Document dQJ4bZwex2je2v6YG4aOKBGkG
838
CHAPTER 37 .
1952 Guide
Fio. 6. Performance Data fob Typical Commercial Solid Adsorbent
Dehumidifier .
1085 grains per minute
..
Then q = 17-6' g|:ait{8 per pound = 616 " air Per minute minimum that must be
supplied to the room to maintain 30 F dew-point.
Note that this figure represents the minimum requirement for the arbitrary condi tions set forth and that in practice, safety margins should be added to the outside air percentage figure and to the calculated internal moisture gain.
VAPOR TRANSFER TO DEHUMIDIFIED SPACE
The walls enclosing a dehumidified space are subjected to a vapor pres sure differential. The pressure, of the vapor outside'the, walls tends to force moisture through the walls into the dehumidified zone of relatively low vapor pressure. As this'process can: be an unnecessary load on-the dehumidifyirig equipment, provisions should be made for keeping the vapor transfer to a minimum. Also, if the space is cooled below the ambient dew-point, there is a possibility that condensation may occur within the walls, unless vapor transfer is controlled. For these reasons a vapor bar rier should be located within the wall construction as near to the high vapor pressure side as feasible. To be effective, a barrier must be continuous and should be so located within the structure that it wiil be protected from rupture. (See section on Water Vapor and Condensation, Chapter 9.)
CHAPTER 38
Automatic control
Basic Types of Control, Types of Controllers, Actuating Devices, Actuated Controls, Residential Control Systems, Zone Control, Automatic Control Application, Control for Central Fan Systems, District Heating Control, Panel Heating Control, Indicating and Recording Equipment
THE function of atUomatic control, as applied to the heating, ventilat ing and air conditioning industry, may be broadly subdivided into the maintenance of temperature, humidity, and pressure, within predetermined ranges. It automatically coordinates the operation of the various con trolled devices in proper sequence to produce the desired result.
BASIC TYPES OF CONTROL
Available automatic control equipment may be divided into four main groups depending on the primary source of power:
1. A self-actuated regulator is one in which all the energy necessary to operate a
valve or damper motor is supplied by the responsive element.or bulb. Temperature
changes at the bulb result in pressure changes of an enclosed fluid which transmits
them directly, to the valve or damper motor. Instruments of this type are available
either with a rigid bulb or with flexible tubing from the bulb to the operating motor.
The flexible tubing ihay be furnished in varying lengths, and is generally protected
by a flexible metal armor.
,
2. Electrically operated equipment utilizes electric current as a primary source of energy, its flow being regulated as required ho operate motors, relays, or other con trolled items.
Electrical controls may be divided into two classes: (1) those wherein the primary measuring device utilizes contacts to regulate the flow of the electric current, and (2) those wherein the primary measuring device is a resistance wire component of. an electronic circuit; these are known as electronic controls.
3. In pneumatically operated equipment the primary source of energy is compressed air usually at a pressure of 15 to 25 psig. The flow of this air is proportioned as re quired to operate valves, dampers, relays, or other controlled devices.
4. In hydraulically operated equipment the primary source of. power is a suitable liquid at a pressure of 15 to 25 psig or higher, which is handled in the same manner as compressed air.
TYPES OF CONTROLLERS The basic types of controllers and their operations are:
1. Two-position or on-off controllers are the simplest type and are clearly described by the name. With controllers of this type the valve or damper motor.can assume only two positions, either open or shut.
2. Proportional or gradual acting controllers function to re-position the controlled device, by small increments of travel, to regulate the flow as the controller senses a slight change in the controller condition.
3. Floating controllers act to produce valve or damper movement whenever there is a deviation from the control point. Whenever the condition to be controlled is above the control point, the valve closes at a constant rate, and continues to close until the temperature returns to the control point. Below the control point the valve reverses its action and moves in the other direction until the control point is again reached.
4. Automatic reset (or proportional plus reset) controllers function to reposition a valve or damper by small increments of travel, as in a proportioning controller. In addition, a mechanical device in the controller automatically and constantly resets the instrument to offset the normal drift (inherent in a proportional controller) be-
839