CHAPTER 18
1946 Guide
The National Warm Air Heating and Air Conditioning Association
recommends empirical equations similar to Equations 2, 3 and 4 for'
gravity furnaces, except that a constant of 2265 is used in place of
the 1785.
-
The following testing and rating codes have been generally accepted,
in the industry:
,.
Commercial Standards CS-100-44 for -rating solid fuel-burning, forced-air furnaces having bonnet outputs of 80,000 Btu per hour or less. This provides a method of rating small coal-fired forced-air furnaces by test.
A Tentative Code for Testing Oil-Fired Furnaces. This code has been adopted by the
National Warm Air Heating and Air Conditioning Association for rating oil-fired fur
naces by test.
'
The American Gas Association method of rating gas-fired furnaces based upon per formance under tests. This is described in the Approval Requirements for Central Heating Gas Appliances.
Commercial Standards 118-44 is a method of rating oil-burning floor furnaces by test.
Commercial Standard CS 104-48 is a method of rating warm air furnaces equipped' with pot-type oil burners by test.
Various codes covering the construction and performance of appliances as related to
fire hazards'have been developed by Underwriter Laboratories, Inc. In addition, there sire many municipal codes 10 which regulate construction and installation of furnace equipment.
The Yardstick of the National Warm Air Heating and Air Conditioning Association provides criteria for evaluating a furnace design and installation against. industry accepted standards.
FURNACE EFFICIENCY .
V
Rating formulae of the National Warm AirHeating and Air Conditioning
Association are based on 55 per cent efficiency for gravity coal furnaces
arid 65 per cent efficiency for forced air coal furnaces. In the tentative-
Oil Testing Code the contemplated minimum efficiency is 70 per cent
for oil fired forced air furnaces. Gravity gas furnaces approved by the.
American Gas Association are assigned a rating based on '75 per cent:
efficiency. Ali forced air gas-fired furnaces approved by American. Gas
.Association are assigned a rating based on 80 per cent efficiency.
DESIGN CONSIDERATIONS
Considerations of prime importance in the design of warm air fur naces and some general suggestions to be observed in connection with' each are as follows:
1. Adequate heat transfer surface.
a. Heat transfer rates of 2,000 to 4,500 Btu per (hour) (square foot) of heating surface may be obtained without unduly high metal temperatures. .
b. Fins, pins and bosses are frequently used to add surface and to break down superficial gas films, both on gas-to-metal and metal-to-air surfaces.
c. Surface and stack (flue gas) temperatures are good indications of the amount and effectiveness-of the heating surfaces.
. 2. Safe and efficient combustion offuel.
a. Proper mixture of fuel and air is'necessary for efficient combustion. This necessitates careful attention to the design of grates, nozzles, burners, air inletareas and location, and combustion chamber baffling.
b. Regulation of the quantity and the distribution of the air for combustion should be provided by use of check dampers, draft regulators, draft hoods, air shutters and air orifices.
Heating Boilers and Furnaces
357
c. Total draft loss through appliances should not exceed that available from
chimneys which would normally be obtainable in the size of building which the
appliance will supply with heat.
.
'
d. The use of ignition safety devices such as safety pilots, hold-fire controls, and the like is recommended.
3. Fuel Capacity of Appliance.
a. With solid fuels adequate coal capacity should be provided for at least 5 hr of operation at the maximum rated combustion rate.
4. Adequate circulation of air over heating surface.
a. In gravity furnaces, free air space between casing and heat exchanger should be great enough to permit free flow over all surfaces.
b. Forced air furnace design must include fans having proper capacity and having performance characteristics.' Internal static pressures must be minimized without losing the advantages of high velocity circulation over the heat exchanger surfaces.
c. The air flow over the heating surface must be directed to obtain maximum efficiency and. to eliminate hot spots and air noises. .
d. Air velocities at bonnet should not be much in excess of 1,000 fpm and air
temperature distribution at the furnace outlet should be uniform within approxi-
mately 30 deg.
,,
5. Durability.
a. A minimum metal weight for gas-fired heat exchangers is established at No. 20
U. S. Gage for plain carbon steel by the A .G.A . Approval Requirements for Central Heating Gas Appliances with some municipal codes specifying 18 gage. Cast-iron
sectional thicknesses of in. to % in. are recommended.
b. Added strength and reinforced designs may be required to preclude damage in shipment, burning out from overfiring, or corrosion from condensation.
c. Maximum heat exchanger surface temperatures which, may be used vary with
the metal. The American Gas Association Approval Requirements for Central
Heating Gas Appliances specify a maximum of 875 F for cast-iron or steel gas
furnaces, and the Bureau of Standards CS 109-44 Code for-Forced Air Solid
Fuel-Burning Furnaces specifies 1000 F-as a maximum surface temperature.
These temperatures define the range in which oxidation of non-alloy ferrous metal
begins. The use of proper alloy additions increases the temperature resistance
properties of metals.
^-
d. Casing temperatures should be controlled so that they do not become hazards to bum those who touch them, or to create fires.
6. Serviceability.
a. Those parts of the furnace which may be subject to soot, fly-ash, or conden sation deposits, should be accessible for cleaning.
b. Parts which may require adjustments or replacements, such as grates, baffles, liners, controls, should be removable.
c. Furnaces should be so designed that they can be installed with a minimum of difficulty.
7. Control.
a. Thermostatic controls of various types should be used to correlate space tem peratures with unit operation.
b. Controls should be provided wherever possible, to prevent the occurrence of excessive temperatures or other conditions in any part of the unit which might cause unsafe operation.
8. General design considerations.
a. Furnace casings are normally constructed of formed and painted sheet steel or of galvanized iron. The casing should be protection from.excessive radiation losses and temperatures by use of insulation or sheet steel air space liners. Liners should extend from the grate level to the top of the furnace and should be spaced from 1 in. to in. from the outer casing.