American Society of Heating and Ventilating Engineers Guide, 1928
Chapter XIV--Automatic Heat Control
Fig. S. An Arrangement for Tempered Air with Warm Air Furnaces
artificial lights, the problem will be to keep cool rather than warm, and the room thermostat, in a temperature above that at which it is set to operate, will ordinarily shut off all heat, while the fan will deliver unheated air. In a room at 80 deg. the admission of air colder than about 70 deg. (depending on the point of entry) will cause discomfort from drafts.
The prevention of this unfortunate situation is achieved by installing two ther mostats, one in the room and one' in the air duct, the room thermostat serving merely to admit air to the duct thermostat. When the room is cool, both thermostats will be closed and warm air will enter. When the room temperature gets to the critical point of the room thermostat, the room thermostat opens, passing air to the duct ther mostat. The duct thermostat may be set to permit this air to pass on by and to function at the heater to reduce the temperature, but will be set so that when the duct tempera ture lowers to the critical point of the duct thermostat, the latter takes control and prevents the entering air from getting so cool as to cause drafts.
Unit Ventilating Systems
These individual fan-radiator units are usually equipped with highly efficient radiators in one section, having one supply and one return valve, and depend on nicely adjusted dampers for mixing the heated air with unheated air to gain a desirable admission temperature. It is usually not wise to operate the steam supply valves with thermostats, since freezing may occur, and it is usually not practicable to install in these units separate tempering heaters with separate automatic control. The approved procedure is. to use an intermediate or slow acting room ther mostat for operating the mixing dampers in the unit. This thermostat
Fig. 7. Thermostat on an Instantaneous Water Heater and Storage Tank
Note.--Controlling supply of steam to an instantaneous water heater and storage tank. Control of steam to heater maintained by temperature of water in tank.
may also operate the radiator valves if a vacuum system of steam circu lation is provided. If the steam circulation is single-pipe, or any kind of gravity type, the direct radiators should have positive thermostats. ;
The fresh air intakes to the units should be closed when the building is unoccupied, and the human operator cannot be trusted, especiallyjin an installation-comprising many units, to do this by manual means at each unit. An excellent recourse is to handle these cold air intake dampers by a compressed air line running from the control point, say in the boiler room, which by manual opening of a valve permits air to pass to all of the units and to open all of the inlet dampers, the arrangement being such
Fig. 6. Thermostat on Storage Water Heater
Nctfe.--Connected to special heavy duty water heater and regulating temperature of water by flow of
steam In coils. Flow of steam controlled by temperature of water to be heated.
a
248
Fig. 8. Thermostat on an Open Feed Water Heater
Note.--Regulating temperature of feed water by injection of live steam to supplement exhaust steam, controlled from temperature of feed water.
249