Document byrpBLK5J35B2dmkJmejNda10
ft EA~ Uni!'d Slate>
~-.,
Enviwnmen!al Protection
"
Aganc\'
Region 6 Compliance Assurance and Enforcement Division
INSPECTION REPORT
Inspection Date(s): Media: Regulatory Program(s)
Aprilll, 2018 Municipal Wastewater NPDES
Utility Name: Facility inspected: Facility Physical Location:
(city, state, zip code) Mailing address:
(city, state, zip code) County/Parish: Facility Contact:
Haslet, City of
Wastewater Collection System
City Hall and Utility Shop via 101 Main Street
Haslet, TX 76052
City of Haslet, 101 Main Street
Haslet, TX 76052
Denton and Tarrant David Rogers
I Public Works Director
817-307-0263
FRS Number: Identification/Permit Number: NAICS: SIC:
110010934533 TXU000160 22132 4952
Personnel participating in inspection:
David Rogers
City of Haslet
Public Works Director
817-307-0263
James Tucker Damon McElroy
City of Haslet Region 6 EPA (6EN-WM)
Water/Wastewater Operator 817-829-4415
Environmental Engineer &
214-665-7159
6EN-WM Enforcement Officer
EPA Lead Inspector Signature/Date
Supervisor Signature/Date
/1
J)~ rvt<--d-
Daman McElroy
{]V//7 ;1n:, tJ~
Carol Peters-Wagnon
sh /'k1()
Date
s/ll/; il
Date
6ENFORM-019-R7 (2/15/2017)
1
Section I- INTRODUCTION
City of Haslet Wastewater Collection System Inspection Date 04/11/2018
PURPOSE OF THE INSPECTION
EPA Region 6 inspector Damon McElroy arrived at Haslet City Hall at 8:45am on Aprilll, 2018, for an announced Compliance Evaluation Inspection. I met with the City's wastewater utility officials illustrated by the inspection sign-in sheet in Appendix 1. I presented my credentials to the group. The purpose of the inspection was broadly explained as a collection system compliance evaluation of areas such as capacity, management, operations, and maintenance (CMOM) and associated Sanitary Sewer Overflow (SSO) mitigation activities; as well as SSO reporting according to Federal and Texas law. For further CMOM program guidance you may reference the web link: https://www3.epa.gov/npdes/pubs/cmom guide for collection systems.pdf.
The inspection examined the City of Haslet's (or City) sanitary sewer collection system, following EPA's National SSO Initiative, in CWA accordance. For further SSO initiative information you may reference the web link: https://www.epa.gov/npdes/sanitary-sewer-overflows-ssos. The inspection scope is to generally evaluate the municipalities that receive Trinity River Authority (TRA) wastewater treatment contractual services in order to assist in stopping unauthorized/ unpermitted discharges (or SSOs) and encourage sustainability. The City's collection system is regulated under the:
Texas Water Code (TWC) Texas Administrative Code (TAC) Texas Health and Safety Code Clean Water Act (CWA) Code of Federal Regulations (CFR) Associated DCWWS NPDES General Permit Conditions
Before leaving the facility, an exit briefing was conducted that explained observations, suggestions and areas of concern. This inspection report is based on information supplied by the City representatives, observations made by the U.S. EPA inspectors, records and reports maintained by the City, the State of Texas, and the U.S. EPA.
FACILITY DESCRIPTION
The City's WW utility serves over 1,500 residents via about 240 residential service connections, 193 septic systems, and 98 commercial connections; covering 8.2 square miles. The City's collection system consists of about 17.3 miles ofWW gravity mains, zero lift stations, and "primarily" concrete manholes. The sewer mains are comprised of 99% PVC (that is between 5 to 20 years old) and about 1% vitrified clay (VC) pipe.
The Public Works Department employees two fulltime City officials (one utility director and one operator indicated in the sign-in sheet in Appendix 1, that split O&M activities between drinking water (purchased from Fort Worth) and Wastewater O&M activities. The City's sanitary sewage is transmitted to the TRA Denton Creek Regional Wastewater System (DCRWWS- Permit No.: TX0104957) for contractual wastewater treatment.
2
City of Haslet Wastewater Collection System Inspection Date 04/11/2018
Section II- OBSERVATIONS
Based on the inspection discussions, data analysis, and observations:
Reportedly, an 1/1 and CCTV analysis was performed approximately 20 years ago that led to the City's Sewer Master Plan and resultant PVC replacement of existing VC with increased line sizing and capacity.
Collection system capacity was increased or upsized based on the estimated 'ultimate' growth flowrates.
The City has adequate capacity during wet weather. CMOM activities were explained to consist of the following:
1. Clean- via trailer mounted jet- about 33% of the WW mains each year. 2. Conduct inspection and preventative maintenance (i.e. jet cleaning) of collection system
areas known to have operational problems (such as sagged or flat sewer lines). 3. Replace and upsize the existing VC gravity system. The City reported one sewer overflow in the past five years as documented in Appendix 2. The City uses the TCEQ Regulatory Guidance "RG-395" for unauthorized discharges and sanitary sewer overflows, revised September 2016. The RG-295 web-address is located here:
htt ps:Uwww.tceq. texa s.govI assets/public/com m exec/pubs/rg/rg-395. pdf
The City's sewer overflow SOP (standard operational procedure) is described as follows: 1. Determine sewer overflow source and call for additional contractual personnel and support as needed. 2. Stop or reduce the source of the sewer outflow. 3. Contain the spill; use sand bags, booms, pillows or earthen dams. 4. Return the spill to the sewer collection system; use a spoil vacuum trailer or trash pump to mop up as much of the spill as possible and dispose of in manhole SH-10 (located at 790 School House Road). 5. Treat and disinfect the affected area; use concentrated enzymes and calcium hypochlorite (HTH or chlorine) mix with water if necessary. 6. Assess any threat to human health and the environment and take laboratory samples as needed. 7. Submit Water Quality Non Compliance Notification form to TCEQ according to RG-395. 8. Make any needed repairs. 9. Evaluate possible ways to prevent future outflows.
If a SSO reaches a waterway, public works does not notify the Texas Parks and Wildlife or the City code enforcement department or any MS4 team.
Customer inquiries are handled at the call center located at City Hall, 101 Main Street. Public Works operates 40 hours per week during "normal" working hours (i.e. Monday through
Friday, from about 8:00a.m. to 5:00p.m.).
3
City of Haslet Wastewater Collection System Inspection Date 04/11/2018
Utility related phone inquiries and emergencies that occur after the 40-hour work week are routed to the City's utility director and the utility operator's cell phone automatically- from the call center's phone.
The City does not participate in the TCEQ Sanitary Sewer Overflow Initiative (SSOi). O&M is funded annually as part of the water and sewer budget. Water rates are adjusted as needed to cover WW utility costs. 1/1 reportedly occur primarily from "older" manholes. City operator(s) are TCEQ certified and receive adequate training. The City was observed to not implement a fat, oils and grease (FOG) program. The City was observed to not have a root-control program. The City does not have a formal program to stop private or subscriber sewer overflows. There is no City ordinance granting authority to take appropriate action to stop private or
subscriber sewer overflows or implement a FOG program (i.e. right of entry, enforcement, and inspection authority). The City does not document, analyze and map repeat problem areas or hot spots. The City purchased a GIS system that is to be populated with WW utility assets in the future. The City intends to conduct a collection system condition assessment in the future, including for PVC pipelines over ten years old and manholes. The City has plans to install additional lines to unserved or underserved areas including to replace septic systems with a gravity sanitary sewer system. The City has not implemented a formal capacity, management, operation and maintenance (CMOM) program. The City does not utilize a work order management system. Wastewater customer inquiries or work orders could not be obtained or compared to reported SSOs to identify non-reported SSOs. The City does not implement an asset management plan. The City indicated it has adequate capital improvement resources for wastewater utility O&M. The City reported that it has adequate resources for an intended future condition assessment. There are no categorical industries in the City.
Section Ill- AREAS OF CONCERN
The City of Haslet utility department will best serve Haslet's customers by addressing the following:
1. The City utility needs a FOG Program.
2. The City needs a program to mitigate private or subscriber sewer overflows.
3. The City needs ordinances (i.e. right of entry, enforcement, and inspection authority) to implement a FOG program and a private sewer overflow mitigation program.
4. The City needs to implement a Work Order Management System to track and identify problem areas.
4
City of Haslet Wastewater Collection System Inspection
Date 04/11/2018 5. The City needs to track and analyze WW relevant customer inquiries to prevent SSOs. 6. The City further needs to document, analyze, and map repeat problem areas or hot spots. 7. Updated 0 & M related SOPs need to be made available for utility staff. Section IV- RECOMMENDATIONS AND SUGGESTIONS
RECOMMENDATIONS 1. The City needs a formal capacity, management, operation and maintenance (CMOM) program. 2. If a SSO reaches a waterway, the City needs to notify and work with the: a. The Code enforcement group, b. The Texas Parks and Wildlife department, and c. Any Municipal Separate Storm Sewer System (MS4) permit program team as appropriate. 3. The City needs a root-control program. 4. The City should implement a formal asset management process. An active asset management plan will support the City to manage and operate utility assets at a lowered cost as well as judiciously identify critical infrastructure rehabilitation or replacement projects.
SUGGESTIONS
The City would benefit by participating in the TCEQ Sanitary Sewer Overflow Initiative (SSOi) (more SSOi information is available via the web-address:
https://www.tceq.texas .govI com pi ia nce/i nvestigatio n/ssoi nitiative)
Section V- FOLLOW UP
No information was received by EPA after exiting the Facility on April11, 2018.
Section VI- LIST OF APPENDICES
Appendix 1- Opening Conference Sign-In Sheet. Appendix 2- Reported SSOs (one in the last five calendar years).
5
Appendix 1 Sign in Sheet
United States Environmental Protection Agency
Region 6- Water Enforcement Branch 1445 Ross Avenue, Suite 1200
DATE:
TIME: SUBJECT:
Aprilll, 2018
8:45am City of Haslet Collection System and Wastewater Utility Compliance Evaluation Inspection
MEETING ATTENDEES
1'-1 ~{'
Pcvt'./~6 r5
J !A rY\ "<. s lu cA-<v
0 ~ 6 rJ r'r\,u~ ll
<!) (l--'o t ivf'\'1:: ~ ~ f-'J ~ -Kz::
t2-lf ~Jl" st7ff JV ?- 13"!..-<;;73),/f. j/?- !J'J-o.Jt '"3<~.
C ,'f''J of' H,.. s{c+ Q: Pwt Rb
g[f?- ; J.:l - 'i"/1c;
J-~J1-IP (p 5 .7f5'f
f2,1/11;,4-l t-
c/O?rrg/w s-kf.7
~ fvcl{u-C?. /.."rl'-- I' 0~'")
""'~"''~0 ~~~ e rf-ll~(. 'tl""'
Appendix 2 SSO Noncompliance Report (One) (For the Past Five Calendar Years)
,..,
PI
Accidental Discharge or Spill Monthly Summary Form
*See back ofform for guidance for completion
General Information:
Permittee: 0
Subscriber: 181
Regulated Entity Name: Town of Westlake
EPAIDNo:N/A
Regulated Entity No: 101272979
TCEQ Region: Region 4- DFW
PermitNo:N/A
County: Tarrant
Start Date Start Time
End Date End Time
Volume Location (gallons)
Cause
Steps taken to reduce, eliminate, and prevent recurrence
Description/Content
7/31/2017 7/31/2017 400 7:30a.m. 9:3oa.m.
Arta Drive &Girona Drive intersection
Developer/Contractor construction activities caused over flow
Construction inspector to inspect plug insertion prior to contractor work.
Inflatable plug installed by tbe development contractor dislodged and blocked flow. Discharge was contained on site.
Standard Method for Volume Calculation
Domestic metered usage from hourly web based meter reading system and field estimation.
Information Reported by (Name/Title~c.~ /J.ro~-eIIvJ D~
/ /
vl;,f:. orl<s 'jS,v.a
Date Reported )$r- I ZD I 7
/' A
/1
Signature: (__. ~ (/ ;:!)~, t /
(;
\
TCEQ-20756 (06-27-16)
Page 1
Note: A copy ofthis fonn should be sent to your TCEQ Regional Office no later than the 2olh day ofthe folio 'Wing month and the original to the TCEQ Compliance Monitoring Team
(MC224), Enforcement Division, P.O. Box 13087, Austin, TX 78711~3087
"'Ifthe accidental spill or discharge occurs at a Subscriber system (collection system only), use the RN associated to the collection system. If you are uncertain ofyour RN, you may
call the TCEQ Regional Office for assistance.