Gerald D. Hines Interests
4040 One Shell Plaza Houston. Texas 77002
I
Area Code 713.225-0565
May 10, 1984
Mr. Frank Bartram Administrative Services -
Manager Office Facilities Shell Oil Company 901 One Shell Plaza Houston, Texas 77002
Dear Frank,
Accredited Industrial Hygienists has completed their air monitoring tests and bulk sample analysis of fireproofing material in One Shell Plaza and Two Shell Plaza. Copies of the test results and a summary of proposed OSHA asbestos regulations are enclosed.
Judging from these test results, it seems evident that the average office worker's exposure to airborne fibers, including asbestos, are well below EPA acceptable levels. In fact, the levels for samples taken outside the Building are higher than those taken inside.
I hope that these test results satisfy your requirements. Please don't hesitate to call if I can be of further assis tance .
Respectfully,
Charles Elder Property Manager One Shell Plaza
/nm Ends.
ABS-011754
LAM 031811
(7131 477-8101
Accredited Industrial Hygienists
P.O. Box 18556 Houston. Texas 77223-8556
Jones Lang Management Office Centex Building
1201 Louisiana, Suite 30Z Houston, Texas 77002
'
Attn: Mr. Lyn Grunze
REPORT OF BULK ASBESTOS ANALYSIS
Received: Coded: Marked:
4-19-84 00399 Three bulk samples to be analyzed for asbestos from Entex Building
Sample
I-Beam Insulation
PI pe
Duct
2 of Asbestos 1-52
N.D. N.D.
Type of Fiber Chrysotlle Asbestos
Fiberglass Fiberglass
N. 0. - Hone Detected
Note: Bulk samples are considered to contain asbestos only if 12 or more asbestos Is present.
Method: Polarized light microscopy, EPA tentative method.
'Sjf\
<-- Analyst V\
_____ ' 1
n
'--r^^'v
L>
Certification
'^7-84
LAM 031812
ABS-011755
(713) 477-8101
Accredited Industrial Hygienists
P.O. Box 18556 Houston, Texas 77223-8556
CONFIDENTIAL
Gerald D. Hines Interests 4040 One Shell Plaza Houston, Texas 77002 Attn: Mr. Charles Elder
REPORT OF BULK ASBESTOS ANALYSIS
Received: 4-9-84
Coded:
00395
Marked: Eight bulk samples to be analyzed for asbestos
Sample
23rd FI Hallway (T.S.P.)
25th FI Control Pit (T.S.P)
26th F1 Ofc Space (T.S.P.)
#1 Level 1 (O.S.P.)
#2 Lobby (O.S.P.)
t3 Level 29 (O.S.P.)
#4 Level 43 (O.S.P.)
#5 Std. Celling tile (O.S.P.)
Asbestos % Type
5-10%
Chrysotlle
5-10%
Chrysotlle
1-5 %
Chrysotlle
5-10% 10-15% 10-15% 10-15%
0
Chrysotlle Chrysotlle Chrysotlle Chrysotlle
--
Major Components --
--
--
-- -- -- -- Glass wool, cellulose, and calcium carbonate
Method: Polarized light microscopy , EPA tentative method
Analyst
Q Py
LJ
Ce^rificatiion
*)
4-25-84
LAM 031813
ABS-011756
(713) 477-8101
Accredited Industrial Hygienists
P.0. Box 18556 Houston. Texas 77223-8556
Gerald 0. Hines Interests 2245 Two Shell Plaza Houston, Texas 77002 Attn: Mr. Morgan Hill
ASBESTOS SURVEY
Conducted: Coded: Subject:
4-28-84 00402 Air monitoring for airborne asbestos at Two Shell Plaza, area testing
Sample Location Room 1102D Room 1530 Room 1708 Room 2109 Room 2245 Room 2386 Room 2405 Room 13106 Outside (near plant shop) Outside (Walker St)
FIbers/cc 0.02 0.01 0.04 0.04 0.03 0.02 0.02 0.01 0.02
0.04
lam 031814
ABS-011757
Accredited Industrial Hygienists-
P.O. Box 18556 Houston. Texas 77223-8556
r7" r
Gerald D. Hines Interests 4040 One Shell Plaza Houston, Texas 77002
Attn: Hr. Charles Elder
ASBESTOS SURVEY
Conducted: Coded: Subject:
4-28-84 00403
Air monitoring for airborne asbestos at One Shell Plaza, area testing
Sample Location Room 563 Room 1828 Room 2152 Room 2188 Room 4040 Room 4401 Room 4801 Room 4872 Outside (Louisiana St) Outside (Smith St)
Flbers/cc LT 0.01 LT 0.01 0.02 0.01 LT 0.01 LT 0.01 0.01-' 0.05 0.03 '0.06
lam 031815
ABS-011758
(713) 477-8101
Accredited Industrial Hygienists
P.O. Box 18556 Houston. Texas 77223-8556
PROPOSED OSHA ASBESTOS REGULATIONS (As of April 10, 1984)
Limit Ceiling
Fibers per cc 2 or 3
PEL (Permissible Exposure Limit) 8 hr shift
0.2 or 0.5*
"Action Level"
0.2
Comments
Reference
No employee may be exposed at concen trations above ceiling at any time.
29 CFR 1910.1001 (b) (3)
No employee may be
29 CFR 1910.1001
exposed to average
(b) (4), (k)
concentrations above
this concentration.
Semiannual personal
monitoring is required;
A training program is
required for concen
trations over 0.2 or
0.5, even if respira
tors are used.
Employees subject to concentrations 0.2 or greater would be con sidered "exposed." Annual medicals, in cluding chest x-rays, are required.
49 FR 14123.
* OSHA is considering whether PEL should be 0.2 or 0.5 Fibers per cc.
PROPOSED RESPIRATOR REQUIREMENTS (29 CFR 1910.1001 (k) (Table 1)
Airborne Concentration, Fibers/cc____________
Up to 2 or 5 Up to 20 or 50
Greater than 20 or 50
Required Respirator
Reusable or single use
Full facepiece, or powered, air purifying
Type "C" (supplied air)
LAM 031816
ABS-011759