BUSINESS I UMK>n I CAH*I CONFIDENTIAL INDUSTRIAL HYGIENE MONITORING FOR Asbestos TO; W. T. Shelton, 704 cc: T. L. Collins, 740-2318 C. P. Maxwell, 725 Computer Ref. W1764 Date April 12, 1985 R. G. Rowe, M. D., 791 C. L. Ruddle, 704-202 PERSON MONITORED Location R. E. Raines , Bldg. 701-Basement . Date April 11, 1985 EXPOSURE RESULTS ; Sample No. Cone. Sampling Time 1 1.3 fibers/cc 63 min. Comments Personal sample: Collected on filter cassette. Time-Weighted Average Concentration (TWA) Ceiling Concentration ALLOWABLE EXPOSURE (8 Hr.) TWA 2 fibers/cc X 0SHA UCC Other Ceiling 0SHA UCC Other COMMENTS R. E. Raines was monitored while stripping approximately 12 ft. of old insulation from 3/4" steam line just outside the telephone room in the basement of Bldg. 701. While stripping the insulation, Mr. Raines wore a disposable respirator, coveralls, gloves, and shoe covers. The area was barricaded, signs posted, and a portable water sprayer was used to wet down the insulation. Evaluation of the sample indicated a level of asbestos fibers less than the allowable exposure limit. However, the fiber concentration was higher than expected for this type of job. It is possible that the insulation was not wetted down thoroughly enough prior to removal due to the fact that some of it was difficult to reach. Please notify employee of exposure results. WORK BY % M. F. Stowers APPROVED BY ^ M. A. Patel UCC 024172 [ UNION BUSINESS [CAB BID* CONFIDENTIAL INDUSTRIAL HYGIENE MONITORING FOR TO: W. T. Shelton, 704 Shop ASBESTOS FILE COPY Computer Ref. W-1314 Date April 22, 1982 cc: R. E. Peele, 701-334 / R. G. Rowe, M.D., 791 PERSON MONITORED __________________________ R. E. Raines_______________________ Location Bldg. 704 Powerhouse - 1st Level and Basement EXPOSURE RESULTS Sample No. Cone, Sampling Time Date 04/14/82 Comments 1 0.13 fibers/cc 2 Hrs. 15 Mins, Personal sample - collected on filter cassette 2 3 4 5 6 Time-Weighted Average Concentration (TWA) Ceiling Concentration 0.04 fibers/cc ~ ALLOWABLE EXPOSURE (8-Hour) TWA Ceiling 2 fibers/cc X OSHA OSHA ____ UCC UCC Other Other COMMENTS Mr. Raines was monitored for exposure to asbestos fibers while stripping old insulation from steam lines at several different locations on the first level and base ment of the Powerhouse. Total length of insulation removed was approximately 15 feet. Mr. Raines wore a disposable respirator, coveralls and used a water spray caimister to wet insulation down. Mr. Raines did not work with asbestos beyond the indicated sampling time. Please report results to employee. ORK BY A, <j~\ , Mario F. Stowers nAPPROVED BY Manhar A. Patel UCC 024173 CONFIDENTIAL INDUSTRIAL HYGIENE MONITORING FOR TO: W. T. Shelton, 704 Shop ASBESTOS HE COPY Computer Ref. W-1274 Date Feb. 1, 1982 cc: b. H. Avashia, M.D., 23-512 J. R. Hall, 8745-514 L. R. Noble, 511-2149 M. A. Patel, 701-330 D. R. Paugh, 511-2009 R. E. Peele, 701-334 R. G. Rowe, M.D., 791 PERSON MONITORED P. J. Agosti Location 704 Powerhouse Date 1/26/82 EXPOSURE RESULTS Sample No. Cone. 1 3.08 fibers Ft urn /r* 2 3 Sampling Time 26 Minutes Comments Personal sample 4 5 6 Time-Weighted Average Concentration (TWA) Ceiling Concentration ALLOWABLE EXPOSURE TWA 2 fibers > 5 gm/cc Ceiling - X OSHA OSHA ____ .UCC UCC ____ Other Other COMMENTS Personal samples were collected while Mr. Agosti and Mr. Wheeler were stripping insulation from aerator and connecting lines on the second level in 704 Powerhouse. The levels of asbestos fibers found were in excess of OSHA standard of 2 fibers >5 pm/cc. We recommend the insulators continue to wear protective clothing, respirators, gloves and the area to be stripped wet down. Please inform IH Department of the next stripping job in this area and inform concerned employees of their exposure. WORK BY M. E. Bell APPROVED BY UCC 024174 W. Bott CONFIDENTIAL INDUSTRIAL HYGIENE MONITORING FOR TO: W. T. Shelton, 704 Shop ASBESTOS FILE COPY Computer Ref. Iff-1274 Date Feb. 1, 1982 cc: B. H. Avashia, M.D., 23-512 J. R. Hall, 8745-514 L. R. Noble, 511-2149 M. A. Patel, 701-330 D. R. Paugh, 511-2009 R. E. Peele, 701-334 R. G. Rowe, M.D., 791 PERSON MONITORED W. G. Wheeler Location 704 Powerhouse Date 1/26/82 EXPOSURE RESULTS Sample No. 1 2 Cone. 3.6 fibers >5 jim/cc 3 4 5 6 Sampling Time 28 Minutes Comments Personal sample Time-Weighted Average Concentration (TWA) Ceiling Concentration ALLOWABLE EXPOSURE TWA 2 fibers >5 pm/cc Ceiling ~ ____________ J_OSHA ____ OSHA ____ UCC UCC ____ Other Other COMMENTS Personal samples were collected while Mr. Agosti and Mr. Wheeler were stripping insulation from aerator and connecting lines on the second level in 704 Powerhouse. The levels of asbestos fibers found were in excess of OSHA standard of 2 fibers <5 pm/cc. We recommend the insulators continue to wear protective clothing, respirators, gloves and the area to be stripped wet down. Please inform IH Department of the next stripping job in this area and inform concerned employees of their exposure. WORK BY ` M.E. Bell APPROVED BY UCC 024175 G. W. Bott