Document dY2m2xpxvwLoYoOQM9VoZEXqG

526 CHAPTER 28 1946 Guide -The dotted line,on the chart illustrates its use in solving a typical example. In using the chart, start with- the scale at the left bottom margin representing the given number of hours of operation per year; then proceed vertically to the line representing the given value of heat;, thence horizontally to the right, to the line representing the given tem perature difference; thence vertically to the line representing the con ductivity of the given material; thence horizontally, to the left, to the line representing the given discount on that material; thence vertically to the curve representing the required per cent return on the investment; thence horizontally to the right, to the curve representing the given pipe size; thence vertically to-the scale at the top right margin where the economical thickness may be.read off directly. UNDERGROUND PIPE INSULATION Underground steam distribution lines are carried in protective struc tures of various types, sizes and shapes (See Chapter 29). Detailed data Table 10. Thicknesses of Pipe Insulation Ordinarily Used Indoors 8tbam Pbsbsurb Pbig or Condition 0 to 25 25 to 100 100 to 200 . Low Superheat Medium Superheat High Superheat Stsam Tekperatubr Fahrenheit Degrees 212 to 267 267 to 338 338 to 388 388 to 500 500 to 600 600 to 700 Thickness o* Insulation Pipes Larger Inao 4 Cl 1 in. l}i in.' 2 in. Wg in. 3 in. 3$* in. Pipes 2 In. to 4 In. 1 in. 1 in. . '1^ in. 2 in. 2^3 in. 3'in. ` Pipes H In to 1H In. 1 in. ' 1 in. 1 in. 1}4 in. . 2 in. 2 in. All piping located outdoors or exposed to weather is ordinarily insulated to a thickness H in. greater than shown in this table, and covered with a waterproof jacket. on commonly used forms of tunnels and conduit systems have been published by the National District Heating Association 2. Pipes in tunnels are covered with sectional insulation to provide maximum thermal efficiency and are also finished with good mechanical, protection in the form of metal or waterproofing membrane outer jackets. In some instances, where actual submersion of hot lines may occur it has , been found good practice to firmly secure the covering with corrosion resistant wire, then sew on. a wire-inserted asbestos fabric jacket with wire. , This jacket is porous. -The principle of withstanding submersion is that water may enter as water, then actually boil at the pipe surfaces and escape as steam without rupturing the insulation or jacket. Conduit systems are in more general use than tunnels. Pipes carried in conduits may be insulated with sectional insulation; however, the more usual practice is to fill the entire section of the conduit around the pipes withhigh quality, loose insulating material. The insulation must be kept dry at all times, and for this purpose effective waterproofing membranes enclose the insulation. A drainage system is also provided to divert water which may tend to enter the conduit. . The economical thickness of insulation for underground, work is difficult to determine accurately due to the many variables which, have to be considered. As a result of theories' previously.developed, together with Pipe Insulation 527 (L. B., McMillan,'Proc, National District Heating Association, Vol. 18,- p. 138). Fig. 6. Chart for Determining Economical Thickness of Pipe Insulation