624 Chapter 34 _______ 1945-Guide- face of the supply openings. Often it is hard to get into the duct system, or it is difficult to find sections where the flow would be sufficiently ' uniform. For accuracy the instrument and its application should be checked on a similar approach and grille in thejaboratory before use in the field. Tests have shown that the propeller type anemometer can be used successfully on most of the common types of supply grilles23,24. The.core, area is divided into equal squares, and the anemometer is held against the face of the grille for the same length of time in each. To get the air volume in cubic feet per minute, the average corrected velocity in feet per minute thus obtained is multiplied by. the average of the gross and net ' free area of the grille (core) in square feet. On exhaust openings, the anemometer traverse is made as described, previously. The air volume may be determined by multiplying the . corrected velocity in feet per minute by the gross core area of the grille in square feet and by a coefficient for average conditions of 0.8525. When a propeller type anemometer is held in a stream of varying velocities, it tends to indicate higher than the true average, that is, the speed of the propeller is nearer to the top velocity in its area than it is to the minimum velocity. This is the main reason for the large difference in ratings of unit ventilators by the anemometer method and by air volume measurements in a duct approach to the inlet2". Any of the other anemometers described can be used within their range at the face of supply grilles when properly applied. In principle it is a case of finding the velocity at many points and using the average thus found with the correct discharge area at that cross-section. The deflecting vane anemometer equipped with a jet on the end of a rubber tube has been found especially convenient and accurate on supply grilles27. On modem air conditioning grilles the core area is used without a cor rection coefficient when the jet is held one inch away from the face of the grille. At this distance the constriction due to the thin bars has disappeared since the small air jets have reunited, and the air stream has not yet spread beyond the core dimensions. With deflecting grilles the exploring jet should be turned to the angle giving a maximum reading. With suitable traversing tips and calibration, this instrument may also be used on exhaust grilles if proper grille factors are applied28. While hardly a quantitative instrument, smoke is very useful in studying air streams and currents. The application of a more accurate instrument is often made more exact by a preliminary exploration with smoke. A mixture of potassium chlorate and powdered sugar in equal portions gives a very satisfactory non-irritating smoke. It is fired by a match, and since considerable heat is evolved, it should be placed in a pan away from inflammable objects. **A.S.H.V.E. Research Reports Nos. 857, 911 and 966--Measurement of the Flow of Air Through Registers and Grilles, by L. E. Davies CA.S.H.V.E. Transactions. Vol. 36. 1930. p. 201, Vol. 37, 1931, p. 619. and Vol. 39. 1933. p. 373). "A.S.H.V.E. Research Report No. 1162--Air Flow Measurements at Intake and Discharge Openings and Grilles, by G. L. Tuve and D. K. Wright. Jr. (A.S.H.V.E. Transactions, Vol. 46,1940, p. 313). "A.S.H.V.E. Research Report No. 1092--The Flow of Air Through Exhaust Grilles, by A. M. Greene, Jr. and M. H. Dean (A.S.H.V.E. Transactions. Vol. 44, 1938. p. 387). "A.S.H.V.E. Research Report No. 936--Investigation of Air Outlets in Class Room Ventilation, by G. L. Larson, D. W. Nelson and R. W. Kubasta (A.S.H.V.E. Transactions, Vol. 38. 1932, p. 463). "A.S.H.V.E. Research Report No. 1076--Air Distribution From Side Wall Outlets, by D. W. Nelson and D. J. Stewart (A.S.H.V.E. Transactions, Vol. 44,1938, p. 77). "Measuring Air Flow, by G. L. Tuve (Heating, Piping and Air Conditioning, December, 1941). --Instruments?arid'Test Methods 625 AIR CHANGE MEASUREMENTS Atmospheric air contains a certain amount of carbon dioxide. Its concentration is increased within enclosures by the carbon dioxide given off by occupants. The total air change through open windows, infiltra tion, and mechanical ventilation, may be measured by the carbon dioxide concentration29. Since occupants also give off moisture, the increase in humidity may also be used as an index of ventilation within a space. Neither method is used at the present time, and more direct methods of measuring air supply and air distribution are in favor. MEASUREMENT OF RELATIVE HUMIDITY _Wet- and dry-bulb mercurial thermometers are usually used to deter mine relative humidity. The sling psychrojneter is a common mounting of the thermometers to permit swinging. The wet-bulb wick and water for wetting it must be clean, and the temperature of the water should preferably be slightly above the wet-bulb temperature. An air stream velocity of 900 fpm is recommended, although velocities from 300 fpm to 1000 fpm have been found satisfactory for passage over the wet-bulb wick. The velocity may be obtained by whirling the thermometer or by aspirating air over the wet-bulb. In ducts, the air flow itself gives the proper evaporating conditions. Several observations should be made until the minimum temperature is reached. Relative humidity may be obtained from tables or psychrometric charts39. Although it is common practice to use the charts which are based on a barometric pressure of 29.92 in. Hg, a correction for barometric pressure is necessary for extreme accuracy. This correction is made by multiplying the relative humidity as determined from the chart by the ratio of the observed barometric pressure and the standard barometric pressure. . For temperatures below 32 F, the water on the wick is allowed to freeze, during which time the temperature will drop below the true wetbulb. A thin film of ice is more desirable than a thick one, and it is satisfactory to remove the wick and freeze a thin film directly on the bulb. Care must be taken to read the temperatures accurately due to the slight wet-bulb depressions. Tables for ice conditions must be used31. The dew-point apparatus for humidity measurements consists of a polished plated container cooled by the evaporation of a volatile liquid within. The temperature at which the first slight water vapor forms is the dew-point. If the temperature is below 32 F, the deposit will appear as frost. Another method of determining humidity is by chemical means in which the water vapor is removed by a drying agent and weighed on a chemical balance. A thermal conductivity method is available for temperatures above 212 F or for extremely low humidities82. DUST DETERMINATION The measurement of dust is complicated by the many kinds involved. Some of the collecting methods are impingement on viscous surfaces, "A.S.H.V.E. Research Report No. 959--Indices of Air Change and Air Distribution, by F. C. Houghten and J. L. Blackshaw (A.S.H.V.E. Transactions, Vol. 39. 1933, p. 261). ... *PsychTometric Tables for Vapor Pressure, Relative Humidity and Temperatures of the Dew-Point W- S. Department of Agriculture. Weather Bureau, Washington, D. C.). A Review of Existing Psychrometric Data in Relation to Practical Engineering Problems, by W. H. turner and C. O. Mackey (A.S.M.E. Transactions, January. 1937, p. 33; Discussion, A^.M.E. Trans actions. August, 1937, p. 528). nGas Analysis by Measurement of.Thermal Conductivity, by H. A. Daynes (Cambridge Press. 1933).