liquid Insulation Is tip-top^snd to hoop It in tho Post of oporsting hostth
*GNS 072969
YOUR ASKAREL" TRANSFORMER SHOULD BE
HONS 01*910
insulation
IN
TRANSFORMERS
OILS -- that can burn
TiH'n* are quite a number of these. They are sold by oil companies; and these mineral oils are used in transformers where, if they catch fire, no groat. harm (besides the transformer itself; comes from the burning oil. If water gets into an oil-filled transformer, it tends to settle through the oil to the bottom. There are certain ways to chock on the health of mineral oil insulation, too, but the "Check points" are somewhat different than for askarel.
ASKAR ELS -- that cannot burn
Although there are TWO types of askarel fluids (supplied under a number of brand names), actually they all have just one and the .same basic ingredient: Monsanto's Aroclor1" 1260. (If you want to know, Aroclor 12G0 is hexachlorobiphenyl). And THIS is one of tin; world's best liquid insulations!
07i<m
don't worry about "different kinds"
S'.', what, .ire the two types? What's the difference? Simply this: they have different pour points and the Liny amount of "scavenger" chemical added to each is different. The 1'yranol 1-170 fienora! 'Wvtrin type has the lower pour point; it will still pour at 17" In-iow ;F.i zero. The Inerteen ITO (Westinghouse) type w ill pour down to 2(JC below (F.j zero. These two types each contain a tiny amount of a different additive; both additives are good and do (heir job. However, the additive in I'yranol type askarel can crystallize out a-bit at 14 above (F.) zero. It docs no harm; the crystals disappear after a while when the transformer warms up.
Other brand names, like Chlorextol (Allis Chalmers); Noflaniol i Warner Klectno; Ashestol lAmertran Corp.i; Saf-T-Kuhl (Kuhlnian I'iieeinc: are either one type or the other. Some manuIaci urers simply call their fluid by the common descriptive name: askarel. Hut. transformer manufacturers who supply askarel fluids have sound reasons for favoring their own type. So, it's best to stay with your particular brand.
However, since basically askarel is askarel, there will be no difference in the operation of your transformer if IN EMERGENCY you would interchange or even mix the two types!
Hut. askarel is NOT oil cannot, should not, must not be mixed with ordinary transformer oil. For one reason: the inside core materials used with mineral oil filled units get gooey with askarel. Fur another reason over 2` f of mineral oil mixed into askarel "clobbers" its fire resistance. For another reason never mind! Don't ti't.r or interchange askarel and oil.
"Askarel" liquid insulation is a very carefully-manufactured, highly imre, chemically made fluid. It does not vary in composition like the range of oils. AND . . . askarel is heavier than water. If water gets into askarel insulation, only a smidgeon (125 ppm i dissolves the rest floats on lop.
Askarel is one of Ihe most fire-resistant, chcnueally-incrt, heat-stable lit/iints ever ileveloped! You can be sure of this: askarel does not deteriorate when exposed to air, heal, hot metal; it does not break down over long use to form conducting or corrosive chemicals; it docs not sludge or oxidize. Askarel will remain perfectly stable \c.tr after year after year unless broken down by exposure to severe arcing the kind that could set an oil transformer afire. The only real "enemy" of askarel is: contamination by water.
HONS C72972
NOW LET'S TALK
\ car to Year
One of the most brain-y electrical engineers in the business once said: "The host `maintenance' for askarel transformers is KEEP 'KM DRY, and leave them alone!"
This business of '`keep 'em dry," however, whether your trans former is EITHER an oil-type or an askarel type, is the watchword! li lakes some care. In fact, anything MECHANICALLY you can do to stop moist air breathing and condensation will be the best health insurance for your liquid filled transformer. Here are 9ome of i he questions that come up when you want to "keep 'em dry."
is your transformer a welded she!) or a gasket top? (even the tightest gaskets can "breathe!")
Does your transformer run, stop; run, stop; run, stop? (This hot-to-cold temperature cycling makes the breathing faster and harder!)
is air around it mostly cold and dry or hot and moist? (Wouldn't it be great for automobiles and transformers if there wasn't any such thing as condensation!)
\Viu:n you have "breathing" and high humidity -- you can cut back on check-ups if you fit the transformer with a drying device uii transformer makers offer these) or you can bleed dry nitrogen mio the shell. Any mechanical steps you take to stop inside con densation will be double insurance on trouble-free operation.
Of course, if you are ordering a brand new transformer -- either oil or askarel type - you can "design out" most of the moistureentry points. Basically, you call for all-welded construction, in cluding fins, pipes, and instrument connections AND a recessed gasket for the hand holes.
(If you or your electrical equipment supplier would like more complete details on tips to keep innards dry, we can send you a copy of: "Design Details For Moisture Protection of Liquid Injulaiion Transformers.")
So you'll be happy to learn that preventing moisture contamina tion is the only major health insurance you need provide for your askarel insulation.
072973
hqns
CHECKING THE CHECKPOINTS
Now you are well on your way to being an "expert." Since you know that keeping tabs on MOISTURE is the major checkpoint on your aakarel transformer, let's ask:
How do you keep tabs on moisture?
.
You do this by a periodic test of the askarel's dielectric strength.
Do not bother to check -- or If you do -- do not be misled or dls*
turbed by relatively high power factor... or even drop In volume resistivity.
(if you want to know why, you can read the fine print on the following page.)
The DIELECTRIC STRENGTH of the aakarel is your major due to the "health" (i.e. dryness) of your aakarel transformer. Besides taking a good look at a sample of your aakarel -- dielectric strength is the only "test" you need actually run!
Here's why: the dielectric strength of aakarel is sensitive to moisture: not sensitive to other ordinary contaminants (like metal duat, salts, dirt, etc.). The dielectric strength is also hurt by severe arcing, but you'll know that arcing is the culprit if the askarel has gotten noticeably black or has particles of sooty carbon floating in it. Unless you've had severe arcing (lightning, accidental overload, back surge, etc.), the dielectric strength is your "moisture indicator."
New askarel has a minimum dielectric strength of 35 KV at 25*0.: a maximum moisture content of 30 ppm. If you check the dielectric strength periodically, And that it is rapidly decreasing -- this la your "clue" to moisture pick-up, arcing, or both. When the moisture content rises to 100-120 ppm (or over) -- the dielectric strength will drop to 20 KV or less. That's your clue!
INSPECT FOR WATER CONDENSATION IN THE SHELL, AND "REFINE" THE ASKAREL.
As the operator, you will have to judge how often you want to check up on your askarel insulation. Steadily running, weil-eealed askarel transformers have run aa long as 25 years on the initial charge of askarel -- and the dielectric strength still cheeked out at above 30 KV. HOWEVER, if the dielectric strength drifts down ward to 25-20 KV at 250C. -- then it is time to "clean-up" the liquid insulation and to get rid of any water accumulation in the shell, too.
This askarel clean up is relatively simple: the aakarel need NOT be discarded. BUT MOST IMPORTANT ... if the dielectric strength drops rapidly over a short period of time, this shows rapid pick-up of water (or arcing).
When you take your sample for check-up -- be sure to take it carefully (so it represents the surface) and handle the sample properly (so it doesn't pick up moisture in the sampling).
MONS 072974
MCNS 07*975
You'll be able to "take the pulse" of your askarel insulation with the following five simple rapid tests. (Three are simply "inspectionby-eye! '; You can do these check-ups yourself or have the tests run by a local transformer service shop.
1 COLOR iby inspection) New askarel is a clear, faintyellow liquid. After long-term use, the color will gradually
intensify to brown. Any color change, such as taking on a green, red or blue cast, indicates extraction. If you find a distinct change in colnr, the complete range of electrical characteristics should be checked to learn if the extracted color is the tell-tale for contamination.
2 CLARITY (by inspection) New askarel is clear and should remain clear in serv ice. Development of turbidity or cloudi ness indicates contamination from water, insulation par ticles, metallic dust or dirt. Cloudiness or turbidity calls for a complete analysis. The exception to this would be cloudiness in a cold sample of PYRASOL H70. This type askarel contains a scavenger additive which will "come out" of solution when cold (around 15#F.) and cause white turbidity and perhaps show salt-like deposits on the trans former shell, if this is noticed, heat the askarel sample to 150-200F. for several hours and agitate. Upon heating, the Pyranol's additive will redissolve, as it will in a warm transformer.
BLACK COLOR AND SMALL CARBON PARTICLES (by in
spection ) -- I f the color of the sample is black, and especially
3 if suspended carbon particles can be seen, this shows that
the askarel has arced and should be discarded. You can
also detect exposure to strong arcing
with
indicator paper. Simply dip a piece of moist blue litmus
paper into the askarel. If the blue litmus turns red, there is
excess acidity from arcing beyond the limit absorbed by
the "scavenger" additive.
PONS C72976
DIELECTRIC STRENGTH i.by ASTM 0901, 1)877) The (iit11eelrie strength is the most important; ami it is a simple .cst to make. 'Hie dielectric strength of new askarel is 35 K V at 25C. minimum. 'Phis value should not be allowed to fall below 25*20 KV. Contaminants (which may have pronounced effect on the power factor and volume resis tivity) itximllif (io not hirer (utkarel'n dicleelric strength. Reduced dielectric strength almost always shows exposure to strong arcing or moisture contamination.
MOISTURE The moisture content of new askarel is .30 parts per million maximum. The moisture saturation level is about 125 ppm at ordinary temperatures. When the moisture content approaches 125 ppm (saturation level), (he dielectric strength goes down. The moisture content of askarel should not he allowed to rise over 70 ppm; it should be held as near as possible to 30 ppm.
NOTE: If your sample shows 30-35 KV dielectric strength, you need not check for moisture. However, if you do check moisture, use the Karl Fisher Method, A STM D-1533.
IF ANY OF THESE FIVE CHECK-UPS APPEAR ABNORMAL, CON TACT YOUR TRANSFORMER MANUFACTURER FOR COMPLETE ANALYSIS. Tln-M- simple tests will show you the condition of your askarel insulation, but. only indirectly the condition of your transformer. They cun be relied upon when the sample is carefully taken (so as not to 'miss" water globules floating on the surface or adhering to the shell m the air space over the insulation). So, if you have taken mechanical precautions against moisture entry into your askarel transformers ami can ''Keep 'em dry!" these tests will be your assurance ih.it, between chocks, you can "Forget 'em."
American institute of Electrical Engineers has published a comprehensive and informative guide titled "Proposed Guide for Maintenance of Transformer AsKariH," AiEC No. 76, December 1958. Tins guide describes properties to be nspected and the ASTM method to be used.
Monsanto completely analyzes each production lot of transformer askarel by mesc methods prior (o shipment. However, these official tests are NOT ES SENTIAL io the user of askarel transformers. When a complete analysis is re* quirec m j special case. I he user should request it from the transformer maker, why in turn c.m call on Monsanto if needed.
HONS 0729??
GROOMING ASKAREL FOR RE-USE
1 f strong arcing has blackened askarel, throw it away; it costs less to replace arced insulation than to reclaim it. If there's been no arcing, bui a low dielectric test shows moisture contamination, you'll find .1 is quite easy to refine the askarel back to good operating dielectric strength. Simply run the insulation through a dry, ab sorbent filter.
Most operators prefer a portable refining apparatus, such as a plate press, fitted with a dolly, (available from Sparkler, Mundelein, 111.;; or the earthen cartridge filter type, (available from Industrial Killer Corp., Lebanon, Ind.). Filter paper liners for the plate press arc available from Carl Schleicher & Schuell Co., Keane, N.H.
\ny flexible hoses and gaskets on the refining equipment should be lined with or made of materials that will not be softened by contact with askarel fluid. (Silicone or Teflon materials are suitable).
If you use a filter press, before refining it is advisable to oven dry the filler paper at 100C. for a half hour to remove all moisture. If the askarel to be refined contains excessive moisture, circulate it hot (55-60C.) through the filter fitted with the paper liners only first, Then, refit press with dry paper and load it with the absorbent earth.
The earth refining process is simple:
7. SPREAD DRY EARTH EVENLY OVER THE FILTER SURFACE. Fme-mesh Attapulgus clay or Fullers earth, dried and activated by heating for 12 hours at 250*C. immediately prior to use, is highly efficient. The amount of earth used should be 0.1 to 0.2 per cent by weight of the askarel (askarel weighs about 13 pounds per gaUon). To deposit the earth evenly, stir one-third of the earth with a small portion of askarel in a clean container. Pump the mixture through the filter and follow with tv/o more one-third portions.
2. PUMP THE HEATED ASKAREL FROM TRANSFORMER THROUGH FILTER. Circulate askarel taken from near the top of the transformer, pass it hot (55-60C.) through the filter and feed back through the bottom transformer outlet.
3. CONTINUE CIRCULATING THROUGH THE FILTER UNTIL ASKAREL IS CLEAR. When the askarel is clear use the simple tests described earlier to check for restored dielectric strength.
4. CHECK THE TRANSFORMER AFTER REFINING. After refining the askarel, the overall power factor and insulation resistance should closely approximate the values it would show with new askarel fluid.
1; the overall power factor \a more than 30-35 per cent (at 20C. and 60 cycles) it is considered POOR and it is advisable to run a complete analysis of the entire insulation system.
HONS 072978
POWER FACTOR & VOLUME RESISTIVITY
M'k'1 powpr factor ami low volume resistivity in transformer ino.ls arc commonly regarded as "danger signals" that the ud :;;i.s deteriorated and broken down chemically.
Tins is NOT true of askare) liquid insulation.
New, unused askare) shows these electrical values:
1 `ower Factor.
0.05-0.2'},',
(. 60 cycles/20C.
(about 1-2.0% ( 60 cycles/100*C.)
Volume Resistivity: 100*1000 x I09 ohm-cm (( 100C., 500V., DC., 0.1" gup)
Used askarel from SATISFACTORILY OPERATING TRANS IN )liM MRS normally (and frequently) shows
Power Factor:
20 to 80% (a 60 cyrles/100C.
Volume Resistivity: about 25 x 109 ohm-cm (( 100C., 500 V., DC., 0.1" gap)
This relatively high power factor and relatively low volume* re sistivity of used askarel ARE TO RE EXPECTED. Even at these levels, the askarel's dielectric strength is STILL in the 30-35
KV range.
The reason is simple: askarel, unlike "oil," is a relatively polar liquid. The volume resistivity is sensitive to traces of conductive
contaminants. Howev er, even in the presence of large amounts of
contaminants, the volume resistivity does not seem to fall below U) x HP tohm-cm). Vet the dielectric strength remains high, be
cause intrinsically askarel remains a non-conductor,
To quote from Insulation Magazine, December 1961
DIELECTRIC LOSS YARDSTICKS
)>y John C. Rotla, Manager Insulation Development Section, and Graham Iajc Moses, Manager Services Engineering, Westin ghouae Electric Corp., East Pittsburgh, l'a.
"Dielectric loss is a good comparative evaluation (or some characteristics of insulation. It may be used fur comparing similar samples of the same materials. It may not be used as an overall evaluation for com paring different materials." (i.o. "oils" and askarels)
Power factor is not an important criteria of askarel insulation wijciency IN A PROPERLY CONSTRUCTED TRANSFORMER.
However if improper construction materials or unpredictable (. ig:i contaminants enter the system - high power factor tin the uh.M-ncc of moisture in the shell) can indicate improper construction.
MCNS 0 72979
sampling your asl
NOW . . . sincr you know that the DIKLKCTUIC STKKNGTH is ;h<` most important. checkpoint, and that (except for arcingi MUIMTUK is the villain that saps dielectric strength you wan; to make sure that your SAMPLK truly represents your askurel insulation.
TAKE YOUR SAMPLE AS CLOSE TO THE TOP OF THE LIQUID SURFACE AS POSSIBLE!
.Many large askarel transformers have a built-in sampling tube near the surface for convenient sam pling. If additional sampling tube connections are mailrived on to valves for easier sampling, make the tubes of clean glass, stainless steel, aluminum or tin for rigid types; and silicone or Teflon tubing for flexible types.)
Water jlnols on askarel. If there is any water in your transformer, it may collect in little puddles ON TOT of the askarel. AND, therefore, more water will probably be dissolved in the askarel mar the top, where it contacts any collected condensation.
If you lind low dielectric strength and high moisture in the askarel, you will probably want to thoroughly dry out the shell and take some mechanical steps to keep it dry.
When you take your askarel sample for testing, take the same precautions (but no more) that you take when sampling mineral oil:
1 Select a dry day. Do not sample insulation on a warm, moist day when humidity exceeds 75%, and
2 Make sure that the askarel is at least as warm as the sur rounding air. (Cold liquids can condense moisture from humid air.)
3 NEW containers for fluid sample Your sample container should be a new and previously unused small mouth pint glass bottle fitted with a Bakelite screw cap fitted with an aluminum or tin bottle cap liner. Make sure that the new bottle does not stand around open to collect dust or moisture. Rinse the sample bottle and cap lining two or three times with askarel from the transformer; then fill it. When sample will be tested promptly, a clear glass bottle can be used. If sample is to be stored indefin itely, use an amber glass bottle or wrap clear glass with aluminum foil.
Whenever a sample is to be shipped to the transformer manufacturer (or to Monsanto) for complete analysis, the container must be a 5-pmt amber glass bottle. For your convenience, various transformer manufacturers and Monsanto will send you the sample bottle filled with new asKarel. You simply empty out the new askarel and re-fill bottle with your sample.
HONS Cli960
Vioibimo Content: 30 50 ppm
Moisture Condensation
MONS 072981
THAT'S THE STORY:
veep cm dry... let'em alone!
iiui you might want these storage and handling "tips" to make you a complete transformer askarel expert.
STORE NEW ASKAREL IN A CLEAN DRY PLACE
Keep the 5, 30, or 55 gallon drums dry; turn them over on their sides to keep water off the drum head. (It can be sucked in by the drum "breathing.">
CLEAN UP SPILLAGE
Askarel can, if left standing, attack paint, rubber, or plastics. Absorb it from floors with sawdust, sweep, and then wipe dry. Use a rag wet with mineral spirits if you want to make sure it's ail ('leaned away.
TAKE ORDINARY PERSONAL CARE
Transformer askarel has beet) made, handled and used for over 30 years without causing toxic or other ill effects. Askarel can be handled in the same manner as insulating mineral oil. As with mineral oil, there may be some people allergic to askarel, so pro* longed skin contact should be avoided where possible.
When accidentally spilled or splashed on the skin, askarel does not present an acute hazard nor will it cause serious skin irritation. Simply wash it off with soap and water. If work clothes become impregnated with askarel, they should be removed and washed.
Kye contact may cause temporarily painful irritation but NO PERMANENT DAMAGE to the tissues or sight. Flush the eye with large amounts of water. A drop of castor oil may be put in the eye. As with all eye first-aid, refer to a physician who will treat the eye with an ointment.
Ordinary, infrequent exposure to askarel vapors will not cause any ill effects. However, prolonged exposure to strong vapors should be avoided. If hot fluid is to be handled in a closed or confined area, provide ordinary exhaust ventilation. Harmful concentrations of askarel vapors are easily detectable by the smarting of the nose or eyes.
Should hot askarel (above 100C.) have to be handled in the open m a confined, unventilated area - it is advisable to wear organic canister-type masks as supplied by Mine Safety (' ''btsburgh, l*a.
MGNS 072962
(AS FAR AS EQUIPMENT CAN BE I)
best friend!
Since "askarel" type transformers were first made in 1930, few pieces oi electrical equipment have equalled these "juice controllers" in trouble-free service. The name "askarel" applies to the liquid insulation that fills askarel type transformers. And "askarel" is a general name for a unique kind of chemical classified as a halogenated hydrocarbon. But, don't let this chemical jargon bother you one bit. After you read this little pamphlet, you'll be an EXPERT on operating askarel transformers; you'll know all about this wonder ful liquid -- askarel insulation -- because it's all very simple.
however!
Since many engineers and maintenance operators work with BOTH askarel and transformer "oils," you will want to remember that askarel is different from mineral oil . . . and you'll want to know the simple ways to "check up" on the health of your aakarel transformer.
That's the reason for this pamphlet. First, to tell you that your askarel transformer, in addition to being FI RESAFE, can be the most trouble-free piece of equipment you operate. Second, to give you the few simple facts that will make you an expert on the "whys" and "wherefores" of the easy maintenance. Knowing the facts given on the following pages, you will keep your askarel (and transformer) operating at trouble-free, top performance, year, after year, after year.*
'We own one that has baan operating aa faithfully as a heart hast far 28 yaaral
HCNS 072983
Monsanto a/so supplies:
Pydraul AC Ail synthetic fire-resistant compressor lubricant.
Pydraul
All synthetic fire-resistant hydraulic fluids.
Thermal Fluid Fire resistant. non-vaporizing heat transfer fluid.
Coolanot
Dielectric coolants for high power electronic circuits.
Fluid OS-59 Dielectric for high frequency power transformers.
MONSANTO CNSMtCAL COMPANY