capacitors
Prior to 1930 most liquid-filled capacitors were made with
mineral oil. The subsequent subs t i t u t i o n .of asksrels for mineral
oil made possible significant technical improvements in the sise*
reliability* and life of these capacitors.
A * S ize
The single most important property of a' liquid
be used in a' capacitor is its dielectric constant
(the ratio of its ability to 6tore electrostatic
energy relative-to air). The dielectric constant of
* capacitor-grade askarcl (Aroclor 1242) is 5.85 while
that of mineral oil is 2,25. V h e n c a p a c i t o r 'tissue
is impregnated with these liquids the dielectric
t%
f
constant of the paper-liquid composite is 6.1 for
. askarel and 2.9 for mineral oil. Furthermore*
because of the relatively close match between the
dielectric constants of cellulose, (6.6) and askarel (5. 8 5 ) ; it is possible to stress askarel- i m p r e g n a t e d
*
paper to 00-500 volts/rail,, while the stresses that
can be applied to comparable paper-mineral oil capacitors are limited to 300-350 voits/mi*. * The
combined effect of these technical advantages of
askarels has be e n to permit a reduction of capacitor
sizes to less than 147. of what theywere in 1924.
In 1965 a new dielectric system consisting of paper-
polypropylene fllm-askarol was introduced w i ! stress capability up to 900 volts/mil. overall. r<
favorable 6tress distributions* the ability
askarel
....... -
increase, the dielectric strength of polypropylene
NtV 0 >669
738924
-19-
is partly responsible for this improvement.
Reliability and life
Asknrcls arc thermally and oxida t i v e l y more stable
than mineral oils, and discharges, which can occur
in capacitors,' are less likely to generate gases
from askarel6 than from mineral oils. The chemical
stability of askarels in the presence of capacitor
tissue and plastic films and the favora !'- .
discributions between solid and liquid referred to
above have made it possible .to design low-cost
capacitors with a life expectancy of more than 10
, years life In lighting applications and more than
20 years in electric utility application. In
'
each application the first-year failure rates are
less than 0.27. This level of life and reliability
had not been achieved prior to the introduction of
askarels. Furthermore, the non-flammability of
askarels is greater than that of mineral oil, which
reduces the fire hazard that might otherwise
accompany those failures that result in' rupture of
the case.
W h e reas the transformer m a n u f acturer has had to
essentially "design around" the properties of'
askarels in order to be able to t a k e .advantage of
the safety factor that they impart to his equipment,
the capacitor m a n u f acturer has been able to "design
with" the properties of askarels and obtain significant
technical improvements along w i t h the imp- cd saf-ty
* factor. As a.result askarels have v i r t v ' -
j \nted
mineral oils in more than 90% of the power and industrial
NV 025070
738925
I -20* N o t e ; Prior to 1952 the liquid used in askarel-impregnated capacitors was Aroclor 125/4 (54% chlorine); it was then replaced by Aroclor 1242 (42% chlorine), which has better electrical properties; and as noted in the. "Askarel" section, in September 1971 Monsan t o Introduced a new capacitor-grade askarel, Aroclor KCS-1016, which . is a modified Aroclor 1242, Unlike askarcl-insulated transformers, the liquid in a skarel-impregnated capacitors contains only Aroclors
and does not contain added bhlcrobenzencs. T ypes and Applications of A s k a r e 1-impregnated Capacitors
The principal types of askarel-impregnated capacitors and
their applications arc described in Appendix 3* Almost 80 million such capacitors are manufactured annually, most of them for first time use. Unlike transformers, capacitors are not rebuilt and returned to service after failure. They arc disposed of (see "Background" section, item concerning ANSI Committc C107) and replaced by new capacitors.
Capacitors used in lighting and air conditioning applications 0,09
contain 0.005 to *$9 gals. (0,05 to 1,0 lbs.) of askarel per unit. The largest power capacitors' contain about 6,7 gals (77 lbs,) of Askarel, The most popular size contains about 3.1 (36 lbs.) The National Electrical Code requires that any installation of capacitors In which any single unit contains more than 3 gallons of co mbustible liquid shall be in a vault like t'.iat required for transformers. .During 1968, the last complete,"normal" year for the electrical industry, the total amount of PCB's used in capacitors was approximately 14.4 thousand tons,
I <
..... .
NEV 025671
738926
1*) { j; ( i) (: AJ to nvn I v r a to A h r e 1 - T.mp ro g ti ;it e d C a p a c i t o r s
If PCI)* were to be no longer available for c loscd-sy r.tcm e l ectrical uses -- as they are no longer a vailable from M o n s a n t o for o p e n - s y s t e m 'n p p l i cations -- what alte r n a t i v e s to a s k a r o l - i m p r e g n a ted capacitors could now be supplied by the electrical Industry, and
what would be the effect upon the user should asliarcl-imprcgnatcd
`c a p a citors no longer be a v a ilable either as new or r e p l a c e m e n t units?
Possible a l t e r natives to a s k n r c l - i m p r e g n a t e d c a p a c i t o r s are
c a p a c i t o r r, impregnated wi t h m i n e r a l oil, tor c a p a c i t o r s impregnated
with certain other liquids,
A. Mineral Oil Replacement of askarels by mineral oil would essentially return c apacitor t e c h n o l o g y to its prc-1932 level. Some specific consequences of such a replacement would be: 1, S a f e t y . None of the possible liquid a l t e r n a t i v e s
s
to askarels arc nonflammable, and a fire hazard would be created by any capacitor failures that were a c c o mpanied .by rupture of the case. Pres e n t l y the use of capacitors containing flammable liquid is governed by the National E l e c t r i c a l Code 'Arti c l e s
A CO and 501. 2- S i z e and C o s t . A few specific examples vi.ll illustrate
the size and cost penalties associated with a switch from ask a r c l to m i n e r a l oil in ca p a c i t o r s . The most popular sized power c a p a c i t o r s today arc rated at 200 KVAK, If mineral oil were substituted fov
Askavcl the volume of the c a p a c i t o r v/oultl be
Ufc.V
quadrupled and the direct labor and material costs
a s sociate d with itr. m a n u f a c t u r e wo u l d increase by 70%, Tod ay power capa c i t o r s arc available in A00 :cv.\K
738927
-22-
; KVAR because of increased heat dissipation problems
f
with increased volume. In addition to increases in
direct corte, the power capacitor Industry would
face increased capital expenses estimated at
'
$2,000,000 to provide the increased volume of
material at p r o j e c t e d .KVAR requirements.
Steel companies faced with increased size, co6t and flammability of capacitor banki^'/. indue.: jcheating furnaces would probably not install new
.Induction heating Capability. Utilities would
have difficulty with substAtion*size Ln crowded
urban areas. An increase in the size of capacitors
for air conditioning would not be critical.
In lighting applications a 3,75/.075 uf 540 VAC
rating for high output applications is typical.
If mineral oil were substituted for ashctrel, the.
capacitor would be 71% larger and materials would
cost 46% more* Lamp ballast manufacturers would
have to increase the size of the ballast to a c c o m m o
date the larger capacitor. This would change the
thermal performance of the unit and require U.L,
approval of new ballast designs* Lighting fixture
manufacturer* would also face redesign costs to
take larger allasts. Reliability. Users of capacitors in all application
areas. have come to expect long life and very low
initial failure rates. The present performance star
dards have been achieved after many ye
of fi- '<1.
testing and accelerated testing by an- `
and users* The reliability of designs containing
I
567
738928
-23-
minerol oil in many applications would be uncertain. Available records show that capacitor reliability prior to tho availability of askarcl was only a fraction of whnt it is today. A. Replacement M a r k e t . The implications of changes in capacitor size hav.e been, d iscussed in terms of new designs. In each major application area some capacitors are sold for replacement business. Power and induction heating capacitors are generally installed in racks of a few to thousands of c a p a citors. It would not be possible to make simple substitutions for failed capacitors while m a i n taining the system rating. In air conditioners replacement of failed c a p a citors might be as simple as installation of new brackets. On the other hand,' tight designs might not take a larger capacitor at all. lighting systems would be seriously affected by Increases in capacitor siae. Larger replacement ballasts would not fit into existing fixtures without altered mounting arrangements. It is possible that space requirements would force complete replacement of lighting fixtures for the want of a replacement ballast.
t 5. Material S o u r c e s . Mineral Oil is currently used
in a relatively small number of specialty capaci tors. In this country there is a single source of capacitor-grade mineral oil with limited facilities for acid refining of crudes from a single oil fxold. Increased demand -ould require
738929
NtV
-2A-
exponded facilities and investment and considerable
development in defining technical requirements for
capacitor-grade mineral oil.
Efficient use of. mineral oil in capacitor designs
would require higher density capacitor tissue
than is currently produced in this country, ^t
the least this would require extensive paper
machine modification. Capacitor winding techniques
and machino6 would need to be developed for winding
tighter rolls.
B* Other Liquids
. 1, Castor 0 1 1 The dielectric constant of castor
oil is 4.5 and this material is useful as an
impregnant in D.C. energy storage capacitors.
However, A.C. capacitors filled with this liquid
have relatively 6hort lives and are not very stable
under A,Cm discharges and in the presence of water
derivable from the-cellulosic paper.
2* Dibutyl s e b a c n t c . This ester is especially useful
in high frequency parallel plate capacitors because
of its low, flat loss characteristics over a broad
frequency range.' In this type of c o n s t ruction the
liquid is the sole dielectric material. W h e n used
in c o n junction with paper, this esfsr is also
.
unstable
*
3 .S..i-l-i-c-one Fluids These materials have a dielectric constant of 27 and would generally be subject to
.the same disadvantages as m ineral oil'
vH ^o
J
C Alternative Designs In addition to liquid dielectric substitutes, olternatives
738930
-25/ to the paper-liquid dielectric might be considered. These would involve the use of plastic film coated with aluminum foil or vapor-deposited aluminum as electrodes. Since the free volume of the system is less than that of paper the capacitance of the system is les6 dependent on the dielectric constant of the liquid and the stress distribution between M;e plar^ic films and low dielectric constant liquids is moi* closely balanced. Such dielectric systems are difficult to construct completely free of voids. It is expected that several years will be required to achieve the required level of reliability in such dielectric systems
NEV 025676 6 rs
738931
-/. u -
l'OSSl l'.l.K DKVP.T.OPHKNT O)' NEW NSUI.AT m : 1.TQUJ DS
The cose o.f asknrel liquids is shout: $2.00 pci* gallon, compared to about
$0.30 per gallon for mineral oil. Thus, long before there were any environ
mental concerns about rCB's there was a strong economic incentive to find
other less-expensive insulating liquids with the d'esirnblo characteriseics
of nsknrols. Since the 1930's, at least 10 major chemical or electrical
companies have invested large amounts of time and money in this search, all
with no success. There ore today no fluids that can be used as ono-for-one
replacements for PCB's.
The continued search for new fluids would probably start with fluorochemicals.
Fluorochcmicals arc nonflammable, nbntoxic, and as far as is presently known
represent no environmental hazard. High-boiling fluorochcmicals might thus
be potential replacements for ?CB's. Considerable laboratory study, over at
* least a one-year period, of the physical, chemical, and dielectric properties
of these materials would be required in order to identify specific candidate
materials.
At least another year would be required to develop a finished product based
upon a fluorochcmical. On one hand, the physical and dielectric properties would
certainly be sufficiently different so that substantial engineering redesign by
electrical manufacturers would be required to accommodate a fluorochcmical. On
the other hnnd a one-year lead time is needed to construct a chemical plant to
produce the identified fluorochcmical in the millions of pounds that would
be required per year.
Furthermore, a significan: program of environ
mental testing would be needed to ensure that the new material was.indeed not an ecological hazard. The foregoing arc all h i g h l y o p t i m i s t i c tine estimate:
The cost of manufacturing fluorochcmicals is inherently high. Prices of
high-boiling liquids are $10 - 15 per pound, or*higher. At best one would .hope
NEV 025677
738932
-t fm I
..
that in sufficient volume the price might approach that of Teflon, currently $3 U per pound. Even this optimistic figure is approximately twenty times the cost of PCB's, and since the value of PCB in.a transformer is roughly ono-tenth the total value of the transformer, the total cost of a fluorochcmical-lnsulated transformer would be at least three times that of an equivalent askarel unit
NV 025678 738933
Appendix 1
Membership of ANSI Committee C107 on Use and Disposal of Askarel Used in Electrical Equipment
Number of Representatives 2 2 1 1 1
1 2 1 1 5 2
2
1' 1
Organisation Represented Department of the Army Environmental Protection Agency U.S, Department of Agriculture Tennessee Valley Authority General Services Administration National Bureau of Standards Certified Ballast Manufacturers Association Edison Electric institute Institute of Electronic & Electrical Engineers National Electrical Manufacturers Association Monsanto Company Commercial Waste Disposal Companies Engineering Consulting Firm Capacitor Manufacturer Serving as an independent Member
NEV 025679 738934
I
Appendix 2
Types of Askarcl-Insulated Transformers
# A. Distribution Transformers
'
`
1. Network (up to 2500 KVA)
2. Single- and three-phase (up to 2500 KVA)
3. Pole-mounted and station (up to 500 KVA)
The application of these transformers in power distribution systems
places a great premium upon their reliability and high overload capability
(which they share with comparable oil-insulated units): such as 100%
overload for 8 hours and 200% overload for 2. hours.
.A. Precipitation (high voltage DC)
These transformers are part of the power supply for electrostatic
precipitators, which are gaining increasing use in preventing air
pollution by particulate matter. They are generally installed close
to hot gas stacks in an atmosphere that would be a fire hazard to
oil-insulated transformers and a corrosion hazard to open dry-type
transformers. Sealed dry-type transformers are impractical for high
voltage DC,
.*
B. Power Transformers
1. Secondary substation
a. Load center units
b. Secondary substation generation units
c. Switchboard units
,
d. Integral units
e. Motor control units
Theso5aoifrisc the largest group of askarel-insu'.ated transformers, %
and they find widespread application in the automobile paper
i NEV 025&80
738935
-30-
chemical, textile, steel, nonferrous metal, cement, mining, and
petroleum industries. They are used In commercial and public
buildings, such as schools and hospitals; in defense and
nuclear energy installations.; and by private and public
utilities* 2. Master unit substation
3. Primary unit substation A. Limited ampere substation
*
5. Industrial furnace
. These transformers are used in the hot, dirty atmosphere In
proximity to glass melting and induction furnaces, which require
high current, low voltage power supplies (more than 2300 KVA at
no more than 13.8 KV). Existing technology does not permit construc
tion of scaled dry-type transformers for these power ratings,
6. Rectifier
These transformers are used for large rolling mills and DC
industrial power supplies, and arc covered by the same comments
given for industrial furnace'transformers.
^
7. Transportation
a. Third rail
These transformers are used for rapid transit systems, and are
basically serving a rectifier function.
b. Locomotive
'*
Prior to 1932, all on-board transformers were open dry-type.
Because of problems with them, railroads went to askarel-lnsulated
transformers. The changes in locomotive design since the 1930's
would not now accomodate open dry-type transformers as replacements
NEV 025681
738936
-31-
for askarel units. A recent trend has been to replace askarcl by oil units, and this will continue unless new DOT regulations require nonflammability. 8. Multiple-unit car (MU) These transformers are mounted under the flat-bed of passenger cars. They ride along in this location, about 8 inches" ~ the r.<T, *t . speeds up to 150 mph. The transformer must be ruggedly built to with stand the impact of flying debris and constant vibration. Power to the cars is brought In through an overhead catenary and is fed to the underside of the car where the transformer, controls, and propulsion equipment are located. Present voltage is 11 KV, but new electrification is expected to be 25.XV. Space and weight are critical in this application. There are only about 33 inches above the'rail. The width of the trainsfo mer is limited by the width of the car. Only oil- or askarel-insulated units would provide the required performance levels in the space available. As with locomotive application* present DOT regulations do not restrict the use of flammable liquids, and the use of askarel units has been dictated largely by the economic considerations of fire Insurance rates.
NEV 025682
738937
0*1 -
./ /
.
, Appendix 3
.
'
Typco of AsUarcl-Insulatcd Capacitors
.*
*
A. tilp.h Voltflfte Power
Generally AC capacitors are used to improve the power factor of
a circuit Powor factor is the ratio of true power in watts to the
apparent power as obtained by multiplying the current flowing to the
load by the circuit voltage. The power factor correction can be made
directly at the load or at utility substations. In the latter case
high.voltage units will be designed for 4,800 to 13,800 volt service*
To the utility engineer the use of capacitors is* purely a matter of
econdmics. The main benefits that result from the use of capacitors
are
1. Reduction of losses associated with the delivery of eleetrl*
cal power to the point of use*
2. Reduction of the investment required in equipment for de-
llvering electrical power to the point of use, which may be
broken down into:
-
a. Reduction of current for the same kilowatt load.
b. . Reduction of the kva rating of equipment required to
handle the same kilowatt load.
c. Reduction of the voltage drop for a given kilowatt load.
d. Control of. delivered voltage if the capacitor kva is
varied,
*
Electric utilities also use capacitor banks in series with dlstri>
bution circuits to improve voltage regulation. High voltage utility
capacitors', low voltage power capacitors, and lnductior heating
capacitors are manufactured at the rate of 200,000 per year, about 2 to
3% of which are for replacements; the balance are for new installations.
-
NEV 025083
738938
-33-
B. Low Voltage Power
Capacitors installed in industrial plants at the demand site (typi
cally large motors and welders) are designed for 230 to 575 volt service
Capacitors installed near the loads are the.most efficient way to supply
the magnetizing current to produce the flux necessary for the operation
of inductive devices. Rates for the sale of power are generally struc
tured to encourage power factor correction at the site eliminating the
need for the electric utility to transmit both power-producing current
and magnetizing current all the way from the generator to the plant site.
The same considerations apply to induction heating applications the
principal difference being that capacitors for this rapidly growing appli
cation are designed for operation at 960 to 9600 Hz.
C. Lighting
Capacitors improve the efficiency of lighting syrterns. A fluorescent
or mercury vapor lamp can be ballasted without the use of a capacitor but
the power factor of the lighting system would then be in the range of 50
to 60%. For commercial or industrial lighting with either fluorescent or
high intensity discharge lamps, the use of a capacitor in the circuit
*
provides part of the lamp ballasting and brings system power factor into
the range of 90 to 95%. The current market for these applications is
about 44,000,000 units annually of which about 10% are estimated to be
replacement ballasts. D. Air Conditioning
I
As in the lighting applications, the capacitor improves system effi
ciency. Air conditioners could be made to operate without capacitors,
as do home refrigerators, but because of the higher capacity required for current
air conditioners, the resultant line/would virtually eliminate home "plug
ins" and would still further overburden a seriously threatened national
.. '
NtV 025684
738939
-34 -
power network. Almost all air conditioner pump motors are of the split-
winding type on which the capacitor provides phase differential for the
so-called start winding,
thus delivering good starting torque. The
proper 6ize capacitor permits high (907. ) power factor after 6tart-up,
The current market for this application is about 12,000,000 units an
nually, with about 57. of these estimated to be for replacement usage,
Ei Industrial Electronics
This market category is a catchall covering many varied applications,
two important ones being motor run and power supply applications. Motor
run applications are for pumps, fans, and farm feed equipment, and do
not differ significantly from air conditioning applications. The power
supply market uses capacitors principally to provide high power factor,
but through careful design the capacitor can also provide wave shaping
where desired. The market is estimated at 23,000,000 units per year
with no estimate as to the relative 6ize of the replacement market.
NEV 025685 738940
9R9S70 A3N
V I
!
!*
rV*
9
I.
L LSO it*
X0
* t:
ri
M7) 2"
r*. *
^> *< -k >-
ur A .: `
c< 1
9r
S
** *t
is j y*
i
S
*
,\
-
sr
j
ir
r- Z .
[*> *. >* #- ?* >
rs (/I <> ^ r
?i #
*%r->r
i
J. KJ>
n W` '
,v
} $
<* H 7 V>' >
\' -c
? VS /
.. i
i
> r*
iA
r*
1r *
o
*
c
A
5
P
> <r*r
<
A
738941
.- i4 l* lu, 9J
> '*
*\ r? ! :1 !
-r r,
IX A
r fr
"
'
'a.
1 A
, !
:.>
f __;*__
_A',.44
S1!.*%s*
9 n
X . 4 -
y 1 \v I
d
* `1
*7
V
<
1^ `* ** a -
' > ^i
f%
. i i-
4 1 `^ >
1 < r V. 1
! 5* '
"}
'
? ^. f4 4k
2^
r r:
5*
> 5 .i r 53 *%n V. j
4 *V c
* T
_ V*. r? ,r i *L V--
Ti i
:r }
;
-p
r^ 5*
4 P'
^ fIk ^ V
f-
73 r
*? Vk ^
>Y ?2 4L! 1!
?! VA
L0
\ rx
\.
C-l y tP >
t*
f >
w
<3 0
jr V*> w
3 -f
\5 1 r*
t
1 1
'Ll\
___
\ 9> li
?
i
9 !jC n c
3: ;
1A C
/ `* %
1*
/e
ir X A
*
i: * r
i
!4 .
!'/
:<
V
i
if. ' i |p
;
9
i 5
iS a
L,, p \t
s/r' 1? s < ` ' i
r
;
sr
r
* 4
?5 ?f ' .
93
ii 0
> TS 4
J;
^ W?i
r2
>- 3 ?*
* r * ? ? V.
4 ! ___ _.
M >: C / f* >^
4r
<n
i\ :: -D
22 u ; j
M 5M .
n
i
V r
t'
\4 a -.-r
1 .'5 \
i
i
X r
1*%
tV
y;
V , k/ ,
P 9
J ! t* V t iU} A o O : o
>J ?
i* * i
!1
1
!
o
9 9
; i* 1f
>1 ; *1 itO .
i !
j
i
? J (4
W i ?) *3
-- -
y 6
V M
--
; X:
Vu XV
N. 5
^ \ r*
\
--
r
X
A
S-V
0
ST oo
xl
I V
1?.
y 0 LV (V y
, t
L
X .c
>'0
9
<
----
i ii
1 V
X:>-
J
c
x X '2 u*
> \
r *4
!* n *e
i1
*
X
>O * o
f
\
0 V
% /r
Ut '
1f
XC ?s
m X!
.y 1 > fJ ;* i
j !r i `Ur *
O ti * ,s>
>1 ** il \ !
*
li N
N Kl 1
b
-
!X' -i *l * !**
v* o o
? tv 7
** P
T
V V
i
^
^ -J -+
M
H
'* !
w W c -
> >* i !
* V
1
9 J
r s V
f * u "o
ij
': \
: 'J ` :*
3
i
?J LI Vk ,L1
i #j a (j
< lo
X *
**4 ,.9
*1 9 t i
i*
is
U )* o i
`
I f *M if f
>
n
* t 1V V
--
1
1 *
k 1* r
i-4 - r 1i [{! ;4 j ! f
;;
j
\<s f* \ , o\
--
*v IV X V J S\
\V ls*> \
X$
V * X
V 0
#
19 9
*1 9 y
9 y9
o
l** 'I
!
!k y
jo3 V
W
9
9 Zk
\ 9
\ * a\ t J\
! l*
f
\V ?
u\
\ P
M\ 4\
H
__ _. 4 . 1l-j p K o
0 0
0 o
\ :
?\
\%
XV \
Ul 1i
4
! '
X
v <
1i <i
>1 y
ii
i
1
!S h rW 1
w o
kJ K
' 1
V iA# *y*
i2
1? !{<
i
M .-A
i
9 tv
W* u
>
Vu > \ ['l >1 \ j
\. -t-
0 ya \
2 X
/ X
A >
\ 0A u*
-\
\*
U c
pX
\ 6 \
Oi \
c
<n >N #>
Xs e X /
V* -V X
X5
XT* \ 3
X o'o. \ -1
1--
X___;_ l
(A
a
NfcV 2 5 7
**
738942
738943
009470 A3N
Z rr. <
o
rsj
U!
O-
OD
O
CO
>i*-oi
*<}
s? VN
i
x>
738944
ct r*
Z