Document dDnLMV5g80gnokYqOrdzex1ZG

WRITTEN BY: PULLEM" QAT APPROVED BY: DERIVATIVE'S AREA SUPERVISORS DATE: 6/22/88 CHECK ACTION STEPS (Capital letters) and Comments (Small letters) This SOP is written to develop a uniform procedure throughout Derivatives to ensure that the appropriate steps are taken prior to removing from service or bypassing an alarm, instrument, or shut down system automatic valve. This SOP will provide an effective way of communicating the status of these instruments to others and making sure that the necessary steps are taken to correct the problem. This procedure is intended to apply to all pressure, temperature, flow, level, analyzer, etc. instrumentation and the associated control valves. This SOP is considered to be each unit's minimum standard. Each unit reserves the right to require a higher lev 1 of reliability if it is deemed necessary by the unit supervision. 1. IF AN ALARM, INSTRUMENT, OR SHUT DOWN SYSTEM MALFUNCTIONS, THI OPERATOR'S FIRST RESPONSE SHOULD BE AN ATTEMPT TO FIX IT. In every circumstance, the first response should be a reasonable effort toward correcting the cause of the problem. Operating without alarms, instrumentation, or shu^ down system valves introduces a level of ri3k that is not desirable. 2. CHECK TO MAKE CERTAIN WHAT PRIORITY THE ALARM OR INSTRUMENTATION FALLS INTO: Check the list of alarms attached in the unit SOP manual to determine what the priority of the alarm is. The priority system to be used is as follows: Priority 1. - Critical instruments whose failure would either cause or fail to inform of situations causing accidental fire, explosion, uncontrolled release of dangerous materials, reportable environmental releases, or major property or production loss. These alarms include those which have been mandated by outside agencies (RCRA, EPA, co DEQ, Consent Decree), also Operations Review Committee (ORC) reliability alarms, and alarms deemed critical by operations supervision. All of these alarms are on the prooftesting schedule. Priority g. - Critical instruments whose failure could eithei CO cause or fail to inform of serious conditions involving recordable environmental releases, property or productior losses, or other non-life threatening situations. These are slightly lower priority alarms which are also on the prooftesting schedule. Priority 3. - All other alarms, which are not on the prooftesting schedule. PAGE 1 OF 4 BTMS>?21 Note: Operations will treat priority 1 and 2 alarms in an identical fashion. The only reason that these are differentiated is for the sake of the prooftesting program. IF THE ALARM IS PRIORITY 1 OR 2, GO TO STEP #S. IF THE ALARM IS PRIORITY 3, GO TO STEP #3. 3. RESPONSE Xa PRIORITY 3 ALARMS. THE LEAD OPERATOR SHOULD FOLLOW ESTABLISHED UNIT PROCEDURES AND HIS KNOWLEDGE OF THE UNIT TO EVALUATE EACH SITUATION AND MAKE A DECISION AS TO WHETHER THE INSTRUMENT CAN BE BYPASSED OR NOT. If there is any doubt about this choice, supervision should be consulted. These alarms and instrumentation are not considered critical under normal conditions. 4. THE LEAD OPERATOR SHOULD IMPLEMENT THE OUT-OF-SERVICE PROCEDURE FOR PRIORITY 3 ALARMS. This will include taking immediate action to initiat repairs. This means that at least a note in the maintenance logbook must be made to initiate repairs to prevent the problem from being forgotten. STOP HERE FOR PRIORITY 3 ALARMS. 5. RESPONSE XO PRIORITY J. OR 2. ALARMS. RCRA, EPA, CONSENT DEGREE, OR CRITICAL ALARMS, INSTRUMENTATION OR SHUT DOWN SYSTEM AUTOMATIC VALVES. NOTIFY YOUR LEAD OPERATOR OF THE SITUATION. No one except the unit lead operator or supervisor has the authority to approve taking an alarm out of service. 6. 4V-)i *4 3 0) O va* o O 4J J M< CJ u 4 o c Z 44 Matt O Vi fa fa oz u <D JZ n 4J C?O H 44 o THE LEAD OPERATOR WILL DECIDE IF IT IS SAFE TO TAKE THE INSTRUMENT OUT OF SERVICE. IF IT IS SAFE TO DO SO, THE LEAD OPERATOR WILL COMPLETE AN "OUT-OF-SERVICE" TAG AND MOUNT IT ON THE CONTROL PANEL. HE WILL ALSO MAKE NOTE IN THE OPERATIONS LOGBOOK TO EXPLAIN THE DETAILS OF WHAT HAS BEEN DONE AND WHY IT WAS NECESSARY. IF, IN THE LEAD OPERATOR'S OPINION, IT IS NOT SAFE TO DO SO, SUPERVISION SHOULD BE CONSULTED. The out-of-service tag is intended to be a communications tool for notifying other people that Priority 1 or 2 alarms are out of service. These tag3 should be affixed to the instrument on the control panel or, if thi3 is not possible, in another prominent place on the control panel. These outof-service tags will remain on the board until the situation is corrected. T>}ere are circumstances during routine operations when some of these alarms or valves need to be taken out of service for short periods of time to perform short term routine work on the system. Some examples of this include the following: (1). Pulling alarm cards at EDC I to look for a "mystery alarm". <2). Taking alarms out of s rvice on the computer at VCM II long enough to identify them on the CRT display. PAGE 2 OF 4 'BTIA30P21 (3). When an op rator and log book instrum nt man go outside to look at a shut down system valve that is sticking. (4). When OHC analyzers are bypassed for preventive maintenance work. Under these and other similar circumstances it would not normally be worth the effort to complete an out-of-s rvice CXI tag. For these short-term situations it will be acc ptable CO practice for the alarm# instrument, or control valve to be taken out of service provided that both of the following o criteria are met: o 1) The lead operator is informed of the situation and gives approval. CO 2) The operator gives undivided attention to this problem. If both of these cannot be met, then the out-of-service tag must be used regardless of the length of time requir d for the work to be done. The out-of-service tags are not a substitute for performing maintenance. The out-of-service tags serve only to communicate the status of instruments in need of repair. ___8. TAKE IMMEDIATE ACTION TO INITIATE REPAIRS ON THE OUT-OF SERVICE INSTRUMENT. After a priority 1 or 2 alarm, instrument, or control valve has been properly taken out-of-service or bypassed, it should not be forgotten about. On day shift this may r quirt redirecting the maintenance logbook priorities, or notifyinc supervision so an "Emergency" work order can be written. Oi the back shifts and during holidays, this may mean notifyinc the shift supervisor and getting shift mechanics or calling out mechanics so that the repairs can be made in a tim ly fashion. In either case it is strongly recommended that repairs be started as soon as practical. Ordering "Out-of-Service" tags. These tags are set up in our reproduction department with a form number (59A-6) so ^ that day shift operators can reorder these by telephon . ___ 9 o WHEN the repairs are successfully completed and the alarm, m instrument, or control valve is put back into service, the O 4J lead operator will remove the out-of-service tag FROM THE board, tape it into the logbook, and complete the bottom g SECTION OF THE OUT-OF-SERVICE TAG. %a h^ MipO^A "WEEKLY OUT-OF-SERVICE TAGGING CHECKLIST" WILL BE COMPLETE! g 0~^,BY EACH UNIT ON MONDAY MORNING GRAVEYARD SHIFT TO CONFIRM S .3'* THAT THE PANEL ALARMS AND LIGHTS ARE IN WORKING ORDER AND z o h n THAT ALL OF THE OUT-OF-SERVICE ALARMS, INSTRUMENTATION, AND CONTROL VALVES HAVE BEEN PROPERLY TAGGED ACCORDING TO THIS 4J SOP. THESE CHECKLISTS WILL BE MAILED TO THE DERIVATIVES Jj ^ ENVIRONMENTAL FOREMAN EACH WEEK FOR RECORDKEEPING AND AUDITING. w^ The objective of th we kly checklist is to routin ly take O an inv ntory of th out-of-s rvic tagging which has been done and to correct all tagging deficl ncies on the spot. __ TJTMSoPzT'' PAGE 3 OF 4 Each individual unit will make up a detailed checklist whict will be entitled "W ekly Out-of-Service Tagging Ch cklist". During this we kly inventory, the audible and visual alarms should be proven to be in working order. A check of all of the out-of-service tags on the panel will be made to insure that they all have been done correctly. Also a cross-check in the field will be made to insure that no bypassed SDS automatic valve has been overlooked. All tagging discrepancies which are found should be corrected on the spot by following step #11 below. 11. IF A PROBLEM IS IDENTIFIED DURING THE WEEKLY CHECKLIST WHICH HAS NOT BEEN PROPERLY "OUT-OF-SERVICE" TAGGED, THE DEFICIENCY MUST BE CORRECTED IMMEDIATELY. RETURN TO STEP #1 ABOVE AND FOLLOW THIS SOP TO INSURE THAT EACH ITEM IS PROPERLY OUT-OF-SERVICE TAGGED. 12. THESE CHECKLISTS WILL BE REVIEWED BY THE UNIT SUPERVISORS ANL AREA SUPERVISOR, INITIALLED, AND MAILED WEEKLY TO THE DERIVATIVES ENVIRONMENTAL FOREMAN. SL 01463 CONFIDENTIAL: Subject to Protective Order of 14th Judicial District Court No. 91-1145 PAGE 4 OF 4 'BTM^OPJU