Document dD5OQoNw0pp6MY2gJVX4qNXv5

34CHAPTER FIRE EXTINGUISHMENT AND CONTROL Water system*. water supply and storage . automatic sprinklers water spray systems hydrants, hoses, and nozzles-------------------------- 34-1 Special systems and agents: foam systems wet water carbon dioxide extinguishing systems dry-chemical sys tems steam systems inerting systems--------------------------------------------- 34-11 Portable fire extinguishers principles of use water-solution extinguishers dry-chemical, carbon dioxide, and liquified- gas extinguishers dry-powder extinguishers federal rules on fire extinguishers miscellaneous equipment training of employees maintenance and inspection34-16 Equipment used to extinguish and control fires is of two types fixed and portable Fixed systems include water equipment automatic sprinklers, hydrants, standpipe hoses, and special pipe systems for dry chemical, carbon dioxide, and foam Special pipe systems are applicable to areas of high fire potential where water may not be effec tive, such as tanks for storage of flammable liquids and on electrical equipment Fixed systems, however, must be supple mented by portable fire extinguishers These often can eliminate the action of sprinkler systems because they can prevent* a small fire from spreading as well as provide rapid extinguishment in the early stages of a fire (See Fig 34-4 ) Water Systems Water supply and storage Sprinkler systems need a reliable water supply of ample capacity and pressure for efficient fire extinguishment (Fig 34-2) For example, to supply all sprinklers likely to open in addition to hose streams, a vol ume as high as 500 to 1,500 gpm may be needed The precise need depends on the occupancy classification Pressure should be high enough to maintain a residual pres sure of 15 psi in top-story sprinklers Water may be supplied from the follow ing sources 1 Public water works underground supply mams 2 Automatically or manually controlled pumps drawing water from lakes, ponds, nvers, surface storage tanks, under ground reservoirs, or similar adequate sources 3 Pressure tanks contaming two-thirds water and one-third compressed air for This chapter was revised by Marshall Petersen based on reviews by selected mem bers of the National Safety Council 34-1