Document dVN0Rg8Bd5mn1GEajrrqX3B9
. Monsanto Chemical Company W. 0. KRUMMRICH PLANT LABORATORY
DATE ISSUED
1/6/61 WWffWTA'V-----------
j rAOK
1 l 2 1 10.620
APPROVED ST
STANDARD ANALYTICAU METHOD
DWJ "ATTACHMENT*
WGK Method 10.100
RFS
PRODUcf
Aroolors, PyranolB. Trl-Chlorobenzene and Trl-TetranhTorohenaena Blends
Water_______________________________ :________ __________________.--
I | UPEREDEt METHOD.
IUUED OH 3/9/53
TMI* POEM g-j REV|||U INSTRUCTIONS
_______ '
SCOPE
Bile method Is used to determine the water content In transformer and capacitor fluids and their components. The water Is titrated with standardised Karl Fischer reagent to an electrometric "Dead . Stop" endpoint.
EQUIPMENT AND REAGENTS
a. Refer to General Method No. 7, WGK Method No. 10/100 for neoessary equipment and reagents.
SAFETY
Aroclors, Pyranols, Tri-Chlorobenzene and Trl-Tetrachlorobenzene blends are Irritating to the skin. Hie vapors of the hot materials are Irritating to the eyes and upper respiratory system. If accidental contact Is made with the eyes, flush 1mmediately with large quantities of water and get Immediate medical attention. Exercise caution to avoid possible thermal burns through contact with hot equipment.
The solvents used In this determination are both toxic and flam mable. Proper precautions should be exercised to keep them off the skin and away from sources of Ignition. Karl Fischer reagent Is toxlo and can be absorbed through the skin. If It comes In contact with the skin. Immediately wash the area ytith soap and water.
DETERMINATION
.
1. Determine the water content of the material atsoordlng to Oeneral Method No. 7 with the following modifications)
a. Plaoe the solvents. In the proportions Indicated below. Into the titration flask: >
0079622
TOWOLDMONOQ56996
Product: Aroclo'rs, Pyranols, Tri-Chloro benzene and Trl-Tetrachlorobenzene Blends
Test: Water
Method No. 10,620 Page 2 of 2 pages
Material
Benzene
Methanol
Pyranol 1488
Pyranol 1467 Pyranol 1470
Pyranol 1481 Inerteen PPO Trl-Tetrachlorobenzene Blends All Aroclors
100 ml. 100 ml. 100 ml.
100 ml. 100 ml. 100 ml. 110 ml.
200 ml. 200 ml. 200 ml.
200 ml. 200 ml. 200 ml. 190 ml.
b. Weigh, to 0.05 g., by difference, on a beam balance a 100 ( 10) g. sample into the "blanked" solvent and allow
the material in the flask to mix thoroughly.
CALCULATION
$ Water = mml. K. F. reagent x K. F. factor x 100 1 sample weight
Report results to the nearest 0.0005$.
Duplicate results should agree within 0.0005$ or the results must be rechecked.
DISCUSSION
No precision data has been compiled on this method but experience shows the results can be duplicated within t 0.00025$.
"The information contained herein is, to our best knowledge, aoouratej but all recommendations or suggestions are made without guarantee, since the conditions of use are beyond our control. Monsanto disclaims any liability for loss or damage inourred
in connection with the use of the above.1
0 0 7962 3
TOWOLDMONOQ56997