Document dDDGoyOD0nNkQbYzoN7N50dN0
. ' V-
.
1
'
\
<;
ft
..................... 1 " .................... . ~ ' " ' '
INSTRUMENT FUNCTION OUTLINE .
DEPARTMENT
24 6
____
TITLE #3 Still Absolute Pressure
LOOP NUMBER024 .
SHEET
1
OF
Control 4
CLASSIFICATION
WRITTEN BY Brawley DATE 4/28/69R-EV.BY
DATE
PIC-2 4 REV .NO.
1.0 NEED FOR LOOP
This loop is needed to maintain the constant pressure desirable for optimum distillation conditions.
1.1 DESCRIPTION OF LOOP
' 1.1.1 Function
The function of this loop is to control the pressure in the
distillation system.
.
1.1.2 System Performance Required
The pressure should be maintained t 1 mm Hg. Abs. of set
point.
. `
1.1.3 Accomplishment of Function
The absolute pressure in the still pot is sensed by an
.absolute pressure transmitter which sends a 3-15 psig air
signal to a pressure indicating controller. The controller
compares this signal to a set point and sends a 3-15 psig
air signal to a control valve to compensate for variation
from set point. The control valve controls an. air bleed
into the still ejector and thus -controls the pressure in
the system. .
.
PCB-ARCH-EXT0373977
"INSTRUMENT FUNCTION OUTLINE
'
Air. to #3 Still Ejector, Abs. Press. --------------------------------------------------------------;--------
OTJEET2
OF
4
DEPARTMENT LOOP NUMBER CLASSIFICATION
Z.O
COMPONENT AND CALIBRATION DATA
246 &24------ ,
OPERATING DATA
A. PT-24 Abs. Press. Transmitter . Location: 14' level, East of tank 502 Output: 3-15 psig Air Supply: 20 psig Span: 0--100 mm Hg Abs.
MECHANICAL DATA
.
A. Foxboro Abs.. Press. Trans.
. #11AM-MS2
'
W/Piped & Mtd. Air Set & Gage
Range: 0 to 400 mm Hg.
316 SS Body
Gauge: 3-15 psig Calib.
0-100 Lin. Scale
Accuracy: 1%
Serial CO.: 1947917
IMO:
IPMO:
001
B. PIC-24 Pressure Indicating Contro ler
'
'
.
Location: Panel
B. Fischer & Porter Press. Ind. Contr
Input: 3-15 psig
#tl-i3 51ABFC
.
Output: 3-15 psig
Range: 0-100 Unif.
Action: Inc. input
Prop. Band: 2-500%
Inc. output
Reset Rate: .2 to 30 min.
.
Air Supply: 20# IAS
Accuracy: 1/2%
Serial No.: 4797A15
IMO: None IPMO: 165
PV-24 Control Valve
.
Location: 28' level, NE of
tank 523
Input: 3-15 psig
Action: Air to close
Fails open
C. Fisher Gov. Control Valve #657A
Actuator Size 30 Travel 3/4"
1" 150# fig. carbon steel body
3/8" 316 SS Micro-Flute Trim
' Teflon Packing; Skirt-Top Guiding
Packing: 1R2900-0101
St. Code: 41-61908
IMO: 45
IPMO: 126
Valve Plug: 2N5492-000A
Store Code: 41-60413
Seat Ring: 1A5106-3507
Serial: 4219080
PCB-ARCH-EXT0373978
f
.^INSTRUMENT FUNCTION OUTLINE
TITLE #3 Still Absolute Pressure
DEPARTMENT
246
LOOP NUMBER
0 24
PCB-ARCH-EXT0373979
INSTRUMENT FUNCTION OUTLINE
DEPARTMENT
Tit L'E #3 Still Absolute Pressure....
LOOP NUMBER
SHEET 4 ________ OF WRITTEN BY
DATE
Control
CLASSIFICATION
REV,BY
DATE
-244-
_02A.
ptp~9A REV. NO.
3.0
OPERATION OF LOOP
"
3. ]_ NORMAL OPERATION
'
.
'
Set vacuum controllers to maintain 40 mm Hg. absolute
pressure at the still pot. Observe the scheduled start
of the stills to insure that operating temperature is reached
before the boiling temperature is reached. If vacuum is
lowered too quickly the Aroclor will flash and belch over
crude material.
-
-
'
. ,3.1.1 Start Up Instructions
Open main valve to jet in the vacuum line just above the catch tank, start steam to first and second stages, open water valve to after condensor, vacuum should pull down to 40 mm Hg. and hold steady.
3.1.2 Shut Down Instructions
Release vacuum by re-adjusting the vacuum controller to 760 mm Hg. Abs. (100% on instrument).
3.1.3 Manual Operating Instructions
Set pressure controller on manual, regulate air pressure to control valve, as per operating instructions.
3.2
INTERLOCKS
None
,
3.3 ABNORMAL OPERATIONS
3.3,3. Air Failure
Loss of air to loop will cause loss of vacuum. Control valve will open and let atmospheric air bleed in.' .
3.3.2 Power Failure
No affect on this loop.
PCB-ARCH-EXT0373980