Document dQrp6B5geBLLM6eGMKM5Mj1a9

The enclosed tabulation records THERMIXOt FR-2 sacrole results from your TtLI^KIIJGL heat transfer system* These results have been previously reported, but I thought you might b particularly Interested In the tabulation of the results, which Is the format we are going to in the future for reporting sample results, I trust that the surging problem in the system expansion tank which you had recently is now corrected and that the system Is operating satisfactorily. Viscosity and hlboilcr levels of the most recent sample indicate negligible fluid decomposition. The acid number is increasedsomewhat over new. fluid specification of 0.01 maximum but is below our arbitrarily established limit of 0.2, The moisture content is increased above our arbitrary limit of 150 PFH, and X would suggest a periodic venting of hot fluid from the discharge side of the pump or heater to the vapor space of the expansion tank. If all vapor lines are unplugged in the system, come degree of venting is provided by the cold seal trap and steam separator provided by American Hydrothcra. vie have found lliafc directly venting a hot etreata of liquid to the vapor space of the expansion tank provides a more positive means of reducing moisture and acid number content. 4 45601 OS'N STLCOPCB4088131 ; / Hr. Lee page y Page Two f November 8, 19$7 1 If we can be of any further assistance, please feel free to contact our Wilmington Office, or call us direct in >t# Louis. . Very truly yours. DERilh Enclosures t>one Id . Roush Engineering Specialist Functional Fluids DSW 435071 STLCOPCB4088132